ECB07/16/2026UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE ELEVATOR MACHINE RM THE SERVICE DISCONNECT SW IS NOT LOCKABLE. ALL SERVICE / DISCON$800 due
ECB07/16/2026UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE REAR OF THE BUILDING COURT YARD EMT CONDUIT INSTALLED OUTDOORS FOR EXIT SIGNS. EMT$800 due
ECB07/16/2026FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN THE BASEMENT THE MAIN WATER GROUND CLAMP IS INSTALLED INCORRECT LOCATION. WATER GROUND CLAMP SHOULD BE INSTALLED BEFORE THE MAIN HOUSE WA$2K due
ECB07/16/2026ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE MAIN VESTIBULE ONE HUNG ELECTRIC HEATER INSTALLED WITH EMT , DISCONNECT SW. CHECKED BIS /DOB NOW NO PERMIT ON FILE ALL WORK MUST BE FILED AND DONE BY A LICESEND$1K due
ECB07/16/2026ATOI OBSERVED IN BASMENT LAUNDRY ROOM WITH 2 DRYERS, 2 WASHING MACHINES. NO PERMIT ON FILE. PER PC 106.1 - PLUMBING WORK, INCLUDING WATER HEATER INSTALLATIONS AND PLUMBING SYSTEM ALTERATIONS, REQUIRES PERMITS.,$2K due
DOB07/25/2024V-DOB VIOLATION - ACTIVE
DOB02/21/2022CYCLE 9A UNSAFE REPORT FILED
HPD12/31/2019§ 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.
HPD11/07/2019§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
DOB05/31/2018FAILED TO FILE FISP CYCLE 8A TECHNICAL REPORT BY 02/21/2017
DOB06/24/2016FAILURE TO PROVIDE ALL NESSARY INFORMATION FOR RELATED APPLICATION # 102936682 REMEDY: RESPOIND IS REQUIRED WITHIN 15 DAYS TO DEPARTMENT OF BLDGS 280 BROADWAY, BORO-COMMISSIONER OFFICE
DOB05/19/2007V-DOB VIOLATION - ACTIVE
DOB09/30/2005V-DOB VIOLATION - ACTIVE