ECB11/12/200844C,50A,18B,50B,50C. 44C- defective steam gauge reading 180 psi which is above the maximum allowable working pressure. 50A-remove check valves that are connected to steam gauge. 50B- flu pipe has indication ofNothing owed — awaiting certificate of correction
ECB11/12/200848B,50A,18B,50B,32A,44C. 50-electrical control panel door missing. 50BINSTALL drain line on water gauge glass. 44C-steam gauge defective leaking & operating in the closed position not able to read operating preNothing owed — awaiting certificate of correction
ECB08/10/200550A/18A/50B/50C. Fulton v.t. Boiler, 10HP, NB 29600, gas 1974. 50A-a section of the external casing of the boiler was severly deformed. Perform repairs to restore the casing to a satisfactory physical conditionNothing owed — awaiting certificate of correction
ECB08/10/2005Fulton v.t. Boiler, 15 hp, NB 51107,gas 1986. 50-boiler flue pipe run in solid contact with piping systems for the adjacent boiler #1-re-position and install independent structure supports(hangers) on the flueNothing owed — awaiting certificate of correction
ECB12/20/200434ANothing owed — awaiting certificate of correction
Factory, industrial, miscellaneous · 4,023 sf lot · 1.91 FAR built · Flood zone X