DOB07/02/2021V-DOB VIOLATION - ACTIVE
DOB06/29/2020V-DOB VIOLATION - ACTIVE
DOB06/01/2016FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB06/01/2016FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB03/08/1996V-DOB VIOLATION - ACTIVE
DOB04/25/19912
ECB05/04/2026REISSUED ECB#35717237Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED INTERIOR WATER DAMAGE DUE TO LEAKS AT EXIT#7,8,9,10 AND 15 MAIN ELECTRICAL ROOM AND WATER SPRINKLER MAIN ROOM.REM:REPAIR AND/ORNothing owed — awaiting certificate of correction
ECB05/04/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED EXIT DOOR#16 BEHIND SCANNING STATIONS IN DISREPAIR,RUSTY WITH HOLES THROUGHOUT.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/04/2026REISSUED ECB#35717239H FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.NOTED EXTERIOR WALLS BECAME POUOUS ALLOWING WATER PENETRATION TO THE INTERIOR SPACES AT EXP#3;BY EXIT#5 AND 6 ELECTRICAL ROOM AND AT SPNothing owed — awaiting certificate of correction
ECB05/04/2026REISSUED ECB#05717240P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED THREE CRACKED WINDOW GLASS PANELS AT EXP#2 AT 3RD FLOOR.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/04/2026REISSUED ECB#35717238X OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS.NOTED AT 2ND FLOOR ROOMS#242 AND #240 ARRANGED AND OCCUPIED AS NURSERY/DAYCARE,CONTRARY TNothing owed — awaiting certificate of correction
ECB04/27/2026EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION.AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 2ND FLOOR STAIRWAY B 1 EXIT DOOR,AT 2ND FLOOR EXIT-4(LANDING AREA)2 EXIT DOOR AT 1ST FLOOR 2 DOOR ATNothing owed — awaiting certificate of correction
ECB04/27/2026REISSUE#35717243K DATE OF ISSUE:05.08.2025 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT THE TIME OF INSPECTION OBSERVED AND NOTED AT CELLAR LEVEL WATER PENETRATING THROUGH FOUNDATION WALLS AT ELECTRNothing owed — awaiting certificate of correction
ECB10/20/2025AMERICAN STANDARD BOILER#4>HAS OIL LEAK@BURNER+@OIL PRESSURE VALVE+WATER LEAKING FROM VAC SYSTEM+MOTORIZED COMBUSTION AIR LOUVER DEFECTIVEÝNOT INTERLOCKED¨+BODY DRAIN PIPES MISSING@SAFETY VALVES;CORRECT VIOLATINothing owed — awaiting certificate of correction
ECB10/20/2025AMERICAN STANDARD BOILER#1>MOTORIZED COMBUSTION AIR LOUVER DEFECTIVE ÝNOT INTERLOCKED WITH BURNER OPERATION¨+BODY DRAIN PIPES MISSING@BOILER SAFETY VALVES;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35671738L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. INTERIOR WATER DAMAGE DUE TO LEAKS AT EXIT 7, 8, 9, 10 AND 15, MAIN ELECTRICAL ROOM AND WATER SPRINKLER MAIN ROOM. SPALLING/CRUMBLING PNothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35671742Y. OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR DOB RECORDS. 2ND FL ROOMS #242 AND 240 ARE ARRANGED AND OCCUPIED AS NURSERY/DAYCARE. CONTRARY TO EXPIRED TCP FROM 1972.Nothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35650734L. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. EXTERIOR WALLS HAVE BECOME POROUS ALLOWING WATER TO INFILTRATE INTERIOR SPACES. AT EXP #3 BY EXIT 5 AND 6 ELECTRICAL ROOM AND AT SPRINKNothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35677433H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT CELLAR LEVEL WATER PENETRATING THROUGH FOUNDATION WALLS AT ELECTRIC METER ROOM AND NEXT DOOR ROOM WITH WATER MAINS. ROOMS B2 AND B3.Nothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE #35557673K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANER. NOTED THREE CRACKED WINDOW GLASS PANELS AY EXP #2, 3RD FLOOR LEVEL. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/20/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. RETAINING WALL AT FRONT BY FLAG POLE, WALL IS CRACKED AND BRICKS FALLING APART ALONG WALL. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/20/2024REISSUE 35672780J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT CELLAR LEVEL WATER PENETRATION OF THE FOUNDATION WALL AT ELECTRIC METER ROOM AND ROOM WITH WATER MAINS. ROOM B2 AND B3. REMEDY: REPAINothing owed — awaiting certificate of correction
ECB02/23/2024CEASE USE KEWANEE BLR MODEL 7L287 CAUSED BY REPORTED OIL LEAK AT PREFERRED OIL FIRED BURNER. CSD-1 REQUIRED TO LIFT CEASE US ORDER. DO NOT OPERATE BOILER UNTIL ALL HAZARDOUS CONDITIONS ARE IMMEDIATELY CORRECTEDNothing owed — awaiting certificate of correction
ECB02/23/2024CEASE USE KEWANEE BLR MODEL 7L287 DUE TO FIRE AT # 2 BOILER CAUSING DAMAGE TO CONTROL CABINET. CSD-1 REQUIRED TO LIFT CEASE USE ORDER. DO NOT OPERATE BOILER UNTIL ALL HAZARDOUS CONDITIONS ARE IMMEDIATELY CORRECNothing owed — awaiting certificate of correction
