HPD05/05/2026(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD11/18/2025§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
HPD06/10/2025(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD11/26/2024§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
HPD04/11/2024(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
HPD11/17/2023§27-2107 ADM CODE OWNER FAILED TO FILE A VALID REGISTRATION STATEMENT WITH THE DEPARTMENT AS REQUIRED BY ADM CODE §27-2097 AND IS THEREFORE SUBJECT TO CIVIL PENALTIES, PROHIBITED FROM CERTIFYING VIOLATIONS, AND DENIED THE RIGHT TO RECOVER POSSESSION OF PREMISES FOR NONPAYMENT OF RENT UNTIL A VALID REGISTRATION STATEMENT IS FILED.
HPD03/24/2023(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.
DOB12/17/2021FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB12/09/2021V-DOB VIOLATION - ACTIVE
DOB11/06/2020V-DOB VIOLATION - ACTIVE
DOB10/21/2019V-DOB VIOLATION - ACTIVE
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB10/03/2018V-DOB VIOLATION - ACTIVE
DOB10/06/2017V-DOB VIOLATION - ACTIVE
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB12/19/2005V-DOB VIOLATION - ACTIVE
DOB08/16/1993V-DOB VIOLATION - ACTIVE
DOB08/16/1993V-DOB VIOLATION - ACTIVE
DOB08/16/1993V-DOB VIOLATION - ACTIVE
DOB08/16/1993V-DOB VIOLATION - ACTIVE
ECB04/07/2026FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 1 ITEM: UPON INSPECTION, THIS DEVICE WAS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. SERVICE ELEVATOR EQUIPMENT ASNothing owed — awaiting certificate of correction
ECB02/06/2026WEIL MCLAIN BOILER# 1 UNREGISTERED. EXPOSED WIRING, LEAKING WATER GAUGE GLASS, THREE STEAM VALVES LEAKING. CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB02/06/2026OBSERVED THROUGHOUT THE BUILDING SPRINKLER HEADS ESCUTCHEONS NOT INSTALLED PROPERLY. FIRST FLOOR AND BASEMENT DAMAGED SPRINKLER HEADS AND OBSTRUCTED SPRINKLER HEADS. THROUGHOUT THE BUILDING NO FIRE STOP FOR PIPNothing owed — awaiting certificate of correction
ECB02/06/2026OBSERVED ON ROOF LACK SUPPORT ON VENT TERMINAL. FIRST AND SECOND FLOOR BATHROOMS NOT OPERATIONAL. MOST OF THE TOILET'S SEATS THROUGHOUT THE BUILDING IS NOT OPEN ENDED HINGE. FIRST FLOOR BATHROOM DOOR IS HITTINGNothing owed — awaiting certificate of correction
ECB02/06/2026CLASS 1 RTS CONT. AGG1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUNothing owed — awaiting certificate of correction
ECB12/23/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REMEDY: RESTORE TO SERVICE AND CONTACT THE DOB ELEVATOR DIVISION AT ELEVATORIR@BUILDINGS.NYC.GOVNothing owed — awaiting certificate of correction
ECB08/25/2025#2 WEILMCLAIN STEAM BOILER HAS KING VALVE LEAKING WATER ONTO TOP OF BOILER+WIRES EXPOSED@BOILER LEFT+NO STEAM PRESSURE@STEAM>HOT WATER HEAT EXCHANGER>WITH/5PSI STEAM@BOILER;CORRECT VIOLATION+SUBMIT CERTIFICATENothing owed — awaiting certificate of correction
ECB08/14/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REMEDY: RESTORE TO SERVICE AND CONTACT THE DOB ELEVATOR DIVISION AT ELEVATORIR@BUILDINGS.NYC.GOVNothing owed — awaiting certificate of correction
ECB06/18/2025FOUND WEIL MCLAIN DUEL FUEL STEAM BOILER MODEL-1188 OPERATING AND UNREGISTERED. REGISTER BOILER AND CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB06/18/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED UNPERMITTED PLASTIC ACCESS PANELS. NOT FIRE RATED. POTENTIAL FIRE HAZARDNothing owed — awaiting certificate of correction
ECB06/16/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSENothing owed — awaiting certificate of correction
ECB05/08/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REMEDY: RESTORE TO SERVICE AND CONTACT THE DOB ELEVATOR DIVISION AT ELEVATORIR@BUILDINGS.NYC.GOVNothing owed — awaiting certificate of correction
