ECB03/12/2026FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED DRYERS CONNECTED WITH NON-COMPLIANT FLEXIBLE HOSES IN VIOLATION OF RCNY 5-16. FURTHER OBSERVED A REDUNDANT PLUG CONNECTION$6K due
ECB02/17/2026CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION$1K due
HPD10/20/2025§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE ...RUBBER GASKET AT REFRIDGERATOR DOOR IN THE KITCHEN LOCATED AT APT 5H, 5th STORY, 4th APARTMENT FROM SOUTH AT WEST
HPD10/20/2025§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ...AT WEST WALL WINDOW FRAME IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 5H, 5th STORY, 4th APARTMENT FROM SOUTH AT WEST
HPD10/20/2025HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5H, 5th STORY, 4th APARTMENT FROM SOUTH AT WEST
ECB08/06/2025CLASS 2:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION,ELEVATOR IS NOT RESPONDING TO CALLS ( IN-CAR )TO 5TH,4TH AND BASEMENT FLOORS W$3K due
HPD04/07/2025§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT WASH BASIN IN THE BATHROOM LOCATED AT APT 6H, 6th STORY, 5th APARTMENT FROM SOUTH AT WEST
DOB12/11/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB11/25/2024PARTIAL VACATE ORDER DUE TO HAZARDOUS CONDITIONS SUCH AS BULGING PARAPET WALL, SPALLING MORTAR JOINTS, STEP CRACKING & VERTICAL BRICK CRACKS OBSERVED AT INSPECTION AT EXPOSURE 3 (EAST ELEVATION). REMEDY: VACATE ENTIRE REAR YARD/GARAGE ROOF AT EXPOSURE 3 (EAST ELEVATION) RESTRICT ACCESS TO VACATED AREAS
DOB11/14/2024EWO:WAS OBSERVED AT MULTI LOCAT THROUGH EXP 1,2,3 & 4(W,N,E,&S.ELEV) SPALLING BRICK, DETERIORATED MOTAR JOINTS, CRACKS & STEPCRACKS ON BRIC FACADE, SPALLED BRICKS.@ EXP1 W.ELEV LOOSE BRICK VENEER & LINTEL PUSH -ING OF ANGLES AND BOWING & RUSTED.@ EXP3E.ELEV BULGING PARAP WALL & COMPROMISE FIRE ESCAPES.REMDY:INSTALL SAFETY MEAS UNDER LP @ EXP 1,2&4
HPD08/13/2024§ 27-2005, 2012 HMC & § 309 MDL: ABATE THE NUISANCE CONSISTING OF EXCESSIVE STORAGE OF MATERIAL HOUSEHOLD ARTICLES ETC. IN THE ENTIRE APARTMENT LOCATED AT APT 2H, 2nd STORY, 4th APARTMENT FROM SOUTH AT WEST
HPD05/28/2024§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE BATHROOM LOCATED AT APT 2H, 2nd STORY, 4th APARTMENT FROM SOUTH AT WEST
HPD05/28/2024HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2H, 2nd STORY
HPD05/28/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CONSISTING OF APPROXIMATELY 15 SQUARE FEET AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 2H, 2nd STORY, 4th APARTMENT FROM SOUTH AT WEST
HPD05/28/2024§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND WEST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2H, 2nd STORY
HPD05/28/2024HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2H, 2nd STORY
HPD05/28/2024§ 27-2045, 2046 ADM CODE PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2H, 2nd STORY
HPD05/28/2024§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2H, 2nd STORY, 4th APARTMENT FROM SOUTH AT WEST
HPD05/28/2024§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 2H, 2nd STORY
HPD05/28/2024§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AND WEST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2H, 2nd STORY
HPD05/28/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CONSISTING OF APPROXIMATELY 18 SQUARE FEET AT CEILING AND WEST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2H, 2nd STORY ORIGINAL VIOLATION 17010360 ISSUED 28-MAY-24 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE §27-2017.3a(5)(a) or (b).
