DOB09/12/2013V-DOB VIOLATION - ACTIVE
ECB06/09/2026REISSUE#35720843L FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:THE SURFACE OF THE TENNIS COURT AT ATLETIC FIELD IS INDISREPAIR.LARGE CRACKS AT VARIOUS LOCATIONS.REM:REPAIR/REPLACE SURFACE.Nothing owed — awaiting certificate of correction
ECB06/09/2026FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT THE ELECTRIC METER,THERE WAS STORAGE OF COMBUSTIBLE MATERIALS.MOSTLY CARDBOARD PANELS AND OTHER COMBUSTIBLES.REM:REMOVE ALL STORAGE FROM ELECTRIC MNothing owed — awaiting certificate of correction
ECB08/25/2025@JOHN DEWEY HS PACIFIC NATIONAL BOILER#2 HAS OIL LEAK@BURNER+HAS DEFECTIVE FUSIBLE LINK@OIL VALVE+INCORRECT BACKFLOW VALVE INSTALLED@VAC SYSTEM WATER FEED;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB08/25/2025@JOHN DEWEY HS PACIFIC NATIONAL BOILER#1 HAS OIL LEAK@BURNER+FUSIBLE LINK@OIL VALVE IS DEFECTIVE+BOILER WATER CHEMICAL FEED TANK CORRODED WITH TEMPORARY PATCH;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB08/25/2025@JOHN DEWEY HS PACIFIC NATIONAL BOILER#4 IS INOPERABLE+HAS DEFECTIVE FUSIBLE LINK@OIL VALVE;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB08/25/2025@PS721=BURNHAM BOILER#2 HAS GAS PIOLIT REGULATOR MISSING VENT LIMITER+HAS CORRODED SAFETY VALVES@STEAM>HOT WATER HEAT EXCHANGERS+HAS DEFECTIVE MOTORIZED COMBUSTION AIR LOUVERS;CORRECT VIOLATION+SUBMIT CERTIFICANothing owed — awaiting certificate of correction
ECB08/14/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ATHLETIC FIELD WALKWAY AND TENNIS COURT WITH LARGE CRACKS AT VARIOUS LOCATIONS. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB08/14/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. HALLWAY/CORRIDOR DOOR ROOF TO 318, 2ND FLOOR NEXT 244 STAIRCASE 4 2 FLOOR AND STAIRCASE 2, 2 FLOOR NOT SELF-CLOSING. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/08/2022@PS721=GAS PIOLIT REGULATOR MISSING VENT LIMITER;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONHearing held — result not yet published$500 proposed
ECB07/08/2022@JOHN DEWEY=TOP LEFT HANDHOLE LEAKING/BODY DRAIN DISCHARGE PIPES MISSING AT SAFETY VALVES;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONHearing held — result not yet published$500 proposed
ECB07/08/2022@JOHN DEWEY=HOT WATER STORAGE TANKS THE SAFETY VALVES ARE DEFECTIVE/BODY DRAIN DISCHARGE PIPES MISSING AT BOILER SAFETY VALVES;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONHearing held — result not yet published$625 proposed
ECB07/08/2022@JOHN DEWEY=BOILER DRAFT INDUCER BELT DEFECTIVE;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONHearing held — result not yet published$625 proposed
ECB06/22/2022@PS721=NEW COMBUSTION AIR FAN MOTOR NOT WIRED/REAR FLAME SIGHT GLASS DEFECTIVE/WIRES EXPOSED@ELECTRIC SPACE HEATER/DISCHARGE PIPES MISSING@HX SAFETY VALVES;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONHearing held — result not yet published$625 proposed
ECB06/22/2022CEASE USE AOSMITH HOT WATER HEATER@PS721@64 AVE X=HOLES IN FLUE PIPE/CIRCULATOR IMPROPERLY INSTALLED/BASE OF CHIMNEY NOT ACCESSIBLE FOR INSPECTION AND CLEANING/, MAINTAIN BOILER; CORRECT ALL HAZARDOUS CONDITIONHearing held — result not yet published$1K proposed
ECB11/16/2016100M7,80M7,2X10,13I10. 100M7-BRAKE MAINTENANCE TAG; 80-M7-COUNTERWEIGHTS CLEARANCE SIGN, 2X10-PHONE INOPERATIVE; 13I10-EMERGENCY LIGHT DAMAGED.Nothing owed — awaiting certificate of correction
ECB11/16/201218M07,05X10,60Q03,16D06,52M07,50H11. 18M-PROVIDE PERK3;05X-ZONE LOCK RESTROOM;16D-3FL SIGHTGUARD;52M-MISSED CROSBIES;50H-NOISE BEARING.Nothing owed — awaiting certificate of correction
ECB11/16/201242G11,60Q03,52K10,18M07,05X10. 42G-UNREADABLE FUSES; 52K-PROVDE DEVELOPING;18M-PROVIDE PERK3;05X-ZONE LOCK RESTROOMNothing owed — awaiting certificate of correction
Public elementary, junior or senior high · Owner of record: NYC DEPARTMENT OF EDUCATION · 348,076 sf lot · 1.05 FAR built · Flood zone X500