DOB09/09/2026PARTIAL VACATE ORDER DUE TO CRACKED/BULGING/SPALLING/SPALLED BRICKWORK AND MORTAR JOINTS ALL ALONG EXPOSURE #2 EAST ELEVATION. MISSING/LOOSE BRICKS, STEP-CRACKING, AND LONG VERTICAL BRICK CRACKING. CRACKED/ MISSING WINDOW PANES. REMEDY: VACATE ENTIRE COURTYARD/WALKWAY @ EXP #2 EAST ELEV & RESTRICT ACCESS TO VACATED AREA
DOB08/28/2026FAILURE TO MAINTAIN BLDG. OBSRVD @ EXP 1, STEP CRACK/CRACK & SPALLED/ SPALLING DECORATIVE STONE. AT EXP 2,CRACK, BULGING SPALLED MASONRY, BROKEN/MISSING WINDOWPANE. AT EXP 3, LONG VERTICAL CRACK, CRACK, DAMAG MORTAR JOINTS & BROKEN/CRACK WINDOW PANE. AT EXP 4, CRACK ON MASONRY, DAMAGE JOINTS & BROKEN WINDOWPANE. REMEDY:REPAIR AND/OR REPLACE
ECB08/28/2026PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. NOTED AT THE TIME OF INSPECTION I OBSERVED DEFECTIVE/INADEQUATE SHED CONDITIONS I. E. LOOSE PARAPET PANEL ON EXPOSURE 3(ELEVATION) SIDEWALK SHED WHICH IS$2K due
DOB08/28/2026EWO FOR REMOVAL/STABALIZATION WORK DUE TO CRACKS,STEP CRACKS,BULGING MASONRY WALL,SPALLED MASONRY,DAMAGED MORTAR JOINTS.CRACK/BROKEN/MISSIN WINDOW PANES ON ALL EXPS. REMEDY:OWNER TO IMMED RETAIN NYS REG.LIC.PRO TO DIRECT AND SUPV WORK IN CONNECTION WITH REMOVAL/STABALIZATION OF CRACKED/BULGING BRICK.RDP MUST BE ON SITE FULL TIME
DOB08/28/2026EWO FOR REMOVAL/STABLIZTN WRK DUE TO CRACKS, STEPCRACKS, BULGINGMASON -RY WALL, SPALLED MASONRY, DAMAGED MORTAR JOINTS, CRACK/BROKEN/MISSING WINDOWPANES ON ALL EXPS. REMDY: OWNR TO IMMEDLY RETAIN A NYS REG LP TO DIRECT & SUPRVSE WRK IN CONNECTN W/ REMOVAL/STABLIZTNOF THEOBSRVDCR -ACKED/BULGING BRICK. RDP MUST BE ONSITE F/T & ENSURE SFTY. PRVIDE RPT
ECB02/25/2026RESPONDING TO A COMPLAINT OBSERVED: SIDEWALK SHED INSTALLED AT EXPO# 1. NO UNDERSIDE LIGHTING INOPERABLE LIGHT BULBS, FAILURE TO MAINTAIN AS PER CODE 3307.6.4.8 BECOME AN UNSAFE AND HAZARDOUS CONDITION FOR PEDE$10K due
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/12/2025EMERGENCY WORK ORDER DUE TO CRACK FACADE AND STONES AT EXPOSURE 1 AND 3. REMEDY: IMMEDIATELY PROVIDE SAFETY MEASURE (UNDER DIRECTION OF NYC LICENSED DESIGN PROFESSIONAL) INSTALLED SIDEWALK SHED AT EXPOSURE 1 AND 3
DOB11/12/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED EXP 1: STEP CRACK/CRACK SPALLED/SPALLING STONE. EXP2:CRACK,BULGING, BROKEN/ MISSING WINDOW PANE. EXPOSURE 3: BROKEN/CRACK WINDOW PANE, CRACK & DAMAGED STONE. EXPOSURE 4: BROKEN WINDOW PANE AND DAMAGED JOINS REMEDY: REPAIR AND/OR REPLACE
DOB12/01/2024FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
DOB06/23/2024FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2023)
DOB05/02/2023FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB04/22/2023FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2022)
DOB02/02/2023FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB12/01/2022FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB11/02/2022FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/21/2022FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2021)
DOB08/02/2022FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/01/2022FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/02/2022FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB12/01/2021FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB11/02/2021FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB10/20/2021V-DOB VIOLATION - ACTIVE
DOB10/10/2021FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2020)