HPD05/28/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CONSISTING OF APPROXIMATELY 12 SQUARE FEET AT CEILING AND WEST WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 2H, 2nd STORY, 4th APARTMENT FROM SOUTH AT WEST
DOB01/03/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB12/13/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB05/26/2016SEC: 27-392; 27-393. FAILURE TO MAINTAIN FLR NUMBERING & STAIR LETTERING PER 27-392; 27-393. NOTED: MISSING FLR NUMBERING ALL FLRS & MISSINGSTAIR LETTERING PER 27-392; 27-393. REM: COMPLY W/ CODE.$-997 due
DOB10/01/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2014 INSPECTION REPORT
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2013 INSPECTION REPORT
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
HPD03/20/2014§ 27-2142 ADM CODE APTS HAVE BEEN VACATED BY THIS DEPARTMENT AND CANNOT BE REOCCUPIED UNTIL SO ORDERED AFTER PROOF OF COMPLIANCE FOR APTS WEST 3 CELLAR APT. LLB (VACATE #115031)
DOB10/01/2012VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2011 INSPECTION/TEST
DOB12/13/2011VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2010 INSPECTION REPORT
DOB12/13/2011VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
ECB07/23/2025FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED OBJECTS ON FIRE ESCAPE ON EXPOSURES 1, 3, AND 4. REMEDY: REMOVE OBJECTS FROM FIRE ESCAPE.Nothing owed — awaiting certificate of correction
ECB07/23/2025FAILURE TO MAINTAIN EXTERIOR WALLS FACADE AND APPURTENANCES. OBSERVED DAMAGED MORTAR JOINTS, STEP CRACKS, CRACKED BRICKWORK, SPALLED/SPALLING BRICK WORK IN MULTIPLE LOCATIONS ON ALL EXPOSURES OF THE BUILDING. RNothing owed — awaiting certificate of correction
ECB06/04/2025RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION, DEVICE IS OUT OF ORDER, BY WAY OF CEASE USE ORDER, REMEDY; COMPLY WITH CEASE USE ORDER THEN NOTIFY THE NYCDOB FOR A RESTORE TO SERVICE RE-INSPECTION,Nothing owed — awaiting certificate of correction
ECB05/30/2025RESPONDING TO A 311 ELEVATOR COMPLAINT,UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, FOR A CEASE USE VIOLATION, REMEDY; COMPLY TO CEASE USE ORDERS, AGG 2 VIOLATION WAS ISSUED TO RESPONDENT, NOTE RENothing owed — awaiting certificate of correction
ECB05/19/2025CEASE USE ITEMS: DOOR LOCK MONITORING AND DOOR ZONE RESTRICTOR INOPERATIVE. TOTAL OF (3) CONTROLLER LINE FUSES 10AMP - A/C AND D/C ARE BYPASSED. THESE ARE SAFETY FEATURES WHICH ENSURES PASSENGER SAFETY. REMEDY:Nothing owed — awaiting certificate of correction
ECB05/01/2025RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION THE DEVICE IS FOUND TO-BE-OUT OF SERVICE, AS PER 1RCNY 11-02, THIS DEVICE PROVIDE SERVICE IN A 6 STORY BUILDING,REMEDY. RESTORE TO SERVICE IMMEDIATELY ANDNothing owed — awaiting certificate of correction
ECB02/27/2025I OBSERVED A 6-STORY BUILDING WITH SWS ERECTED EXP#1-4,DURING MY INSPECTION I NOTICED SWS DOESN'T MEET BC3307.6.4.9 AVOID INTERFERENCE. ALSO AS PER SECTION 3307.6.3AREA TO BE PROTECTED. I NOTICED THAT SWS DECKNothing owed — awaiting certificate of correction
ECB01/28/2025FAILURE TO PROVIDE OBSTRUCTED EXIT PASSAGEWAY. NOTE AT TIME OF INSPECTIONS OBSERVED MULTIPLE OBJECTS ON EXP #3 REAR FIRE ESCAPE ON VARIOUS LEVELS AT EXPOSURE #1 OBSERVED OBJECTS ON VARIOUS LEVELS THIS IS A HAZANothing owed — awaiting certificate of correction
