ECB07/22/2026CLASS 2 ITEMS: REQUIRED FIRE EMERGENCY SIGN IS MISSING ADJACENT TO THE ELEVATOR ENTRANCE/HALL CALL STATION. INSTALL APPROVED SIGNAGE STATING: "IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS." IN$625 due
ECB06/11/2026CLASS 1 ITEM: BRAKE LINING IS IMPROPERLY FITTED AND NOT FULLY SEATED ON THE BRAKE DRUM, RESULTING IN INCOMPLETE CONTACT WITH THE BRAKING SURFACE. UNSAFE BRAKE CONDITION OBSERVED, IN VIOLATION OF ASME A17.1-2013$1K due
HPD01/27/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE CRACKED GLASS PANE AT LOWER SASH AT 1ST WINDOW FROM WEST AT NORTH IN THE 1st ROOM FROM NORTH LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD12/03/2025§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER EXCEEDING MAXIMUM OF 130 DEGREES AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT EAST
HPD12/11/2023§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION FLOOR TO CEILING PARTION ERECTED CREATING ADDITIONAL ROOM IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT EAST
HPD12/11/2023§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER EXCEEDS THE MAXIMUM OF 130 DEGREES IN THE ENTIRE APARTMENT LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT EAST
ECB08/16/2023FLUE PIPE WAS REDUCE IN SIZE / FLUE PIPE AROUND CHIMNEY HAS TO BE RECEMENT/MISSING DAWG IN REAR DOOR/SAFTEY VALVE BODY DRAIN MISSING/BACKFLOW AIR GAB AND DRAIN PIPE MISSING$625 due
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB02/22/2023FAILED TO FILE FISP CYCLE 9B TECHNICAL REPORT BY 2/21/2023
HPD10/18/2022§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM WINDOW TO FIRE ESCAPE OR PROVIDE APPROVED TYPE GATE ,,, IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 2A, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD10/18/2022§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE FOYER LOCATED AT APT 2A, 2nd STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD12/29/2021§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE METAL DOOR FRAME AT APT DOOR IN THE ENTRANCE LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
HPD06/07/2017§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED
HPD12/04/2016§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM WEST AT NORTH WALL, NORTH WALL, WEST WALL IN THE 4th ROOM FROM NORTH AT WEST LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD12/04/2016§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING, 1st RISER FROM EAST AT SOUTH WALL, EAST WALL IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD11/25/2016§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING, SOUTH WALL IN THE 2nd PRIVATE HALLWAY FROM NORTH AT EAST LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD11/25/2016§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION THE 2nd WINDOW FRAME FROM WEST AT NORTH WALL, 1st WINDOW FRAME FROM WEST AT NORTH WALL IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD11/25/2016§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE SOUTH WALL IN THE KITCHEN LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD11/25/2016§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE 1st DOOR FROM SOUTH AT WEST WALL, SOUTH WALL, WEST WALL IN THE 2nd ROOM FROM NORTH AT EAST LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD11/25/2016§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION THE 1st DOOR FRAME FROM NORTH AT EAST WALL, 1st WINDOW FRAME FROM WEST AT NORTH WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD11/25/2016§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING, 1st DOOR FROM NORTH AT EAST WALL, NORTH WALL, EAST WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM WEST AT NORTH
DOB09/21/2016FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB08/24/2016FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD03/23/2016§ 27-2045, 2046 ADM CODE PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM WEST AT NORTH
HPD03/23/2016§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM WEST AT NORTH
DOB08/30/2013FAILED TO FILE FISP CYCLE 7B TECHNICAL REPORT BY 08/21/2012
