HPD10/07/2024§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES, DOOR LEAD FROM VESTIBULE TO PUBLIC HALL AT PUBLIC HALL, 1st STORY
HPD06/02/2005SECTION 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ENTRANCE DOOR TO BLDG AT FRONT AREAWAY
ECB04/14/20153-B, 39, 50A, 50B,51. 50A-BOILER HAS EVIDENCE OF OVERHEATING DUE TO COMBUSTION AND DRAFT PROBLEMS. INDICATION OF FLAME ROLLOUT AND HEAVY SOOT BUILDUP CONDITION (CON EDISON RED TAG BOILER DUE TO UNSAFE CONDITNothing owed — awaiting certificate of correction
ECB04/14/20153B,50A,50B,51. 50A-HEAVY SOOT CONDITION CAUSE BY DEFECTIVE OIL BURNER;50B-DEFECTIVE FLUE PIPE FUMES IN BASEMENT; 51-CEASE USE BOILER DO NOT OPERATE UNTIL ALL REPAIRS ARE MADE AND DOB REINSPECTS FOR COMPLIANCE.Nothing owed — awaiting certificate of correction
ECB04/13/2015FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER-COMMERCIAL COOKINGEQUIPMENT EXHAUSTING INTO RESIDENTIAL CHIMNEY INSP TIME 10:20AM ON 4/13/15 I OBSERVED IN BAKERY ON 1ST FL GAS EXHAUST TIED INTO SAME CHIMNEYNothing owed — awaiting certificate of correction
ECB01/21/200950A, 50B, 50C, 50D, 50E, 51. 50A- OPEN FLAME EXPOSED OUTSIDE OF COMBUSTION AREA DUE TO ONE BURNER ASSEMBLY MISSING. 50B- REPLACE ENTIRE FIRERATED CEILING IN BOILER & ROOM DUE TO CORROSION FROM WATER LEAKS. 50C-Nothing owed — awaiting certificate of correction
ECB07/25/200750A/50B/.50A-DIRTY BOILER ROOM,DIRT,WATER & STORAGE OF METAL & WOOD UNABLE TO PERFORM A PROPER INSPECTION OF BOIELR DUE TO THESE CONDITIONS.50B-POOR LIGHTING IN BOILER ROOM.Nothing owed — awaiting certificate of correction
ECB06/14/19933ANothing owed — awaiting certificate of correction
Single or multiple dwelling with stores or offices · Owner of record: SAM HOLDING NY LLC · 6,375 sf lot · 1.34 FAR built · Flood zone X