ECB01/28/2025FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION OBSERVED DAMAGED MORTAR JOINTS THROUGHOUT THE BUILDING FACADE MULTIPLE STEP CRACKS AT PARAPET LEVEL OBSERVED SPALLINGNothing owed — awaiting certificate of correction
ECB01/23/2025: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNYNothing owed — awaiting certificate of correction
ECB11/14/2024UNLAWFUL ACTS.FAILURE TO COMPLY WITH COMMISSIONER'S ORDER#35686575H REQUIRING THE INSTALLATION OF SAFETY MEASURES AND TO REPAIR DAMAGED FACADE AS PER 1RCNY 103-04 CODE AS WELL AS TO MAINTAIN EXTERIOR BUILDING ANothing owed — awaiting certificate of correction
ECB11/01/2024RESPONDING TO A 311 ELEVATOR COMPLAINT,UPON INSPECTION, CLASS 1 VIOLATION ISSUED FOR, CAR DOOR CLUTCH DEFECTIVE, ALTERED TO LOCK ON TO HOIST WAY DOOR ROLLERS TO PREVENT CAR DOOR FROM SPLIT, TO CHECK DLM. REMEDYNothing owed — awaiting certificate of correction
ECB08/19/2024FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES. AS NOTED:-AT THE TIME OF INSPECTION I OBSERVED ON EXPOSURE #1, 2, 3 AND 4:-ACUNITS INADEQUATELY SUPPORTED ON WINDOW SILLS ON SEVERAL FLOORS. SEVERANothing owed — awaiting certificate of correction
ECB08/19/2024FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES.AS NOTEDAT TIME OF INSPECTION I OBSERVED ON EXPOSURES#1,2,3 & 4 AC UNITS INADEQUATELY SUPPORTED ON WINDOWSILLS AT SEVERAL WINDOWS AND FLOORS:SEVERENothing owed — awaiting certificate of correction
ECB06/25/2024RESPONDING TO A 311 ELEVATOR. UPON INSPECTION IN A SINGLE CAR BUILDING. DEVICE IS STILL UNDER CEASE USE FOR PREVIOUS VIOLATION, REMEDY; REPAIR THEN CONTACT NYCDOB FOR RESTORE TO SERVICE RE-INSPECTION.Nothing owed — awaiting certificate of correction
ECB05/21/2024RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION ON DEVICE IN A SINGLE CAR BUILDING,CEASE USE VIOLATION ISSUED FOR, CAR DOOR RESTRICTOR ALTERED, / OVERHEAD TRACTION SHEAVE HUB BEARING WORN, / DLM NOT WORNothing owed — awaiting certificate of correction
ECB01/17/20245-A-10, 42-L-10, 56-L-10, 99-BB-5. 5-A-10=DOOR ZONE RESTRICT AND TAMPER WITH RENDERED INOPERATIVE BY REMOVING LOCKING PIN AND PLACE IT ON TOP OF CAR; MUST REPAIR IMMEDIATELY, THIS IS A SAFETY DEVICE THAT ENSURENothing owed — awaiting certificate of correction
ECB11/15/2023OCCUPANCY IN CONTRARY TO THAT ALLOWED BY C/O AND/OR DEPARTMENT OF BUILDING RECORD.UNOCCUPIED AND/OR ILLEGALLY CREATED ROOMS AT CELLAR WITH HALF BATHROOM,NO KITCHEN.NO 2ND MEANS OF EGRESS PROVIDED.NO VACATE WARRNothing owed — awaiting certificate of correction
ECB08/16/2023AGGRAVATED II CONDITION. RESPONDENT HAS A HISTORY OF FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDERS. RESPONDENT FAILED TO COMPLY WITH THE COMMISSIONER'S ORDERS TO FILE CERTIFICATES OF CORRECTION FOR 8 OPEN ECNothing owed — awaiting certificate of correction
ECB07/17/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED AT REAR OF DRYERS AT ABOVE PREMISES THE USE OF FLEXI HOSES THAT DO NOT COMPLY WITH CODE (R5-16) ALSO REDUNDANT LINE WILL PLUG CONNECTION BETWEEN GNothing owed — awaiting certificate of correction
ECB06/22/2023FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR VIOLATION#32071829Z AND#32075353K/CORRECT ALL VIOLATING CONDITIONS/SUBMIT CERTIFICATE OFNothing owed — awaiting certificate of correction
