HPD05/18/2025§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF WOOD BLOCK AT FIRE DOOR LEADING TO STAIRS AT PUBLIC HALL, 1st STORY
HPD05/18/2025§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF WOOD BLOCK AT COMPACTOR DOOR AT PUBLIC HALL, 1st STORY
HPD05/18/2025§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING CONSISTING OF WOOD WEDGE AT FIRE DOOR LEADING TO GARBAGE AREA, AT BASEMENT AT PUBLIC HALL
HPD01/04/202528 RCNY § 25-171; & 67 (7)(B) MDL; NYC FIRE CODE § 703.1.3; NYC FIRE CODE § 703.2: ADJUST DOOR TO PREVENT GAPS BETWEEN THE TOP AND SIDE EDGES OF DOOR AND DOOR JAMB EXCEEDING THE MAXIMUM ALLOWABLE CLEARANCE OF 1/8 OF AN INCH AND MAXIMUM ALLOWABLE CLEARANCE OF 3/4 OF AN INCH BETWEEN THE DOOR BOTTOM AND SILL AT FIRE STAIRS EXIT (LABELED AS 4TH FLOOR) AT PUBLIC HALL, 3rd STORY
HPD12/29/2024§ 27-2005, 2007 ADM CODE REMOVE DEVICE PREVENTING DOOR FROM BEING SELF-CLOSING FOR METAL CHAIN TIED TO 2ND FIRE DOOR LEADING FROM LOBBY TO LAUNDRY ROOM AT PUBLIC HALL, BASEMENT ENTRANCE STORY
HPD12/29/2024§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT FIRE DOOR AT NORTH WALL LEADING TO FIRE STAIRS AT PUBLIC HALL, BASEMENT ENTRANCE STORY
HPD12/29/2024§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM NEAR MAILBOX AT BASEMENT
HPD03/13/2024§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES ON DOOR IN THE ENTRANCE LOCATED AT APT 7J, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/13/2024§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7J, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/13/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE RADIATOR CONTROL VALVE AT SOUTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 7J, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD03/13/2024§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 7J, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD01/28/2024§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD01/28/2024§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED, 1st STORY
HPD01/28/2024§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
HPD01/28/2024§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD01/28/2024§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING.
HPD01/28/2024§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY
HPD01/28/2024§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL, 1st STORY
HPD01/28/2024§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY
HPD03/19/2023§ 53, 187, 231 M/D LAW AND DEPARTMENT RULES AND REGULATIONS. PROVIDE A SHOE PROPERLY SECURED TO BOTTOM OF STRING OF DROPLADDER MISSING ON NORTH STACK AT BUILDING FRONT
HPD03/19/2023§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIRCONDITIONER PROTRUDING BEYOND WINDOW SILL AT 3RD STORY BALCONY ON SOUTH STACK AT BUILDING FRONT
HPD03/19/2023§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT BULKHEAD AT PUBLIC HALL, 6th STORY
HPD03/19/2023§ 53, 187, 231 M/D LAW AND DEPARTMENT RULES AND REGULATIONS. PROVIDE A SHOE PROPERLY SECURED TO BOTTOM OF STRING OF DROPLADDER MISSING ON SOUTH STACK AT BUILDING FRONT
HPD03/19/2023§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIRCONDITIONER PROTRUDING BEYOND WINDOW SILL AT 4TH STORY BALCONY ON NORTH STACK AT BUILDING FRONT
HPD01/13/2023§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT BASEMENT AT PUBLIC HALL
HPD01/13/2023§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL
HPD04/01/2022§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL
HPD04/01/2022§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX AT PUBLIC HALL
HPD04/01/2022§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING.
HPD04/01/2022§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL
HPD08/06/2021§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL
HPD08/06/2021§ 27-2021 ADM CODE PROVIDE SUFFICIENT, PROPER AND SEPARATE METAL RECEPTACLES FOR THE DEPOSIT OF GARBAGE, RUBBISH AND OTHER WASTE MATERIAL AND ARRANGE FOR COLLECTION AND DISPOSAL OF SUCH MATERIAL.
