ECB06/09/2026Reissue#35720843L failure to maintain building in code compliant manner.noted:the surface of the tennis court at atletic field is indisrepair.large cracks at various locations.rem:repair/replace surface.Nothing owed — awaiting certificate of correction
ECB06/09/2026Failure to maintain building in code compliant manner.noted:at the electric meter,there was storage of combustible materials.mostly cardboard panels and other combustibles.rem:remove all storage from electric mNothing owed — awaiting certificate of correction
ECB08/25/2025@PS721=burnham boiler#2 has gas piolit regulator missing vent limiter+has corroded safety valves@steam>hot water heat exchangers+has defective motorized combustion air louvers;correct violation+submit certificaNothing owed — awaiting certificate of correction
ECB08/25/2025@john dewey hs pacific national boiler#4 is inoperable+has defective fusible link@oil valve;correct violation+submit certificate of correctionNothing owed — awaiting certificate of correction
ECB08/25/2025@john dewey hs pacific national boiler#1 has oil leak@burner+fusible link@oil valve is defective+boiler water chemical feed tank corroded with temporary patch;correct violation+submit certificate of correctionNothing owed — awaiting certificate of correction
ECB08/25/2025@john dewey hs pacific national boiler#2 has oil leak@burner+has defective fusible link@oil valve+incorrect backflow valve installed@vac system water feed;correct violation+submit certificate of correctionNothing owed — awaiting certificate of correction
ECB08/14/2025Failure to maintain building in code-compliant manner. Hallway/corridor door roof to 318, 2ND floor next 244 staircase 4 2 floor and staircase 2, 2 floor not self-closing. Remedy: repair and/or replace.Nothing owed — awaiting certificate of correction
ECB08/14/2025Failure to maintain building in code-compliant manner. Observed athletic field walkway and tennis court with large cracks at various locations. Remedy: repair and/or replace.Nothing owed — awaiting certificate of correction
ECB07/08/2022@PS721=gas piolit regulator missing vent limiter;correct violation and submit the certificate of correctionHearing held — result not yet published$500 proposed
ECB07/08/2022@john dewey=top left handhole leaking/body drain discharge pipes missing at safety valves;correct violation and submit the certificate of correctionHearing held — result not yet published$500 proposed
ECB07/08/2022@john dewey=hot water storage tanks the safety valves are defective/body drain discharge pipes missing at boiler safety valves;correct violation and submit the certificate of correctionHearing held — result not yet published$625 proposed
ECB07/08/2022@john dewey=boiler draft inducer belt defective;correct violation and submit the certificate of correctionHearing held — result not yet published$625 proposed
ECB06/22/2022@PS721=new combustion air fan motor not wired/rear flame sight glass defective/wires exposed@electric space heater/discharge pipes missing@hx safety valves;correct violation+submit certificate of correctionHearing held — result not yet published$625 proposed
ECB06/22/2022Cease use aosmith hot water heater@PS721@64 ave x=holes in flue pipe/circulator improperly installed/base of chimney not accessible for inspection and cleaning/, maintain boiler; correct all hazardous conditionHearing held — result not yet published$1K proposed
ECB11/16/2016100M7,80M7,2X10,13I10. 100M7-brake maintenance tag; 80-M7-counterweights clearance sign, 2X10-phone inoperative; 13I10-emergency light damaged.Nothing owed — awaiting certificate of correction
ECB11/16/201218M07,05X10,60Q03,16D06,52M07,50H11. 18M-provide PERK3;05X-zone lock restroom;16D-3FL sightguard;52M-missed crosbies;50H-noise bearing.Nothing owed — awaiting certificate of correction
ECB11/16/201242G11,60Q03,52K10,18M07,05X10. 42G-unreadable fuses; 52K-provde developing;18M-provide PERK3;05X-zone lock restroomNothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB06/20/2023Violation issued-failure to file 2018 external low pressure inspectionAnswered on the city's records: a 2018 boiler inspection report was accepted (Aug 13, 2018)
DOB04/05/2019Violation issued to elevator - failure to file category 1 2017 inspection/testThe owner has filed since: Category 1 elevator reports are on file for later years (latest 2026). This one is not shown as answered
DOB01/26/2018Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tstThe owner has filed since: Category 1 elevator reports are on file for later years (latest 2026). This one is not shown as answered
DOB01/03/2017Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tstThe owner has filed since: Category 1 elevator reports are on file for later years (latest 2026). This one is not shown as answered
DOB11/14/2016Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tstThe owner has filed since: Category 1 elevator reports are on file for later years (latest 2026). This one is not shown as answered