DOB08/02/2021FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/02/2021FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB04/29/2021FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB02/02/2021FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/02/2020FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2020FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/29/2020FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 IN 2019
DOB05/02/2020FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/02/2020FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB11/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB08/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/16/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB02/02/2018FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB11/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB02/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/06/2014FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB07/03/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB07/03/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB07/03/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/03/2013FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/15/2012V-DOB VIOLATION - ACTIVE
DOB05/03/2012FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB01/01/2012FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB01/01/2009V-DOB VIOLATION - ACTIVE
DOB01/01/2009V-DOB VIOLATION - ACTIVE
DOB03/21/2003V-DOB VIOLATION - ACTIVE
DOB02/19/2002V-DOB VIOLATION - ACTIVE
DOB03/08/2001V-DOB VIOLATION - ACTIVE
DOB02/27/2001V-DOB VIOLATION - ACTIVE
DOB02/27/2001V-DOB VIOLATION - ACTIVE
DOB01/31/1996VW-VIOLATION WORK WITHOUT PERMIT - ACTIVE
ECB05/25/2017FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNET;LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1,27-345.NOTED:NO EMERGENCY SIGNS/LIGHTS AT DOORS USED AS EXITS AT KNothing owed — awaiting certificate of correction
ECB05/25/2017EMERGENCY SIGNS AT ELEVATOR C211 STATION MISSING,DEFECTIVE OR NON-COMPLIANT WITH SECTION REQUIREMENTS.NOTED:AT 4TH FLOOR AND AT BASEMENT,ELEVATOR C211 SIGNS MISSING.REM:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB02/27/201527-371(B) VISION PANEL. PLEXI GLASS/THERMOPLASTIC VISION PANELS INSTALLED ON 4TH FLR PRESCHOOL OFFICE DOOR AND CLASSROOM 408A DOORS. RMDY: PROVIDE REQUIRED GLASS.Nothing owed — awaiting certificate of correction
ECB04/03/2013VIOLATION OF ELECTRICAL CODE TECHNICAL STANDARDS. DEFECTIVE ELECTRICALWIRING AT FRONT OF BUILDING AT 11:15AM OBSERVED DEFECTIVE ELECTRICAL WIRING TO ROLL UP GATE MOTOR AND ELECTRIC SIGN USING BX CABLE,EMT,OUTDNothing owed — awaiting certificate of correction
ECB04/02/2013VIOLATION OF ELECTRICAL CODE TECHNICAL STANDARDS. ILLUMINATED ELECTRICSIGN INSTALLED PRIOR TO OBTAINING PERMIT,INSPECTION AND TAGGING.AT 11:15AM OBSERVED THAT ELECTRIC SIGNIN SHAPE OF A CROSS, AND DOUBLE SIDEDNothing owed — awaiting certificate of correction
ECB04/02/2013ELECTRICAL WORK W/O PERMIT. ELECTRICAL WIRING OF ROLLUP OF MOTOR FOR GATE, AND ILLUMINATED ELECTRIC SIGN.PRIOR TO OBTAINING PERMIT. AT 11:15AM OBSERVED THAT ELECTRIC WIRING HAD BEEN INSTALLED AND CONNECTED TONothing owed — awaiting certificate of correction
ECB06/14/2004EXIT PASSAGEWAY OBSTRUCTION: NOTED AT SIDE OF BUILDING AC UNIT HAVE BEEN INSTALLED BLOCKING EGRESS TO STREET UNIT AT REAR APPROX 1FT 6IN OPEN SPACE UNIT AT FROM APPROX 3FT OPEN SPACE GAS LINE APPROX 6" ABOVE GRNothing owed — awaiting certificate of correction
ECB07/08/200312D06/25D06/16B01/08V01/57F10 (12)SECUR LIGHT CAR(25)SECURE TOP EXIT COVER(16)ADJUST HOISTWAY DOORS(08)ADJUST FLOOR STOP(57)REPAIR WORM & GEARNothing owed — awaiting certificate of correction