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
HPD07/16/2019§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONERS PROTRUDING BEYOND WINDOW SILL AT 5TH ,4TH 3RD AND 2ND STORY BALCONYS, 3RD STACK FROM SOUTH AT EAST (BUILDING FRONT)
HPD07/16/2019§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITONERS PROTRUDING BEYOND WINDOW SILL AT 4TH ,3RD AND 2ND STORY BALCONYS ,1ST STACK FROM SOUTH AT EAST (BUILDING FRONT)
HPD05/31/2019§ 27-2010, 2011, 2012 ADM CODE REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE WEST YARD , (BUILDING REAR )
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
HPD01/24/2017§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION THE WINDOW FRAME. ALL WINDOWS IN THE 1st BEDROOM FROM NORTH LOCATED AT APT 2M, 2nd STORY, 4th APARTMENT FROM WEST AT NORTH
HPD01/24/2017§ 27-2026 ADM CODE REPLACE THE BROKEN OR DEFECTIVE INOPERATIVE WEST RADIATOR IN THE 1st BEDROOM FROM NORTH LOCATED AT APT 2M, 2nd STORY, 4th APARTMENT FROM WEST AT NORTH
HPD10/25/2016§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION FLOOR TO CEILING PARTITION ERECTED CREATING TWO ROOMS OBSTRACTING LIGHT AND VENTILATION AND HEAT TO EAST PART OF THE ROOM IN THE 1st ROOM FROM NORTH LOCATED AT APT 5J, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD10/25/2016§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION FLOOR TO CEILING PARTITION ERECTED CREATING TWO ROOMS OBSTRACTING LIGHT AND VENTILATION AND HEAT TO WEST PART OF THE ROOM IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5D, 4th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD10/25/2016SECTION 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. LOCATED AT APT 3D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST
HPD10/25/2016SECTION 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING LOCATED AT APT 3D, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST
DOB06/10/2015VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2014 INSPECTION/TEST
DOB10/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2013 INSPECTION/TEST
HPD10/16/2006SECTION 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN BEDBUGS IN THE ENTIRE APARTMENT LOCATED AT APT 3J, 3rd STORY
HPD09/07/2005SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILINGS IN THE ENTIRE APARTMENT LOCATED AT APT 1D, 2nd APARTMENT FROM EAST AT SOUTH
HPD09/07/2005SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALLS IN THE BATHROOM LOCATED AT APT 1D, 1st APARTMENT FROM EAST AT SOUTH
HPD12/06/2004SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALLS AND CEILING IN THE ENTIRE APARTMENT LOCATED AT APT 3J, 3rd STORY, APARTMENT AT WEST
HPD12/06/2004SECTION 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN BEDBUGS IN THE ENTIRE APARTMENT LOCATED AT APT 3J, 3rd STORY, APARTMENT AT WEST
HPD09/02/2003SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALLS AND CEILING IN THE BATHROOM LOCATED AT APT 3J, 3rd STORY, APARTMENT AT SOUTH
HPD09/02/2003SECTION 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE WALL IN THE BATHROOM LOCATED AT APT 3J, 3rd STORY, APARTMENT AT SOUTH
HPD09/02/2003SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WALLS AND CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 3J, 3rd STORY, APARTMENT AT SOUTH
HPD09/02/2003SECTION 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF CONCEALED WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 3J, 3rd STORY, APARTMENT AT SOUTH
HPD08/14/2002SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING OF BED ROOM AND FOYER ER-1 IN THE FOYER LOCATED AT APT 3J, 3rd STORY
HPD08/14/2002SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING OF LIVING ROOM ER-1 LOCATED AT APT 3J, 3rd STORY
HPD08/12/2002SECTION 27-2005 ADM CODE REPLACE WITH NEW THE MISSING electrical ceiling fixture at north fire passage,yard to street
HPD08/05/2002SECTION 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS HOPPER DOOR COMPACTOR CLOSET 3RD 5TH & 6TH STORY AT PUBLIC HALL
HPD08/05/2002SECTION 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX 1ST STORY AT PUBLIC HALL
HPD08/05/2002SECTION 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL
HPD09/15/1999SECTION 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF EXPOSED ELECTRICAL WIRES AT CEILING REAR YARD EAST FIRE PASSAGE.
HPD11/08/1995SECTION 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF CONCEALED WATER LEAK 4 STY NORTHWEST APT 4K BATHROOM AND KITCHEN CEILINGS ER1. , SECTION '' ''
HPD03/21/1991SECTION 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM AT LEAST 1 WINDOW OR PROVIDE APPROVED TYPE GATE BASEMENT APT 1F. LOCATED AT APT 1F
HPD03/21/1991SECTION 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF EXCESSIVE STORAGE ELECTRIC METER ROOM REAR EAST BASEMENT.
HPD03/21/1991SECTION 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WALLS BATHROOM 2 STY APT 3J. LOCATED AT APT 3J
HPD03/21/1991SECTION 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION PANELED PARTITION ERECTED SUB DIVIDING EAST ROOM 2 STY APT 3C. LOCATED AT APT 3C
HPD12/27/1989SECTION 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE AT 5 STY SOUTHWEST APT 5H MS DOMADIN. , SECTION '' ''
HPD07/18/1986D26-20.08 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT CELLAR STY PUB HALL.
HPD07/18/1986D26-12.01 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WALLS & CLG ALL ROOMS 4 STY APT 5A 2 FROM NORTH AT WEST. LOCATED AT APT 5A
HPD07/18/1986D26-13.03 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN MICE AT KITCHEN 4 STY APT 5A 2 FROM NORTH AT WEST. LOCATED AT APT 5A
HPD07/18/1986D26-10.01 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF DOUBLE CYLINDER KEY LOCKED ENTRANCE DOOR 4 STY APT 5A 2 FROM NORTH AT WEST. LOCATED AT APT 5A
HPD07/18/1986D26-10.01, 10.05 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS ENTRANCE TO 5 STY APT 6L 3 FROM SOUTH AT WEST. LOCATED AT APT 6L
ECB04/25/2016FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER; PROHIBITED MATERIALS.AT THE ABOVE DATE AT 3:22PM I OBSERVED THE INSTALLATION OF A FUTURE GAS VALVE WITH PLUG ON THE GAS PIPING.FUTURE CONNECTIONS NOT PERMINothing owed — awaiting certificate of correction