HPD08/13/2026§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING KEYED LOCK AT BULKHEAD DOOR AT PUBLIC HALL STAIRS, 4th STORY
HPD07/15/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE-RETARDANT MATERIAL AT CEILING AT BASEMENT
ECB07/15/2026ATOI OBSERVED PVC PIPE USED ON EXHAUST VENT OF WATER HEATERS, T&P VALVE CAPPED OFF ON 1 HEATER PER.FUEL GAS CODE 501.15 - PER PC 102.3 INSTALLATIONS BOTH EXISTING AND NEW AND PARTS THEREOF SHALL BE MAINTAINED I$2K due
HPD07/15/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE-RETARDANT MATERIAL AT CEILING AT BASEMENT
HPD07/15/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE BRICKWORK AND MORTAR JOINTS AT WEST SIDE OF WEST CHIMNEY STACK AT ROOF
HPD07/15/2026§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRES AT CEILING AT BASEMENT
HPD07/15/2026§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF FORCED AIR KEROSONE HEATERS AT BASEMENT
HPD07/15/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT CEILING AND WEST WALL AT BASEMENT
HPD07/15/2026§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK INSTALLED AT DOOR TO ROOM WITH FIRE ESCAPE IN THE 1st ROOM FROM NORTH LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD07/15/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT CEILING AT BASEMENT
HPD07/15/2026§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF FORCED AIR KEROSENE HEATERS AT BASEMENT
HPD07/15/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT DOOR TO ROOF AT BULKHEAD AT PUBLIC HALL, 4th STORY
HPD07/15/2026§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING LATCH AT DOOR TO ROOF AT BULKHEAD AT PUBLIC HALL, 4th STORY
HPD07/15/2026§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY
HPD07/15/2026§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRES AT CEILING AT BASEMENT
HPD07/15/2026§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD07/15/2026§ 27-2005 ADM CODE PROVIDE OPERABLE DOOR KNOB ALLOWING RE-ENTRY FROM ROOF TO BULKHEAD AT PUBLIC HALL, 4th STORY
HPD07/15/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR PANELS IN THE 7th ROOM FROM NORTH LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
ECB07/15/2026ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED ON THE ROOF THE REMOVAL OF ONE A/C CONDENSER REMOVED BY TECHNICIAN. CHECKED BIS / DOB NOW NO PERMIT ON FILE. ALL WORK MUST BE FILED WITH DOB. MUST BE DONE BY LICESEND$2K due
HPD07/03/2026§ 27-2005, 2007 ADM CODE REMOVE ALL ENCUMBRANCES CONSISTING OF BICYCLE AT PUBLIC HALL, 1st STORY
HPD04/15/2026HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1B, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH
HPD04/15/2026HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1B, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH
HPD04/15/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT PLASTER AT CEILING AT CELLAR
HPD04/15/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 1B, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH
HPD04/15/2026§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 1B, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH
HPD04/15/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR TO REAR YARD IN THE 1st ROOM FROM NORTH LOCATED AT APT 1B, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH
HPD04/15/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 1B, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH ORIGINAL VIOLATION 18788995 ISSUED 15-APR-26 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
HPD03/13/2026§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD03/13/2026HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD03/13/2026§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES NO VOLUME AT SHOWER STALL IN THE 2nd BATHROOM FROM EAST LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD03/13/2026§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF COLD WATER FOR THE FIXTURES NO VOLUME AT SHOWER STALL IN THE 2nd BATHROOM FROM EAST LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD03/13/2026§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS AND REPAIR ALL DEFECTS IN WASTE LINE AT WASH BASIN IN THE BATHROOM LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD03/13/2026§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD03/08/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL VENTILATION AT CEILING IN THE KITCHEN LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/08/2026§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES THAT IS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/08/2026§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF LOCKABLE KNOB AT DOOR PREVENTING ENTRANCE TO FIRE ESCAPE IN THE 1st ROOM FROM NORTH LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/08/2026§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS THAT IS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/08/2026§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT SHOWERSTALL IN THE BATHROOM LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/08/2026§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/08/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/08/2026§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BASEMENT AT BOILER ROOM