HPD09/22/1994§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING 1ST STY SOUTHEAST APT 1F MR ROSARIO. , SECTION '' ''
ECB02/24/2022CLASS 1 VIOLATION ISSUED , DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMAN SECTION 3.10.12 OF APPENDIX K3. CLASS 2 VIOLATION ISSUED , / UNREADABLE FUSE AMP SIGNAGE TAGS ON DEVICE. (R) PROVIDE, / HOIST MOTORNothing owed — awaiting certificate of correction
ECB06/28/2016FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.2;27-954.NOTE:AT THE TIME OF INSPECTION OBSERVED AT CELLAR LEVEL ALONG EXP#2 LAUNDRY RONothing owed — awaiting certificate of correction
ECB06/02/2016WORK W/O A PERMIT. NOTE: AT THE TIME OF INSPECTION OBSERVED AT CELLAR LEVEL ALONG EXP#2. GAS & WATER LINES INSTALLED TO CREATE A LAUNDRY ROOM W/4 COMMERCIAL DRYERS & 4 COMMERCIAL WASHING MACHINES. REMEDY: COMPLNothing owed — awaiting certificate of correction
ECB11/25/2014FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR WALLS & APPURTENANCES AS REQUIRED BY ARTICLE 28-302 & THE DEPT OF BLDGS RULES & REGULATNothing owed — awaiting certificate of correction
ECB07/16/2009FAILURE TO FILE AN AMENDED SIXTH ROUND REPORT ACCEPTABLE TO THIS DEPARTMETN INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL LOCAL LAW 11/98 REPORT. REM: FILE AN AMENDED REPORT FOLLOWING REMEDIALNothing owed — awaiting certificate of correction
ECB04/27/2009FAILURE TO FILE AN AMENDED SIXTH ROUND REPORT ACCEPTABLE TO THIS DEPT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL LOCAL LAW 11/98 REPORT REMEDY:FILE AN AMENDED REPORT FOLLOWING REMEDIAL OFNothing owed — awaiting certificate of correction
ECB04/14/2009FAILURE TO MAINTAIN EXTERIOR BLDG NORTH ELEVATION OBSERVE BLOCKS OF WOOD AND METAL CANS IMPROPERLY INSTALL UNDER AIR CONDITION UNITS; FLOW TSTORAGE ON FIRE ESCAPE (LANDING) EXTENSIVE BOWING AND DETERIORATINGNothing owed — awaiting certificate of correction
ECB08/14/2008FAILURE TO FILE AN AMENDED 6TH ROUND REPORT ACCEPTABLE TO THIS DPMT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL LOCAL LAW 11/98 REMEDY: FILE AN AMENDED REPORT FOLLOWING REMEDIAL REPAIRS OF TNothing owed — awaiting certificate of correction
ECB01/31/2008LOCAL LAW REPORT FILES AS "UNSAFE" CONDITIONS EXITS & NO MEASURES TAKEN TI SECURE SAFETY OF PUBLIC AS PER 27-129(D) & RCNY 32-03(B)(5)(I). REMEDY: PROVIDE SAFETY MEASURES AS PER BLDG CODE; FILE REPORT "AMENDNothing owed — awaiting certificate of correction
ECB10/24/2006FAILURE TO MAINTAIN EXTERIOR BLDG. SOUTH ELEVATION SHOWS BLOCKS OF WOOD BRICKS & METAL CANS UNDER A/C UNITS. REMEDY: MAKE AREA SAFE, REMOVE & REPLACE ALL BLOCKS OF WOOD, BRICKS & METAL CAN FROM UNDER A/C UNITSNothing owed — awaiting certificate of correction
ECB03/20/2006FAILURE TO MAINTAIN EXTERIOR BLDG SOUTH, EAST AND NORTH ELEVATIONS SHOWS BLOCKS OF WOOD, BRICKS AND CANS UNDER A/C UNITS. REMEDY: MAKE AREA SAFE, REMOVE AND REPLACE IMPROPERLY SUPPORTS UNDER A/C UNITS AND REPLANothing owed — awaiting certificate of correction
ECB08/25/2005FAILURE TO MAINTAIN EXTERIOR FACADE. SOUTH ELEVATION SHOWS BLOCKS OF WOOD UNDER A/C UNITS AND FLOWER POTS ON FIRE ESCAPE. REMEDY: MAKE AREA SAFE, REMOVE FROM UNDER A/C UNITS AND INSTALL WITH METAL SUPPORTS, REMNothing owed — awaiting certificate of correction
ECB04/27/2004OCCUPANCY CONTRARY TO THAT ALLOWED BY THE COFO COFO#764-42 STATES CELLAR 1-3RM APT CUPER STORAGE BOILER GARAGE RM& DOCATORS OFFICE NOW ILLEGAL CONVERSION OF DOCTORS OFFICE TO 1 CLASS APT 3 RM APT SUPERNothing owed — awaiting certificate of correction
ECB04/27/2004WORK WITHOUT PERMITS CONSTRUCTED PARTITION WALLS TO CREATE 1 LIVING RMWALLS CONST OF SHEETROCK & WOOD FRAMES INSTALLED GAS LINE TO CREAT KI TCHEN CONST A 3 PIECE BATHROOM(NOTE NO MECHANICAL VENTILATION NO WINDONothing owed — awaiting certificate of correction
ECB09/18/199511Q,14M,35P.Nothing owed — awaiting certificate of correction
ECB03/01/199314M,08V,28H,57O,35P,74O, 35-NO ACCESS 74-CLEAN TOP OF CAR.Nothing owed — awaiting certificate of correction
ECB06/03/199150X,21I,08V 74-A PROVIDE 5YR TEST ON GOVERNOR AVD TAG SAME.Nothing owed — awaiting certificate of correction