ECB06/29/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE GARBAGE, OBSTRUCTING THE EMERGENCY EXIT. LOCATED AT BASEMENT LEVEL, REPAIR AND/OR REPLACEHearing held — result not yet published$1K proposed
ECB06/29/2026FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN THE MAIN ELECTRICAL NO INSTALLATION OF ELECTRODE GROUND ROD ALSO NO MAIN WATER GROUND CLAMP OR WIRE IS PRESENT. POTENTINAL ELECTRICAL SHOCK NEC ARTICLE 250 GROUHearing held — result not yet published$5K proposed
ECB06/29/2026UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. STORAGE WAS OBSERVED WITHIN BOILER ROOM. LOCATED AT BASEMENT LEVEL, MAINTAIN STORAGE IN COMPLIANCE WITH FIRE CODEHearing held — result not yet published$2K proposed
ECB06/29/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED FIRE ESCAPE OBSTRUCTED WITH AC UNITS (EMERGENCY EGRESS). LOCATED AT EXPOSURE 1, REPAIR AND/REPLACEHearing held — result not yet published$2K proposed
ECB06/29/2026ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL ROOM THE STORAGE OF BUILDING SUPPLIES LADDER, BUCKETS, VACUUMS. POTENTINAL FIRE ELECTRICAL CLOSTES / ROHearing held — result not yet published$1K proposed
ECB06/29/2026UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED THRU OUT HALLWAYS THE RECEPTACLES ARE NOT TAMPER RESISTANT. THE STAIRWELL LIGHTS ARE NOT IHearing held — result not yet published$2K proposed
ECB06/29/2026FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT PER EC. OBSERVED THE ELEVATOR SAFETY DISCONNECT SW THAT THE OVER CURRENT IS FUSED INCORRECTLY 125 AMPS. ALSO ITS FUSED FOR TWO DEVICES. POTENTINAL FIRE / SHOCHearing held — result not yet published$2K proposed
ECB06/29/2026MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON ALL FLOORS 1-6 THAT THE ELECTRICAL PANELS IN HALLWAYS HAVE NO ARC FLASH LABELING ON THE FRONT DOOR. THIS TO SHOW THAT THE PANEL ISHearing held — result not yet published$800 proposed
ECB06/24/2026CLASS 2: 1) MOTOR ROOM IS BEING USED AS A STORAGE AREA, CONTRARY TO ASME A17.1/CSA B44 8.6. REMEDY: REMOVE ALL STORED ITEMS AND MAINTAIN MOTOR ROOM CLEAR AND ACCESSIBLE. 2) LENS MISSING FOR DOOR RE-OPENING DEVIHearing held — result not yet published$310 proposed
ECB06/24/2026LOCHINVAR BLR HAS ILLEGAL DRAFT STATÝHAS DRAFT HOOD¨ILLEGAL DRAFT INDUCERÝNOT@CHIMNEY BASE W/DRAFT PROVING SWITCH INTERLOCKED W/ALL UNITS+COMBUSTION AIR FAN NOT DUCKED TO THE OUTDOORS W/AIR PROVING SWITCHÝINTERHearing held — result not yet published$620 proposed