ECB02/17/2026RE-ISSUED #35691834J. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. AT THE TIME OF INSPECTION, EXTERIOR FACADE HAS BECOME COMPROMISED, ALLOWING WATER TO SEEP IN THE BUILDING AT VARIOUS LOCATIONS CAUSINNothing owed — awaiting certificate of correction
ECB02/17/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: AT THE TIME OF INSPECTION, THE WINDOW AND DOORS IN STAIRWELL TO SECOND FLOOR ROOF AREDETACHING FROM WALL. LINTEL, JAMB AND SILL ARE SEPARATED FROM WALL. RENothing owed — awaiting certificate of correction
ECB02/17/202628-301.1. UNLAWFUL PLACEMENT OF FURNISHINGS, DECORATIONS OR OTHER OBJECTS AT EXITS THAT OBSTRUCT ACCESS TO, EGRESS FROM OR VISIBILITY THEREOF PER FDNY 2008 CODE; FC 1027.4. AT THE TIME OF INSPECTION, THE FOLLOWNothing owed — awaiting certificate of correction
ECB02/17/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: AT THE TIME OF INSPECTION, THE FOLLOWING CLASSROOM DOORS WERE NOT SELF-CLOSING:-414, 413, 402, 406, 400, 404, 401, 402, 317A, 316, 312, 309, 307, 308, 302,Nothing owed — awaiting certificate of correction
ECB02/17/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). AT THE TIME OF INSPECTION, CLASSROOM DOORS THROUGHOUT THE SCHOOL HAS SPHERICAL KNOB/HANDNothing owed — awaiting certificate of correction
ECB02/17/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT THE TIME OF INSPECTION, EMERGENCY LIGHT #2 STAIR 2 AND 3 WAS NOT WORNothing owed — awaiting certificate of correction
ECB02/13/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, MULTIPLE CRACKS AND DELAMINATION OF CONRETE WERE OBSERVED ON THE TOP OF HAND BALL COURT WALL APPROX. 16' HIGH. THE CONCRETE WALLNothing owed — awaiting certificate of correction
ECB02/13/2026RE-ISSUED #35691832X. EXIT DOOR NOT SELF-CLOSING. AT THE TIME OF INSPECTION, THE FOLLOWING EXIT DISCHARBE DOORS WERE NOT SELF-CLOSING PROPERLY:-4, 5, 6, 7, AND 9. REMEDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB02/13/2026RE-ISSUED #35691831Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, WATER INFILTRATION IN THE 4TH FLOOR STAIRWELL #7 CAUSED BULDING AND SPALLING ON WALLS AND COILING. GYM WALNothing owed — awaiting certificate of correction
ECB02/13/2026RE-ISSUED #35691833H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, THE FOLLOWING FPSC SMOKE DOORS WERE NOT SELF-CLOSING:-STAIRWELL #DOORS, CORRIDOR DOORS NEXT TO STAIRWELL 4Nothing owed — awaiting certificate of correction
ECB03/11/2025FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED BUILDINGS EXTERIOR WALLS HAVE BECOME POROUS.ALLOWING WATER INTO INTERIOR SPACES DETERIORATED MORTAR JOINTS & CRACKING NOTED AT SCATTERED LOCATIONS.REM:Nothing owed — awaiting certificate of correction
ECB03/11/2025REISSUE#35678677Z FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED EVIDENCE AT WATER DAMAGE,SPALLING PLASTER ON WALLS & CEILINGS.LOCATIONS STAIR B/C BULKHEAD 4TH FL GYM & EXIT 6 & 7 STAIR.2ND FL GYMNothing owed — awaiting certificate of correction
ECB03/11/2025REISSUE#35663193K EXIT DOOR NOT SELF-CLOSING.NOTED EXTERIOR DOORS AT EXIT#9,6,7,4 & 5 NOT OPENING OR CLOSING PROPERLY.REM:REPAIR/REPLACE DOORS.Nothing owed — awaiting certificate of correction
ECB03/11/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED INTERIOR FPSC SMOKE DOORS NOT OPENING/CLOSING PROPERLY LOCATIONS:3RD FL STAIR B/C,2ND FL STAIR E,1ST FL:EXIT 9 SMOKE DOORS,STAIR E & D,EXIT 4 & 5 SMOKNothing owed — awaiting certificate of correction
ECB03/11/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED SOUTH ROOFIN DISREPAIR,MISSING SECTIONS OF ROOFING INSULATION & GRAVEL EXPOSED SECTIONS OF DETERIORATING INSULATION & LOOSE/DETACHED METAL FLASHING.RENothing owed — awaiting certificate of correction