ECB06/22/2023AT TIME OF INSPECTION I OBSERVED THAT VIOLATION NUMBERS 34478098L AND 34478099N HAVE NOT BEEN CORRECTED. IN RESULT YOU HAVE FAILED TO COMPLY WITH THE COMMISSIONERS ORDERS., FILE A CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB03/30/2023RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON ON INSPECTION OF THE DEVICE VIOLATION WAS FOUND, CEASE USE ITEM, DLM NOT WORKING, REMEDY; REPAIR THEN CONTACT NYCDOB FOR RESTORE TO SERVICE RE-INSPECTION, 2/ IN CARNothing owed — awaiting certificate of correction
ECB07/26/2022CLASS 1 VIOLATION ISSUED DLM IMPROPERLY IN STALLED ON DEVICE. NO FIREMAN SERVICE PRESENT IN CONTROLLER, IN STALL FIREMAN SERVICE SO DLM IS IN COMPLIANCE WITH SECTION 3.10.12 OF APPENDIX K3,.........CLASS 2 VIOLNothing owed — awaiting certificate of correction
ECB04/30/202042M5,11X10:42-M-5=NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLERAS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY:FILE APPLICATIONothing owed — awaiting certificate of correction
ECB05/31/201602L10,05M07,21D10,30M11,97X10Nothing owed — awaiting certificate of correction
ECB06/22/2015B254,16,22C,24B,50,50A/50B,50C,50D,50E,50F,50G,50H. 50-GAS PILOT REGU LATOR DEFECTIVE; 50A-OIL LEAK AT BURNER; 50B-OIL PUMP BELT GUARD NOT IN PLACE; 50C-CONDENSATE TANK VENT REDUCED; 50D-2"NIPPLE AND CAP RTNothing owed — awaiting certificate of correction
ECB11/07/201428-210.1 MULTIPLE DWELLING CONVERTED, MAINTAINED OR OCCUIPED W/3 OR MORE DWELLING UNITS THAN LEGALLY AUTHORIZED BY THE CERT. OF OCCUPANCY OROFFICAL RECORDS. NOTED : C.O. # 42584 INDIATES LEGALLY APPROVED FOR 89Nothing owed — awaiting certificate of correction
ECB11/03/201428-212.11 VIOLATION OF CLOSURE ORDER AT TIME OF INSPECTION. CELLAR NORTHWEST APT. DOOR REMOVAL OF ACTIVE VACATE 85/2014. APT. DOOR HAS THE REMAINS OF THE VACATE STICKER SCRAPED ON THE DOOR. REMEDY: COMPLY W/ THNothing owed — awaiting certificate of correction
ECB07/21/2014OCCUPANCY IN CONTRARY TO THAT ALLOWED BY C OF O OF DOB RECORDS.OCCUPIED ILLEGAL CLASS "A"APT CREATED @ CELLAR WITH FULL BATHROOM & A KITCHEN PARTITIONS MADE UP OF WOOD/METAL STUD & SHEET ROCK/PLASTER.VACATE WARNothing owed — awaiting certificate of correction
ECB02/29/2012B254,34A,46B,48A,50A,B. 50A- FRESH AIR INTAKE BLOCKED, 50B- IMPROPER STORAGE OF FUEL OIL IN OPEN CONTAINER. REPAIR/REPLACE ALL DEFECTIVE BOILER PARTS & FILE A C/C ATTACHED.Nothing owed — awaiting certificate of correction
ECB12/19/201114L10,8V1,21I11,44H8,44H11,52H11,57H10,60Q3,100M7,72M7: 57;HOIST MOTORBEARINGS. 100;COMMUNCATION IN CAB.Nothing owed — awaiting certificate of correction
ECB02/11/200941G11.60T15.68M7.98BB5.99BB5.44H11.44H9.51H11.60Q3.24B10.29Q3.17H11.28B1.32O2.33O2.34O2.36O2.39O2.40O2.42O2.70O2.73O2.74O2.77O2.24 BSMT INDICATOR 17 BSMTNothing owed — awaiting certificate of correction
ECB01/05/200714M07/10H10/86U05/43H08/05H11/05L10/05E10/17H10.05-CAR DOOR ROLLERS.05L10-REPAIR DOOR CLUTCH ROLLER ARM.17H10-WORN GIBSON(LL OR B)-FLOOR H/DOORNothing owed — awaiting certificate of correction
ECB07/29/2005FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPINKLERS WHERE REQUIRED FOUND (4) COMMERCIAL DRYER WITH NO SPINKLER COVERAGE OVER THEM. REMEDY:PROVIDE AUTOMATIC SPRINKLERSNothing owed — awaiting certificate of correction
ECB07/29/2005USE OR INSTALLATION OF PLUMBING MATERIALS OR EUIPEMENTS WHICH DO NOT COMPLY WITH RS-16 FOUND (4) COMMERICAL DRYEER WITH FLEX HOSE ON BACK OFTHEM REMEDY:REMOVE NON-COMPLYING MATERIAL OR EQUIPEMENTNothing owed — awaiting certificate of correction
ECB09/28/200414M07/57F10/10H10/17H10/67O02/68O02 57- ELIMINATE VERY HARD STOR-ROCKING- AT FLOOR STOPS 17H10-LL-LEVEL (BASEMENT)Nothing owed — awaiting certificate of correction