DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
ECB06/05/2025REISSUE #35682898Y. FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. NOTED DIAGNAL STEP CRACK WITH SEPERATION AT HAMPTON STREET SIDE 3RDTERRACE NEXT TO EXP #3 AND 4 CORNER. REMEDY: MAINTAIN EXTERIOR BUILDINNothing owed — awaiting certificate of correction
ECB06/05/2025EMERGENCY SIGNS AT ELEVATOR CALL STATIONS MISSING DEFECTIVE OR NON-COMPLIANT WITH SECTION REQUIREMENTS. CELLAR LEVEL ELEVATORS "C" WERE MISSING EMERGENCY SIGNS AND PICTORIAL FLOOR PLAN FOR EVACTUATION IN THE EVNothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35654846Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT CELLAR LEVEL GAS AND ELECTRIC METER ROOMS, FOUNDATION WALLS HAVE DETERIORATING BRICKS AND MORTAR AND CORRODING DECLINING ON CEILINGSNothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35682399X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 718.3; 27-345. AT CELLAR METER ROOM AN APPROX. 8"X8" PENETRATION IN CMU WALL AT FLOOR LEVEL FOR NEW GAS PIPE, NNothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35682896K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED ILLEGAL KICK STOPS MOUNTED ON RM 106, AUDITORIUM EXITS AND 1STNothing owed — awaiting certificate of correction
ECB07/01/2024FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J).NOTED:AUDITORIUM STAIRWELL E FIREPROOF SELF CLOSING DOORS ARE EQUIPPED WITH KICKDOWN DOOR SNothing owed — awaiting certificate of correction
ECB07/01/2024EXIT DOOR NOT SELF CLOSING.NOTED:EXTERIOR EXIT DOORS T EXITS#10 & #3 NOT SELF CLOSING PROPERLY.ALSO BOILER ROOM EXIT DOOR GETS STUDE EXTREMELY DIFFICULT TO OPEN & WILL NOT SELF CLOSE.ADDITIONALLY CORRIDOR SMOKENothing owed — awaiting certificate of correction
ECB07/01/2024FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED A VERTICAL STEP CRACK WITH BRICK SEPARATION AT THE HAMPTON ST SIDE 3RD FL TERRACEEXP#3 & 4 CORNER.REM:MAINTAIN EXTERIOR BUILDING WALLS.Nothing owed — awaiting certificate of correction
ECB07/01/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRESTOPPING PER BC 712.3;27-345.NOTED AT CELLAR LEVEL GAS METER ROOM OR APPROX.8"X8" PENETRATION IN CMU WALL AT FLOOR LEVEL WITH NO FIRESTOPPING IN PLANothing owed — awaiting certificate of correction
ECB10/06/2023FOUND LAARS PNCVO500 GAS FIRED WATER BOILER NOT REGISTERED, MAINTAIN BOILER; REGISTER THE BOILER AND SUBMIT A CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB05/16/202228-301.1 FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:AT TIME OF INSPECTION OBSERVED AT ROOF LEVEL MACHINE RM VERTICAL CRACKS/SEPARATION OF BLOCK WALLS AT CELLAR GAS & ELECTRIC METER ROOMS,W/CRACKED BRICKNothing owed — awaiting certificate of correction
ECB06/17/2021BOILER DOORS OPEN,#1 BOILER HAS CRACKED CHAMBER,2 LOW WATER CUT OFFS ON 1-TAPPING,CLOSE OPEN DUCTS NO WOOD,MISSING VALVE ON SUCTION LINE ON OIL TNK B/4 ANTI SYPHONNothing owed — awaiting certificate of correction
ECB06/17/2021BOILER DOORS OPEN,MISSING RATING PLATE,MISSING INSULATION ON BOILER,WISKA SWITCH MISSING ON LOUVER #2 BLR,COVER MISSING ON CONTROLNothing owed — awaiting certificate of correction
ECB06/02/20212-LOW WATER CUT OFFS ON 1-TAPPING,BOILERS DOORS ARE OPEN,MISSING RATING PLATE,VALVE LEAKING ON BOILERNothing owed — awaiting certificate of correction
ECB05/04/2021FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTED:AT(ROOF LEVEL)MACHINE ROOM VERTICAL CRACKS/SEPARATION OF BLOCK WALLS AT(CELLAR)GAS/ ELECTRIC METER ROOMS W/CRACKED BRICKS MISSING MORTAR CEILING DECKINGNothing owed — awaiting certificate of correction