ECB12/26/2014FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS,WORK SPACE ABOUT ELECTRICAL EQUIPMENT. OBSERVED AT 1:45PM THAT ACCESS TO MAIN SERVICE DISCONNECT SWITCH & CIRCUIT BREAKER PANEL,METER IS OBSTRUCTED BY STORAGE MIN 3Nothing owed — awaiting certificate of correction
ECB12/26/2014ELECTRICAL WORK W/O PERMIT. ELECTRICAL WIRING INSIDE & OUTSIDE PRIOR TO OBTAINING PERMIT. BRACH CIRCUITS,FLUORESCENT FIXTURES,SWITCHES RECEPTICLE OUTLETS,MOTORS,CONTROL WIRING,OBSERVED SAID VIOLATIONS AT 1:45PMNothing owed — awaiting certificate of correction
ECB12/26/2014FAIL TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS,ENCLOSURES,CABLE ARMOR. OBSERVED AT 1:45PM THAT ARMORED CABLES ARE OPEN SPLICE BOX TO METERIZAL GATE MOTORS. GATES & MOTORS ARE NOT GROUNDED &Nothing owed — awaiting certificate of correction
ECB12/26/2014UNAPPROVED/UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. AT 1:45PM OBSERVED OUTSIDE UNDER CANOPY INDOOR FIXTURES USED OUTDOORS. NOT APPROVED FOR (DAMPER)WET LOCNothing owed — awaiting certificate of correction
ECB12/23/2014SEC. 400.8 MISC. VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS 1:45PM OBSERVED FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD FOR BRANCH CIRCUITS & POWER TO MOTORIZED GATE MOTORS FOR BRANCH CIRCUITS ANDNothing owed — awaiting certificate of correction
ECB12/23/2014LUMINAIRES(FIXTURES)& LAMP HOLDERS NOT INSTALLED IN AN APPROVED MANNER. AT 1:45PM OBSERVED THAT FLURESENT FIXTURES TRU-OUT STORE IS NOT INSTALLED IN APPROVED MANNER W/APPROVED MATERIAL,FIXTURES USING LIGHT CHAINothing owed — awaiting certificate of correction