ECB04/22/2024ONLY ELEVATOR IN THE BUILDING OUT OF SERVICE. RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDOB. AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB10/04/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11Nothing owed — awaiting certificate of correction
ECB05/22/2023STEAM TRAPS LEAKING INTO DRAIN AT HX/TOP BOILER ISOLATION VALVE LEAKING ONTO BOILER/NO CLEANOUT AT CHIMNEY BASE/BODY DRAIN PIPE MISSING AT SAFETY VALVE/HW CIRCULATING PIPE DEFECTIVE VALVE CLOSED;CORRECT VIOLATINothing owed — awaiting certificate of correction
ECB05/22/2023SAFETY VALVE BODY DRAIN PIPE IS MISSING/CHIMNEY BASE IS 1/2 FULL/OIL GAUGE IS DEFECTIVE/FRONT HW CIRCULATING PIPE CORRODED;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB04/28/2023THE ONLY ELEVATOR IN BUILDING OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. REMEDY: RESTORE TO SERVICE IMMEDIATELY AND, NOTIFY NYCDNothing owed — awaiting certificate of correction
ECB03/27/2023RESTORE SERVICE TO DEVICE.Nothing owed — awaiting certificate of correction
ECB06/07/2022RESTORE SERVICE TO DEVICE.Nothing owed — awaiting certificate of correction
ECB01/12/2022UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB10/15/2021FOUND WEIL MCLAIN MODEL# 1188 BOILER NOT REGISTERED CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/15/2021STOPS ON DRAFT CONTROL MUST BE REMOVED CLEANOUTS ON BOILER LEAKING CORRECT ALL VIOLATING CONDITIOND AND SUBMIT A CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/15/2021UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. THIS IS THE ONLY DEVICE IN THE BUILDING. RESTORE TO SERVICE IMMEDIATELY. YOU CAN CONTACT NYCDOB AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB12/30/2020UNREGISTERED BOILERNothing owed — awaiting certificate of correction
ECB12/30/2020NO CLEAN OUT ON CHIMNEY #2. CHIMNEY #1 NEEDS TO BE CLEANED. HOLES IN CEILING AND WALLS. REMOVE RED BLOCK PEGS FROM BAROMETRIC DIVERTERS. NO C.O DETECTOR INSTALLED. C.O DETECTOR MUST BE INTERLOCKED WITH BOILER.Nothing owed — awaiting certificate of correction
ECB10/31/2019(97X17)UPON INSPECTION THE DEVICE WAS FOUND TO BE OUT OF SERVICE.THIS IS THE ONLY ELEVATOR IN THE BUILDING RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB02/14/201997X17; 97-X-17 THIS DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02.RESTORE TO SERVICE IMMEDIATELY AND NOTIFY NYC D.O.B AT 212-393-2520 & E-MAIL:EIR EBUILDINGS.NYC.GOVNothing owed — awaiting certificate of correction
ECB02/13/2019BOILER IS NOT REGISTERED; RE-AGGRAVATED SUMMONS BASED ON PREVIOUS SUMMONS #32097159Y. REGISTER BOILER & SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB01/16/201997X17 UPON INSPECTION THE DEVICE IS FOUND OUT OF SERVICE. REPORT IMMEDIATELY AND CALL DOB FOR REINSPECTION.Nothing owed — awaiting certificate of correction
ECB10/18/201897X10.UPON INSPECTION DEVICE OF SERVICE LOCKED OUT TAGGGED OUT.RESTORETO SERVIVE IMMEDIATELYNothing owed — awaiting certificate of correction
ECB06/28/20186A,15,36,50,50A,50B-50)GAS PILOT REGULATOR IS MISSING SPRING CAP. 50A)2ND LWCO NOT ON 2ND WATER COLUMN. 50B)CONDENSATE TANK VENT NOT PIPED DOWN.Nothing owed — awaiting certificate of correction
ECB06/28/20186A,50-50)2ND LWCO NOT OR 2ND WATER COLUMN.Nothing owed — awaiting certificate of correction
ECB06/16/2015/67L10/13L10/56Y13/17H11/76M07/16J01/45E01/ (13L) DIMLY LIT. (56Y) SEAL LEAKS. (17H) WHERE NEEDED. (16J) 1ST FL ACCESS HALL. (45E) JAW.Nothing owed — awaiting certificate of correction
ECB11/13/201216Q03,17H11,67X10,56Y13,59Y02,68B07,69B11,39B01,26D06,76M07,77B11.16Q-PROVIDE SIGHT&ADESPERK3;17H-REPLACE WHERE NEEDED;67X-REPAIR;56Y-SEAL LEAKS;57Y-CLEAN DRUM;68B-PROVIDE UP TO DATE PLAN;69B-WRONG CODE;37B-TOCNothing owed — awaiting certificate of correction