ECB10/20/2025Exit door not self-closing. Observed emergency exits doors non self closing. Located on the east and west wings of the building on the 1ST floor. Potential fire hazard., repair/replace doorNothing owed — awaiting certificate of correction
ECB12/08/2022Failure to comply with commissioners request for certificate of correction for violation #39049048JNothing owed — awaiting certificate of correction
ECB11/23/2022Failure to comply with commissioners request for certificate of correction for violation #39049047HNothing owed — awaiting certificate of correction
ECB12/15/2021Exit door not self-closing. Observed at basement level,exit doors on staircase#a,g&i,doors do not close automatically due to door leaves overlapping the frame,excessive corrosion and other failure. Also,exit doNothing owed — awaiting certificate of correction
ECB10/14/2021Found hb smith water boiler serial# 101875 not registered register the boiler and submit a certificate of correctionNothing owed — awaiting certificate of correction
ECB10/08/2021Found hb smith water boiler serial# 162620 not registered register the boiler and submit a certificate of correctionNothing owed — awaiting certificate of correction
ECB01/22/2021Combustion air intake screen clogging. Correct all violating conditions and submit a certificate of correction.Nothing owed — awaiting certificate of correction
ECB01/22/2021Register the boiler and submit a certificate of correction.Nothing owed — awaiting certificate of correction
ECB01/22/2021Correct all violating conditions and submit a certificate of correction.Nothing owed — awaiting certificate of correction
ECB01/22/2021Register the boiler and submit a certificate of correctionNothing owed — awaiting certificate of correction
ECB03/16/2020Found 1 hb smith 28A-12 gas fired hot water boiler not registered. Register boilerNothing owed — awaiting certificate of correction
ECB03/16/2020Found 1 hb smith 28HE-12 gas fired hot water boiler not registered. Register boilerNothing owed — awaiting certificate of correction
ECB10/04/2019Found unregistered hb smith mdl# 28A-12 boiler. Register boiler and submit a certificate of correction.Nothing owed — awaiting certificate of correction
ECB10/04/2019Found unregistered hb smith mdl# 28HE-12 boiler. Register boiler and submit a certificate of correction.Nothing owed — awaiting certificate of correction
ECB05/07/2019Failure to maintain building in code-compliant manner.@ east section,@rd sty corridor & 3RD sty stairwell, water penetration @ ceiling.plaster @ceiling flaking anf falling directly onto tenant walkway.rem:Nothing owed — awaiting certificate of correction
ECB05/07/2019Exit door not self-closing, noted:@wwest section, @cellar lvl, 4 of 4 emergency exit doors not self closing. Emergency exit doors located inthe child care area.rem: repair/replace doors.Nothing owed — awaiting certificate of correction
ECB02/06/2019Failure to maintain building in code compliant manner. No fire stopping per 712.3; 27-345. Noted at cellar level, observed several holes in ceiling and walls in several areas throughout cellar eliminating fireNothing owed — awaiting certificate of correction
ECB07/10/201836)found 2-hb smith boilers not registered and permit expired. Register boilers.Nothing owed — awaiting certificate of correction
ECB07/14/2017Unsafe/unapproved/unsuitable electrical equipment, materials,apparatusdevices,appliances or wiring in use. Observed receptacles throughout corridors not child proof or jumper resistant.exhaust fan k-92 defectiNothing owed — awaiting certificate of correction
ECB06/07/201736,32A,50A 36,found hb smith gas fired boiler not registered 50A no storage in boiler room.register the boiler and correct violating condition,submit the certificate of correction.Nothing owed — awaiting certificate of correction
ECB06/07/201736,32A,50,a 36 found hb smith boiler not registered. 50A fresh air l ouver clogged no air register the boiler and correct all violating conditions,submit the certificate of correction.Nothing owed — awaiting certificate of correction
ECB01/24/2017Altered blg occupied w/o a valid certificate of occupancy as per 28-118.3.1, 28-118.3.2 note: tco#400047141 expired 6-7-1994, bldg fully occupied at time of inspection. Rmdy:obtain a valid certificate of occupaNothing owed — awaiting certificate of correction
ECB02/16/2016Exit door not self closing.note:exit #10, the door has an inoperative door closer and remains open after exiting. Rem:comply w/code, repair door closer.Nothing owed — awaiting certificate of correction
ECB06/27/2015B101/ work without permit. H.b. Smith 28A-12 boiler. Power flame CR3-G25.Nothing owed — awaiting certificate of correction
ECB06/27/2015B251/34A/50A/50B/ 50A-manual reset low water cut off missing. 50B-covers missing on controls.Nothing owed — awaiting certificate of correction
ECB06/27/2015B154/32A/34A/50A/50B/50C/ 50A-shut down cease use boiler leaking front section. 50B-exposed wires. 50C-jacket off. 50C-missing covers - do not operate boiler until all hazardous conditions are immediately corNothing owed — awaiting certificate of correction
ECB03/10/2015Failure to comply w/commissioner's order to file certificate of correction with DOB. Observed on march 6 2015 2:40PM boiler room water piping not corrected as per viol #35066861L. Rmdy: file a certificate of coNothing owed — awaiting certificate of correction
ECB08/20/2014Sprinkler system is not properly painted. Failure to paint dedicated sprinkler piping. During physical inspection i observed that there are section of the dedicated overhread sprinkler main supply line not paiNothing owed — awaiting certificate of correction
ECB08/20/2014Unapproved, unsafe, unsuitable, electrical equipment, materials, devices, appliances or wiring is in use. Noted: throughout all floors, halls, hallways, corridors, stairwells & closets, exit lights, wallpacks,Nothing owed — awaiting certificate of correction
ECB08/20/2014Use or installation of plumbing material which do not comply with rs-16. During physical inspection i observed a section of black iron pipe connected to the brass domestic water line in the boiler room. BlackNothing owed — awaiting certificate of correction
ECB08/20/2014Failure to provide a system of automatic sprinkler system where required. During physical inspection i observed that there are no sprinklers provided for the supply room on the 1ST floor containing flamable prNothing owed — awaiting certificate of correction
ECB08/20/2014Work without permit. Illegal work noted: at cellar level elevator machine room sub-divided to create storage room. Remedy: obtain permit.Nothing owed — awaiting certificate of correction
ECB08/20/2014Electrical closet not dedicated to electrical distribution equipment only. Noted: at time of inspection, in electrical service room used as storage room also, misc materials are being stored in front of, arounNothing owed — awaiting certificate of correction
ECB08/20/2014Failure to provide unobstructed exit passageway. Noted: at 1ST floor main entry large desk in place obstructing passage flow to exit doors. Remedy: remove desk.Nothing owed — awaiting certificate of correction
ECB08/20/2014Failure to maintain. Noted: exit door #8 stuck shut. Also corridor doors not closing properly when released. Illegal door stops on fpsc doors. Remedy: comply with code.Nothing owed — awaiting certificate of correction
ECB08/20/2014Failure to maintain. Noted: east side corridor ventilation system not operational at time of inspection. Remedy: repair / replace system.Nothing owed — awaiting certificate of correction
ECB08/20/2014Altered bldg occupied without a valid cert of occupancy as per 28-118.3.1, 28-118.3.2, tco# 400047141 expired 9-7-1994, bldg fully occupied at time of inspection. Remedy: obtain valid c of o.Nothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB11/14/2025Violation issued-failure to file 2024 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered2 identical filings
Old · issued 3+ years ago and still listed by DOB; nothing on the city's records either way
DOB07/01/2021Elevator: elevatorrequired (DOB violation)Issued 2021; DOB's record still lists it as active