ECB02/12/2024REISSUE#35663194M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.SPALLING PLASTER & BY GYM 2ND FLOOR,EXIT 6 & 7,EXIT 8,EXIT 9.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB01/24/2023REISSUE #35260607P EXIT DOOR NOT SELF-CLOSING.2ND FL THROUGHOUT AUDITORIUM BTWN 1ST & 2ND FL EXIT #9, #6, #7.REMEDY:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB01/24/2023REISSUE #35383913N:FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:SPALLING & CRACKED PLASTER @14TH FL NEAR RM #617, 3RD FL 313, 2ND FL GYM & EXIT #8.REMEDY:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB03/04/2022REISSUE35548339K NOTED:@4FL GYM STAIRWELL BY EXIT6&7,2FL GYM@EXI8&1FL BY EXIT9,ALL HAVE SPALLING PAINT&CRACKS IN VARIOUS AREAS THRUOUT.REPAIR &OR REPLACENothing owed — awaiting certificate of correction
ECB03/04/2022REISSUE35548341J NOTED:@4FL GYM ENTRANCE BY EXIT4&5,3FL SMOKE BY STAIRB,2FL SMOKE BY 215,SMOKE BY STAIRB,1FL SMOKE BY EXIT9&EXTERIOR DOOR AUDITORIUM MAIN ENTRANCE,1FL SMOKE@STAIRE,BSMT SMOKE@EXIT6&7,BSMT ENTRANNothing owed — awaiting certificate of correction
ECB03/02/2021REISSUE#35467684R-NOTED:AT THE 4TH FLOOR EXIT#11 BY 404,2ND FLOOR BY THE ELEVATOR,STAIR C BY 213,1ST FLOOR STAIR E BY 114,SMOKE DOOR TO 1ST FLOOR LOWER LEVEL BY THE AUDITORIUM,1ST FLOOR SMOKE BY EXIT#9,AUDITORINothing owed — awaiting certificate of correction
ECB03/02/2021REISSUE#35467686K-NOTED:AT THE 4TH FLOOR GYMNASIUM BY UNIT 6 AND 7,3RDFLOOR ROOM 313,2ND FLOOR GYMNASIUM AT EXIT 8 AND 1ST FLOOR BY EXTERIOREXIT DOOR #9;ALL HAVE SPALLING PAINT AND CRACKS IN VARIOUS AREAS THROUNothing owed — awaiting certificate of correction
ECB02/06/2020REISSUE#35383913N DATE OF ISSUE:02-08-2019.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIMANT MANNER SPALLING AND CRACKED PLASTER AT 4TH FLOOR NEAR EIXT 617 DOOR WAY 3RD FLOOR ROOM 313 CEILING 2ND FL GYM AT EXIT 8Nothing owed — awaiting certificate of correction
ECB02/06/2020REISSUE #35381220L DATE OF ISSUE 02-08-2019.EXIT DOOR NOT SELF CLOSING AT FIRST FLOOR EXIT-9(OUTSIDE)ONE DOOR FROM LOBBY RIGH TSIDE ONE DOOR & 2ND FLOOR STAIR CASE-C EXIT 3 ONE DOOR NOT SELF CLOSING PROPERLY ATNothing owed — awaiting certificate of correction
ECB07/19/2019FOUND UNREGISTERED LOCHINVAR AWN501PM BOILER IN BOILER ROOM., MAINTAIN BOILER; REGISTER BOILERNothing owed — awaiting certificate of correction
ECB02/08/2019REISSUE #35311974Y DATE OF ISSUE 01-29-2018 EXIT DOOR NOT SELF-CLOSING,AT FIRST FLOOR MAIN ENTRANCE ONE EXIT DOOR NOT SELF CLOSING PROPERLY AT 2ND FLR EXIT NEXT TO ELEVATOR.AUDITORIUM BETWEEN 1ST AND 2ND FOOR NNothing owed — awaiting certificate of correction
ECB02/08/2019REISSUE: 35317536L DATE OF ISSUE 01.29.2018. FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER SPALLING AND CRACKED PLASTER AT 4TH FLOOR NEAR EXIT 617 DOORWAY 3RD FLOOR ROOM 313 CEILING 2ND FL GYM AT EXT 8 ANDNothing owed — awaiting certificate of correction
ECB01/29/2018REISSUED 35260607P/EXIT DOOR NOT SELF CLOSING:NOTE AT 2NF FLR EXIT NEXT TO ELEVATOR AUDITORIUM BETWEEN 1ST AND 2ND FLR DOOR NOT CLOSING ALSOEXIT DOORS AT EXIT 9 FOR RIGHT HAND SIDE AND EXIT 6 & 7 FOR LEFT HANDNothing owed — awaiting certificate of correction
ECB05/03/2017EXIT DOOR NOT SELF CLOSING. NOTED AT 2ND FLR EXIT NEXT TO ELEVTOR,AUDITORIUM BETWEEN 1ST AND 2ND FLR, HALL FLAGS EXIT 9 HAVE SOME DOORS THATARE NOT SELF CLOSING. ALSO OBSERVED AT THE BASEMENT EXIT 6/7 BY EMERGNothing owed — awaiting certificate of correction
Public elementary, junior or senior high · Owner of record: NYC DEPARTMENT OF EDUCATION · 100,000 sf lot · 1.75 FAR built · Flood zone X