ECB05/05/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR SUMMONS # 39518634L ISSUED 6/30/23., FILE A CERTIFICATE OF CORRECTION$1K due
HPD04/26/2026§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF BICYCLES AT PUBLIC HALL, 2nd STORY
DOB02/26/2026FTM BLDG IN A CODE COMPLIANT MANNER-OBSVD DETERIORATED CORNICE @ EXP1/ 4 CORNER AND 1/2 CORNER. OBSVD LOOSE AND MISSING SIDING AT EXP4 OWNER TO IMMED RETAIN NYSPE TO EVAL THE ENTIRE BLDG,PREPARE/FILE REPAIR DEGS, REPAIR BLDG UNDER PERMIT, START WORK BY 4/26/26
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
ECB03/12/2024WEILMCLAIN EGH-85 BOILER= IS INSTALLED WITHOUT A DOB PERMIT> SEE PERMIT 301704494 AND SIGNOFF;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION$6K due
ECB03/12/2024WEILMCLAIN EGH-85 BOILER=OUTSIDE FRESH AIR INLET BLOCKED/DEBRIS IN BOILER ROOM/GRD FLOOR HALL RADIATOR IMPERATIVE/MISSING A CHIMNEY BASE CLEANOUT;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION$3K due
ECB06/30/2023NOTED: AT TIME OF INSPECTION, OBSERVED THE CELLAR WITH HOLES IN THE CEILING IN VARIOUS AREAS THROUGHOUT. LEAVING THE WOOD MEMBERS EXPOSED. CREATING A HAZARDOUS CONDITION IN THE EVENT OF A FIRE.$6K due
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
HPD12/27/2022§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD10/20/2022§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR .. IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
HPD10/17/2022§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
DOB01/17/2020VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2013 INSPECTION REPORT
DOB03/01/2013VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2011 INSPECTION REPORT
DOB12/13/2011VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2010 INSPECTION REPORT
DOB12/02/2010FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD09/02/2010§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM ..
HPD09/02/2010§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
HPD09/02/2010§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM AT CELLAR
HPD09/02/2010§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
DOB12/31/2009V-DOB VIOLATION - ACTIVE
DOB06/25/2009FAILURE TO MAINTAIN BUILDING REMEDY; MAINTAIN BUILDING-MAKE REQUIRED REPAIRS IMMEDIATELY PROVE ENGINEERS REPORT AS PER COMMISSIONER'S ORDER
DOB01/01/2009V-DOB VIOLATION - ACTIVE
DOB01/03/2008V-DOB VIOLATION - ACTIVE
DOB01/19/2007V-DOB VIOLATION - ACTIVE
HPD10/25/1998§ 27-2040 ADM CODE PROVIDE ADEQUATE LIGHTING AT OR NEAR THE OUTSIDE OF THE FRONT ENTRANCEWAY OF THE BUILDING AND KEEP SAME BURNING FROM SUNSET EVERY DAY TO SUNRISE ON THE DAY FOLLOWING 100 WATT INCAND REQUIRED FIXTURE PRESENT LIGHT NOT ON
HPD06/05/1990§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING CEILING LIGHT FIXTURE 3 STY NORTH APT 3L 1ST ROOM FROM KITCHEN
HPD06/05/1990D26-16.01 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET BATHROOM 3RD STY WEST APT 3L.
HPD06/05/1990§ 27-2044 ADM CODE REPLACE OR REPAIR THE SELF-CLOSING THE DOORS THAT IS MISSING OR DEFECTIVE ENTRANCE TO 3 STY NORTH APT 3L
HPD06/05/1990§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF EXPOSED ELECTRICAL WIRING CEILING 3 STY NORTH APT 3L 1ST ROOM FROM KITCHEN
HPD06/05/1990D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CEMENT PLASTER WALLS KITCHEN 3RD STY WEST APT 3L.
HPD05/31/1990D26-10.01, 10.05 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF BLDG MATERIAL 2 STY PUB HALL.
HPD05/31/1990D26-10.01, 10.05 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF WOOD CHAIRS ETC AT 3RD STY PUBLIC HALL.
HPD05/31/1990§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE NORTH WALL AND CEILING 3 STY PUBLIC HALL
HPD05/31/1990§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING DOUBLE CYLINDER KEY OPERATED LOCK INSTALLED ENTRANCE DOOR TO BLDG
HPD05/31/1990§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE CELLAR THRU OUT
HPD05/31/1990§ 27-2037 ADM CODE PROVIDE ADEQUATE LIGHTING CELLAR THRU OUT
HPD05/31/1990§ 27-2039 ADM CODE PROVIDE ADEQUATE LIGHT OF NOT LESS THAN 60 WATTS INCANDESCENT OR EQUIVALENT ILLUMINATION VESTIBULE AND 2 STY PUBLIC HALL
HPD05/31/1990§ 27-2048 ADM CODE PAINT OR POST A SIGN INDICATING FLOORS ON WALL AT OR NEAR STAIRS PUBLIC HALL ALL STYS
HPD05/31/1990§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE WASHBASIN 2 STY NORTH APT 2L BATHROOM
HPD05/31/1990D26-10.01 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE PARAPET WALLS 1 STY EXTENSION ROOF AT ROOM.
HPD05/31/1990§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR FRAME MISSING.
HPD05/31/1990D26-20.01 ADM CODE PROVIDE A PEEP HOLE IN ENTRANCE DOOR OF THE DWELLING UNIT SO LOCATED SO AS TO PERMIT A PERSON INSIDE THE DWELLING TO VIEW ANY PERSON OUTSIDE ENTRANCE DOOR 2ND STY EAST APT.