ECB04/28/2023REISSUED#35495187Y FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTE:AT CELLAR LEVEL WATER PENETRATION THE FOUNDATION WALLS AT ELECTRIC METER ROOM AND NEXT TO ELECTRIC METER ROOM,SUCH AS ROOM#B2 & B3.RENothing owed — awaiting certificate of correction
ECB04/27/2023OCCUPANCY CONTRARY TO THE EXPIRED TCO FROM 1972 WITH THE ILLEGAL ARRANGEMENT & USE OF 2ND FLOOR CLASSROOM INTO DAY NURSERY., DISCONTINUE ILLEGAL OCCUPANCY OR AMEND C OF ONothing owed — awaiting certificate of correction
ECB03/23/2023REISSUE #34908042N FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES EXTERIOR BRICK WALL MISSING MORTAR BTWN BRICK LOCATED BTWN SCHOOL & SCHOOL YARD REM.REMEDY:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB03/23/2023OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS.OCCUPANCY CONTRARY TO EXPIRE TCO FROM 1972 WITH ILLEGAL ARRANGEMENT & USE OF 2ND FL CLASSROOM INTO DAY NURSERY.REMEDY:COMPNothing owed — awaiting certificate of correction
ECB03/23/2023REISSUE #352527275: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER WATER LEAK DAMAGE 1ST FL RM B26 MAIN ELECTRICAL RM EXIT 7,8,9 & 15.REMEDY:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB04/07/2022REISSUE#35557668X 3/19/2021.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT EXITS 5 AND 6 ON 1ST FLOOR FROM EXTERIOR TO VESTIBULE WALLS DAMAGED DUE TO WATER PENETRATION FROM ELEMENTS.REMEDY:REPAIR ANDNothing owed — awaiting certificate of correction
ECB04/07/2022REISSUE#35557669H 3/19/2021.FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.AT EXP3 EXTERIOR WALLS BY EXITS 5 AND 6 WATER PENETRATION INTO THE BUILDING.REMEDY:MAINTAIN EXTERIOR BUILDING WALL/WATERPROOFING.Nothing owed — awaiting certificate of correction
ECB03/19/2021REISSUED35495182P FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED OBSERVED@3FLRM308&2FLRM218 BROKEN GLASS IN WINDOWS.ALSO RM208 DOOR MISSING GLASS.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB03/19/2021REISSUED35495176Z FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES NOTED OBSERVED:EXTERIOR WALLS BY EXITS5&6 HAVE BECOME POROUS ALLOWING WATER TO ENTER BLDG.MAINTAIN BLDG EXTERIOR WALLS.Nothing owed — awaiting certificate of correction
ECB03/19/2021REISSUED35495183R FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED OBSERVED:@1FL,EXITS5&6 VESTIBULE WALL DAMAGED DUE TO WATER PENETRATION.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/05/2020REISSUE#35454705Y FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE: AT 1ST FL WATER PENETRATION AT EXIT 5-6 & ELECTRICAL ROOM THRU THE WALLS. REMEDY: REPAIR WALLS.Nothing owed — awaiting certificate of correction
ECB05/05/2020FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCE. NOTE: AT CELLAR LEVEL WATER PENETRATON THRU WALLS IN ROOMS B2 & BC. REMEDY: MAINTAIN BLDG EXTERIOR WALLS.Nothing owed — awaiting certificate of correction
ECB05/05/2020FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE AT EXIT 9&10 CEILING IN DISREPAIR DUE TO WATER PENTRATION AT DOORS. ALSO AT EXIT 5&6WALLS IN DISREPAIR DUE TO WATER PENETRATION. REMEDY: REPAIR & OR REPLANothing owed — awaiting certificate of correction
ECB10/03/2019REISSUE#35316838M FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: WATER PENETRATION AT 1ST FL AT EXIT 5-6,7-8,9-10 ROOM B26,ROOM 103. REMEDY: MAKE NECCESSARY REPAIRS.Nothing owed — awaiting certificate of correction
ECB02/01/2018REISSUE #35252727J FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED: THERE ARE LEAKS AT SEVERAL LOCATIONS THROUGHOUT THIS FACILITY. AT EXITS 7-8, 9-10 ROOM B26 ROOM #103 @ WINDOWS,AND ROOMNothing owed — awaiting certificate of correction
ECB04/10/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTED: AT THE FIRST FLR ROOM B26 MAIN ELECTRICAL ROOMS EXIT 7-8 AND EXIT 9-10 WATER LEAK TO THE DOOR. RMDY: REPAIR AND/OR REPLC SOURCE OF LENothing owed — awaiting certificate of correction
ECB07/16/2013REISSUE 34958532H RETAINING WALL 6'HIGH ALONG SIDE/REAR OF BUILDING JOINTS MISSING/BRICKS SPALLING. RMDY: REPAIR WALL.Nothing owed — awaiting certificate of correction
ECB05/22/2012REISSUE:34908642N.BRICK WALL APPROX 6' TALL IS MISSING MORTAR BTWN BRICKS LOCATED IN BTWN THE SCHOOL & BASEBALL FIELD.REM:REPLACE MISSING MORTAR BTWN BRICKS.Nothing owed — awaiting certificate of correction
ECB04/20/2011EXTERIOR BRICK WALL IS MISSING MORTAR BTWN THE BRICK LOCATED BTWN THE SCHOOL & SCHOOL YARD REM: REPAIR BRICK WALLHearing held — result not yet published
ECB11/24/199716M12,74U05,73B07, PERFORM 3 YEAR TEST, PROPERLY LABEL CITY ID NUMBERNothing owed — awaiting certificate of correction
ECB11/24/199709H12,74U05,75B07, PERFORM 3 YEAR TEST ( 73 ) PROPERLY LABLE CITY ID NUMBERNothing owed — awaiting certificate of correction