DOB04/28/2023AT THE TIME OF INSPECTION OF 6 FLOOR PARKING GARAGE I OBSERVED AT 2ND,3RD,4TH,5TH FLOORS AT 41 AVENUE SIDE CLOSE TO STAIRS, RUSTED STRUCTURAL LOAD BEARING STEEL BEAMS WITH CHUNKS SEPARATING AND FALLING
ECB04/28/2023AT THE TIME OF INSPECTION OF 6 FLOOR PARKING GARAGE I OBSERVED AT 2ND,3RD,4TH,5TH FLOORS AT 41 AVENUE SIDE CLOSE TO STAIRS, RUSTED STRUCTURAL LOAD BEARING STEEL BEAMS WITH CHUNKS SEPARATING AND FALLING., REPAIRNothing owed — awaiting certificate of correction
ECB11/01/2014FAILURE TO MAINTAIN.NOTED:(1)HEAVILEY CORRODED STEEL POSTS @ STAIRS WAYS & STEEL POSTS @ STAIR WAYS & STEEL BEAMS @ CEILING(GARAGE)(2)CURBS/WHEELCHOCKS NOT SECURED IN GARAGE PARKING SPACES.PERMIT ISSUED NO WORKNothing owed — awaiting certificate of correction
ECB11/06/2013EXIT PASSAGEWAY TOTAL OBSTRUCTION AT 5 FLOOR NORTHSIDE,MULTIPLE CARS BLOCKING STAIRCASE.RMDY: REMOVE OBSTRUCTION.Nothing owed — awaiting certificate of correction
ECB11/04/2013FAILURE TO MAINTAIN NOTED CURBS FOR CAR PARKING SPACES ARE LOOSE AND NOT AFFIXED TO SLAB. RMDY: SECURE CURBS TO SLAB.Nothing owed — awaiting certificate of correction
ECB11/04/2013FAILURE TO MAINTAIN; NOTED STEEL SUPPORTS FOR STAIRCASE AND OTHER STRUCTURAL STEEL SEVERELY CORRODED WITH FLAKING.RMDY: PROVIDE ENGINEERS REPORT ON REMEDIAL ACTION TO BE DONENothing owed — awaiting certificate of correction
ECB12/21/201127-464)FAILURE TO PROVIDE PARKING CURBS OR BUMPERS.NOTED:@ GARAGE NO CURBS OR BUMPERS INSTALLED TO PROTECT PERIMETER WALLS FROM VEHICLE CONTACT @ ALL TIERS/LEVELS.REM:PROVIDE PERIMETER PROTECTION PER CODE.Nothing owed — awaiting certificate of correction
ECB12/21/2011OCCUPANCY CONTRARY TO CERT OF OCCUPANCY.NOTED:@ GARAGE OVER CROWDING OF GARAGE W/ 670 PARKED VEHICLES CONTRARY TO CERT OF OCCUPANCY #4P0009036 ISSUED 4/25/95 WHICH STATES TOTAL # OF CARS=576.REM:COMPLY W/ CODE.Nothing owed — awaiting certificate of correction
ECB12/17/2009FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. NOTED: STEEL BEAM IS RUSTED LOCATED ON THE 4TH FLR LEVEL ADJACENT TO 41 AVE. REMEDY: REPAIR/REPLACE STEEL BEAM.Nothing owed — awaiting certificate of correction
ECB12/27/2007FAILURE TO MAINTAIN.NOTE:SIGNIFICANT CORROSION,PITTING & FLAKING OFF OF ( )SECTIONS OF I BEAMS LOCATED ON FLOORS 2,3,4 THE 6 BEAM FROMSOUTH END STRUCTURE.REMEDY:MAINTAIN BLDG - RENAL CORRED AREAS PRIME &Nothing owed — awaiting certificate of correction
ECB12/27/2007SEC.27-464.NO CURBS OR BUMPERS INSTALLED TO PREVENT VEHICULAR CONTACT W/WALLS THROUGHOUT(AT PARAPETS & EXT WALLS)ALL LEVELS AS REQUIRED BY SECTION 27-464 OF THE CODE.REMEDY:PROVIDE CURBS OR BUMPERS AS REQUIREDNothing owed — awaiting certificate of correction
ECB12/27/2007FAILURE TO MAINTAIN.NOTE:EXIT LIGHTS ON FLOORS 2,3,4 NOT WORKING.REMEDY:MAINTAIN BLDG.Nothing owed — awaiting certificate of correction
ECB12/07/2005EXIT SIGN DEFECTIVE/FAILS TO MEET BLDG CODE STANDARDS. NOTED: ROOF, 41AVENUE SIDE MISSING EXIT SIGN & LEVEL 5 AT STAIRWELL/ELEVATORS. LEVEL 5, 41 AVENUE SIDE INOPERATIVE & MISSING SIGN FACE. LEVEL 4, 3 & 2, 41Nothing owed — awaiting certificate of correction