HPD05/31/1990D26-10.01 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR NORTH WALL 2 ROOM FROM FRONT 2 STY NORTH APT 2L.
HPD05/31/1990D26-16.01 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS SINK KITCHEN 2 STY NORTH APT 2L.
HPD05/31/1990D26-10.01 ADM CODE REPLACE WITH NEW THE MISSING CHAIN DOOR GUARD 2 STY NORTH APT 2L.
HPD05/31/1990D26-10.01 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE WOOD FLOOR NEAR SINK & STOVE KITCHEN 2 STY NORTH APT 2L.
HPD05/31/1990D26-12.01 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CLGS & WALLS THRU OUT 2 STY NORTH APT 2L.
HPD05/31/1990D26-10.01 ADM CODE REPLACE WITH NEW THE MISSING DOOR KNOBS DOOR BATHROOM 2 STY NORTH APT 2L.
HPD05/31/1990D26-10.01, 10.05 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES EXCESSIVE WIRES AND RUBBISH ALL STYS REAR.
HPD05/31/1990D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PLASTERBOARD CLG CELLAR FRONT.
HPD05/31/1990D26-11.01, 11.03, 11.05 ADM CODE CLEANSE AND DISINFECT TO THE SATISFACTION OF THIS DEPARTMENT AFTER REMOVING THE WATER CELLAR FRONT.
HPD05/31/1990§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE BALUSTRADE AT STAIRS 1 TO 2 STY PUBLIC HALL
HPD01/18/1984D26-15.01 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES KITCHEN & BATHROOM 2 STY NORTHWEST APT 3L.
HPD11/24/1982D26-17.07 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES KITCHEN & BATHROOM 2 STY APT 2.
HPD11/23/1982D26-10.01 ADM CODE REPLACE WITH NEW THE MISSING GLASS LOWER SASH AT KITCHEN 2 STY APT 2 ER1.
HPD11/23/1982D26-13.03 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN MICE AND ROACHES 2 STY APT 2.
HPD11/23/1982D26-10.01 ADM CODE REPLACE WITH NEW THE MISSING GLASS LOWER SASH NORTHWEST ROOM 2 STY APT 2 ER1.
HPD11/23/1982D26-10.01 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF CASCADING WATER LEAK AT BATHROOM CLG 2 STY APT 2 ER1.
ECB08/23/2014WORK W/O A PERMIT WORK NOTED:CELLAR ERECTED APPROX FOUR TALLY COLUMNS THAT ARE SUPPORTING THE GURDER.REM:OBTAIN PERMIT OR RESTORE PREMISES TO PRIOR LEGAL CONDITION.Nothing owed — awaiting certificate of correction
ECB06/30/2009WORK W/O PERMITS NOTED FULL LOT REAR HORIZONTAL EXTENSION W/ ASSOCIATED LIGHTING & ELECTRIC & WATER WASTE AND GAS LINES INSTALLED FOR RESIDENTIAL KTCN AND THREE PIECE BTRM TO CREATE ILLEGAL CLASS A APT AT REARNothing owed — awaiting certificate of correction
ECB03/27/2009FAILURE TO MAINTAIN BLDG WALL DEFECT NOTED AT EXP 4 WALL LEANING APPROX 6 OUTWARD AT APT 2R FLRS HAVE APPROX 5-6 DEFLECTION TOWARDS EXP 4 WALL INTERIOR STAIRWELL LEANING APPROX 5-6 REMEDY: FACILITATE REPAIRSNothing owed — awaiting certificate of correction
ECB12/10/2008FAILURE TO MAINTAIN BLDG *HAZARDOUS*. 2ND OFFENSE PRIOR ECB #34574064NNOTED: AT CELLAR - SUPPORT GIRDER SPLIT, NUMEROUS FLOOR JOISTS ROTTED,AT NORTH/WEST ELEVATION - EXTERIOR STUCCO CRACKED, DISPLACED ANDNothing owed — awaiting certificate of correction
ECB10/22/2008FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.NOTE:AT CELLAR LEVELOF ABOVE PREMISES FIRE STOPPING @ CEILING MISSING THROUGOUT.REMEDY: MAINTAIN BLDG.REPAIR DEFECTS.Nothing owed — awaiting certificate of correction
ECB10/22/2008FILING A FALSE CERTIFICATION W/NYC DEPT OF BLDG.PURSUANT TO SECTION 28-204.2 RESPONDENT FILED A CERTIFICATE OF CORRECTION FOR NOV #34611700P ON 7/29/2008.AN INSPECTION MADE ON 10/22/08 WHICH RESULTED IN ISSUANCNothing owed — awaiting certificate of correction
ECB10/22/2008FAILURE TO COMPLY W/THE COMMISSIONERS ORDER TO CORRECT THE VIOLATING CONDITION & FILE A CERTIFICATE OF CORRECTION W/THE NYC DEPT OF BLDG FORNOV 34611700P.REMEDY:CORRECT THE VIOLATING CONDITION & FILE A CERTIFICNothing owed — awaiting certificate of correction
ECB05/10/2007FAILURE TO MAINTAIN BLDG.DEFECTS NOTED:AT CELLAR LEVEL OF ABOVE PREMISS NUMEROUS BEAMS ARE ROTTED AND AT LEAST ONE OF SAID BEAMS HAS SPLIT.NUMEROUS SECTION OF FIRE STOPPING IS MISSING FROM CEILING AT CELLARNothing owed — awaiting certificate of correction