HPD03/08/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT NORTH WALL IN THE KITCHEN LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/04/2026§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT 1ST STORY PUBLIC HALL LEADING TO BASEMENT TO BOILER ROOM. AT BOILER ROOM, 1st STORY
HPD02/23/2026§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF KEY OPERATED LOCK AT DOOR TO FIRE ESCAPE WINDOW IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2R, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST
HPD02/23/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE KITCHEN LOCATED AT APT 2R, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB10/28/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB07/27/2020FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. AT TIME OF INSPECTIONOBSERVED TERRACOTTA FACADE MISSING & DISMEMBERED AT EXP#1 ABOVE & BELOW WINDOW OPENINGS. ALSO OBSERVED MISSING & DISMEMBERED BRICKS AT 4TH F$2K due
DOB07/11/2018FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB07/11/2018FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB07/11/2018FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB03/07/2018ACCESS TO PREMISES TO INSPECT APPROVED WORK UNDER ACTIVE PLUMBING JOB #321580945 DENIED. INSPECTION TIME 11:15AM ON ABOVE DATE. NEED ACCESS TO VERIFY WORK. PROVIDE ACCESS TO DEPARTMENT PERSONNEL
DOB07/12/2017FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB02/10/2016FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB02/10/2016FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD10/18/2015§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE RADIATOR AND STEAM PIPES IN THE 3rd ROOM FROM NORTH LOCATED AT APT 4R, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD10/18/2015§ 27-2005 ADM CODE REPLACE WITH NEW THE BROKEN OR DEFECTIVE RADIATOR AND STEAM PIPES IN THE 4th ROOM FROM NORTH AT EAST LOCATED AT APT 4R, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
DOB08/16/1993V-DOB VIOLATION - ACTIVE
HPD08/19/1991§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING DOUBLE CYLINDER KEY OPERATED LOCK INSTALLED ENTRANCE DOOR STREET TO VESTIBULE.
ECB04/18/2018GAS BEING SUPPLIED TO W/OUT INSP & CERT BY DOB @TIME OF INSP IN CELLAR,I OBSERVED NEW GAS LINE FOR BOILER WHICH IS USED FOR LAUNDROMAT GAS LINE FOR BOILER WAS WAS INSTALLED UNDER PERMIT # 321580945,BUT NO PLUMBNothing owed — awaiting certificate of correction
ECB04/18/2018FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.@TIME OF INSP IN LAUNDROMAT .I OBSERVED 20 GAS DRYERS WHICH USE FLEXIBLE GAS CONNECTIONS,&FLEXIBKE FLUE PIPES OBSERVED FUTURE TEE ON GAS LINE FOR BOILER.*PHOTONothing owed — awaiting certificate of correction
ECB04/18/2018FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER CODE OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.2;27-954 @TIME OF INSP IN LAUDROMAT I OBSERVED 20 GAS FIRED DRYERS & NO SPRINKLER PROTECTION.Nothing owed — awaiting certificate of correction
ECB04/19/2017B265 AS PER CLASS 2 (B265) 28-303.7 FAILURE TO FILE A COMPLETE BOILERINSPECTION REPORT AS PER DOB RECORDS. SUBMIT A CURRENT B09 REPORT.Nothing owed — awaiting certificate of correction
ECB04/19/2017B154(36,51)AS PER CLASS 1(B154)28-301.1 FAILURE TO REGISTER BOILER AS PER DOB RECORDS. CORRECT ALL VIOLATING CONDITIONS AND HAVE BOILER REGISTEREDNothing owed — awaiting certificate of correction
ECB11/18/2015B101 LAAPS 750,000 BTU LAUNDRY HOT WATER BOILER HLW STAMPERD INSTALLEDW/O PERMIT.Nothing owed — awaiting certificate of correction
ECB11/18/2015B154,51,6A,7D,15,24B,32A. 51-FLUE OUTLET REDUCED ON LAARS. LAUNDRY HOTWATER BOILER (HLW) 750,000 BTU'S *REPAIR IMMEDIATELY ALL HAZARDOUS CONDITIONS,AND CALL DOB 212-393-2661 TO LIFT CEASE USE ORDER.Nothing owed — awaiting certificate of correction
ECB11/18/2015B154,50. 50-GOOD MAN HOT AIR FURNACE IN 4TH FLOOR APARTMENT, ILLEGAL GAS AND ELECTRIC CONNECTIONS.Nothing owed — awaiting certificate of correction
ECB10/14/2014FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED AT TIME OF INSPECTION. ALUMINUM SIGN HANGING W/ROTTED WOOD & RUSTY NAILS EXPOSED CREATING A FANGER TO THE PUBLIC. REMEDY: REMOVE SIGN & MAKE SAFE.Nothing owed — awaiting certificate of correction