DOB05/17/2021V-DOB VIOLATION - ACTIVE
DOB05/17/2021V-DOB VIOLATION - ACTIVE
DOB05/17/2021V-DOB VIOLATION - ACTIVE
DOB05/17/2021V-DOB VIOLATION - ACTIVE
DOB07/27/2020V-DOB VIOLATION - ACTIVE
DOB07/24/2020V-DOB VIOLATION - ACTIVE
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB12/13/2011VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
DOB10/08/2010V-DOB VIOLATION - ACTIVE
DOB01/13/1997V-DOB VIOLATION - ACTIVE
ECB02/06/2026CLASS 2: PHONE INOPERATIVE REPAIR & PROGRAM TO 24 HR EMERGENCY OPERATOR.Nothing owed — awaiting certificate of correction
ECB03/05/2025REISSUE#35665421M FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:THE LANDSCAPE BRICK RETAINING WALLS AT MAIN ENTRY ARE IN DISREPAIR.THEY ARE CRACKED,MOVING OUT OF ALIGNMENT,MISSING BRICKS AND LOOSINothing owed — awaiting certificate of correction
ECB03/05/2025REISSUE#35665420K FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT T.O.I.,OBSERVED SEVERAL OF THE CROSS CORRIDOR SMOKE DOORS ARE NOT OPERATING CORRECTLY.THE DOOR USE IS DISABLED CAUSED BY THE ELECNothing owed — awaiting certificate of correction
ECB03/05/2025REISSUE#35665416H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8,27-371(J).NOTED:AT ROOM#203 OF ANNEX BLDG.THE DOOR IS LABELED FIRE RESCUE AREA.THENothing owed — awaiting certificate of correction
ECB03/05/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT T.O.I.,OBSERVED THE WINDOWS IN THE CAFETERIA THAT FACE THE COURTYARD ARE ALL IN DISREPAIR NONE OF THEM WORK.THEY DON'T OPEN,AND CANNOT OPERATE.THEYNothing owed — awaiting certificate of correction
ECB03/05/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT T.O.I.,THE CONCRETE WALKWAYS,FROM MAIN ENTRANCE OUT TO MANOR RD CURB ARE IN SERIOUS DISREPAIR.THEY ARE CRACKED,CHIPPED,UNOVEN AND ARE A SERIOUS TRINothing owed — awaiting certificate of correction
ECB03/05/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT T.O.I.OBSERVED THE DOOR AT ROOM#149 NEEDS TO BE TOTALLY REPLACED.IT IS FALLING APART AND IS MISSING PIECES AT AND AROUND THE LOCK SET.THE DOOR HASNothing owed — awaiting certificate of correction
ECB03/05/2025REISSUE#35665418L FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT T.O.I.,IN ROOM#193,THE WINDOW AT THE LEFT CORNER IS BROKEN.THE LOWER SASH CANNOT BE OPERATED OR OPENED.IF OPEN IT SLAMS SHUT.REM:Nothing owed — awaiting certificate of correction
ECB03/05/2025REISSUE#35665419N FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT T.O.I.ROOM#356 AND #456,BOTH LABELED AS RESCUE AREA HAVE KEYED LOCKING DEVICE FACING THE CORRIDOR.REM:REMOVE KEYED CYLINDER OR CONothing owed — awaiting certificate of correction
ECB03/05/2025REISSUE#35665417J FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT T.O.I.,OBSERVED USE OF PROHIBITED DOOR AND/OR HARDWARE PER 1008.1.8;27-381(J).THERE WERE SEVERAL CLASSROOM DOORS AND OTHERS WITHNothing owed — awaiting certificate of correction
ECB09/25/2024RE-ISSUE #35655568H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER. NOTED: ROOM #456 AND ROOM #356 OR LABELED ON THE DOORS AS RESCUEAREA. THE KEYED LOCKING DEVICE FACING THE CORRIDOR IS ILLEGAL HARDWARENothing owed — awaiting certificate of correction
ECB09/25/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THERE ARE SEVERAL CORRIDOR SMOKE DOORS THAT ARE NOT OPERATING CORRECTLY; THE AUTOMATIC RELEASE OF THE MAGNETIC CLOSING DEVICE IS NON OPERATIONAL. THNothing owed — awaiting certificate of correction
ECB09/25/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ADJACENTTO THE MAIN ENTRY, THE BRICK MASONRY LANDSCAPE/RETAINING WALL IS CRACKING, BROKEN AND FALLING APPART, COULD CAUSE INJURY TO THE PEDESTRIAN TNothing owed — awaiting certificate of correction
ECB09/25/2024RE-ISSUE #35672464H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. THE WINDOW IN ROOM #1931 AT LEFT CORNER OF ROOM IS BROKEN. THE LOWER SASH IS DANGEROUS AND CAN NOT BE OPERATED. REMEDY: REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB09/25/2024RE-ISSUE #35672465J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: AT T. O. I. THERE WERE SEVERAL CLASSROOM DOORS AND OTHERS WITH KICKNothing owed — awaiting certificate of correction
ECB09/25/2024RE-ISSUE #35672466L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: THE DOOR AT RM. #203 OF ANNEX IS ANNEX IS LABELED FIRE RESCUE AREA. THENothing owed — awaiting certificate of correction
ECB07/11/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC1008.1.8;27-371(J) THE DOOR AT RM #P203 OF THE SUSAN WAGNER H.S. ANNEX, IS LABELED FIRE RESCUE AREA. THE KEY LNothing owed — awaiting certificate of correction
ECB07/11/2023RE-ISSUE #35655568H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J).THERE ARE SEVEREAL DOORS AT CLASSROOMS AND OTHERS WITH KICK STOPPERS INothing owed — awaiting certificate of correction
ECB07/11/2023RE-ISSUE #35655566Y FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. THE WINDOW TO ROOM #1193 AT FAR LEFT OF WINDOW WALL, IS UNSAFE TO OPERATE. THE FRAME OF THE LOWER SASH, IS BROKEN MAKING THE WINDOW PANNothing owed — awaiting certificate of correction
ECB07/27/2022RE-ISSUE #35586704R FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED AT T.O.I. THE WINDOW IN ROOM #193 AT FAR LEFT IS STILL BROKEN AND NOT OPERATIONAL. IT CANNOT OPEN. REMEDY: REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB06/13/2022FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J). OBSERVED AT T.O.I. ROOMS#356 AND #456 LABELED "RESCUE AREA" HAVE KEYED LOCKING CYLINDERS WNothing owed — awaiting certificate of correction
ECB07/16/2021FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT TOI ROOM #193 WINDOW AT FAR LEFT OF WINDOW WALL IS NON OPERATIONAL.CANNOT OPEN.REMEDY:REPAIR/REPLACE WINDOW.Nothing owed — awaiting certificate of correction
ECB09/03/2020MISSING CAT 1 TAGS,NO DOOR LOCK MONITORING INSTALLED IN THE CONTROLLER AS MANDATED IN 3.12.10 OF APPENDIX K BY 2014 BUILDING CODES. REMEDY: INSTALL DLM, FILE AND PERFORM TEST WITH NYC DOB,PROVIDE SUFFICIENT CATNothing owed — awaiting certificate of correction
Public elementary, junior or senior high · Owner of record: NYC HEALTH & HOSPITAL/SEAVIEW · 8,259,785 sf lot · 0.09 FAR built · Flood zone X