ECB05/04/2026Re-issue #35721076Y. Failure to maintain. No fire-stopping per bc 172.3; 27-345. Noted: inside gas meter room, there section of cmu blocks removed approx: 24" x 24" opening and can not have fire-stopping applieNothing owed — awaiting certificate of correction
ECB05/04/2026Failure to maintain building in code-compliant manner. Noted: interiorfire-proof doors do not self-close properly at 2ND flr-staircase "a". Classroom doors do not self-close properly when testedat 4THF flr rm #Nothing owed — awaiting certificate of correction
ECB05/04/2026Exit door not self-closing. Noted: exterior fire-proof doors do not self-close properly at 1ST flr-exit "8", exit "6", exit "5". Remedy: repair/replace door.Nothing owed — awaiting certificate of correction
ECB08/28/2025Reissue: #35688787Z date of issue: 09-24-2024. Failure to maintain building in code-compliant manner. Illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. At the time of inspectioNothing owed — awaiting certificate of correction
ECB08/28/2025Reissue: 35688786R date of issue: 09-24-2024. Failure to maintain building in code-compliant manner. No fire stopping per bc 712.3; 27-345. At the time of inspection observed and noted at cellar level gas meterNothing owed — awaiting certificate of correction
ECB09/24/2024Reissue #35672258R. Failure to maintain building in code-compliant manner: no firestopping per bc 712.3; 27-345. Noted: at cellar gas meter room with large opening in the cmu wall approx. No firestopping. RemedNothing owed — awaiting certificate of correction
ECB09/24/2024Reissue #35672255L. Failure to maintain building in code-compliant manner. Illumination for exits, exit discharges and public corridor per bc 1006.1; 27-381. Noted: at auditiorium 5 emergency exit lighting founNothing owed — awaiting certificate of correction
ECB06/23/2023Failure to maintain building in code-compliant manner: no fire-stopping per bc 712.3;27-345. Note: observed at cellar level, gas meter room has a large opening approx 32"X32" hole in the cmu wall and adjoiningNothing owed — awaiting certificate of correction
ECB07/07/2022Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed existing emergency lights with battery back-up power at auditNothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB11/14/2025Violation issued-failure to file 2024 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered2 identical filings
DOB11/08/2019Violation issued for failure to file annual boiler 2017 inspection reportThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered2 identical filings