DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB07/09/2026REISSUED ECB#35719710J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT ROOF/4TH FL MECHANICAL RM,ROOMS 440,432,430 AND HALLWAY/CEILING NEAR RM 430 WATER DAMAGE/STAINING WITH SPALLING OF PLASTER/PNothing owed — awaiting certificate of correction
ECB07/09/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT EVERY LEVELS/STAIRCASES MISSING/NONE OF MESH GLASS PANELS THROUGHOUT VARIOUS AREAS.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/09/2026REISSUE ECB#35719711L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:AT 4TH FL GYM 3RD FL LIBRARY RM 305 1ST FL AUDINothing owed — awaiting certificate of correction
ECB07/09/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIODRS PER BC 1006.1;27-542.NOTED:AT 3RD FL LIBRARY RM 305 1ST FL FITNESS RM 143 NOT INSTNothing owed — awaiting certificate of correction
ECB07/09/2026REISSUED ECB#35719712N FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT 4TH FL HALLWAY SMOKE DOOR NEAR RM 449,STAIR E,B,A 3RD FL HALLWAY SMOKE NEAR RM 351 2ND FL HALLWAY SMOKE DOOR NEAR RM 250,221Nothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE ECB #35719708K. EXIT DOOR NOT SELF CLOSING. NOTED: AT(ROOF) BULKHEAD/STAIR C IN DISREPAIR/NOT CLOSING WHEN TESTED. REMEDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB06/26/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-542. NOTED: AT(4TH FL) LIBRARY RM 409 NON INSTALLED/PROVIDE WINothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE ECB #35719706R. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT(ROOF) BULKHEAD/STAIR C(4TH FL) LIBRARY RM 409 WATER DAMAGE TO CEILINGS/WALL WITH SPALLING PLASTER/PAINT THROUGHOUT VARIOUSNothing owed — awaiting certificate of correction
ECB06/26/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT (3RD FL)STAIR D (1ST FL)STAIR D, EXIT 7, 2 DOORS IN DISREPAIR/RACKED WHEN TESTED. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/26/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT (1ST FL)STAGE/EXIT 8 EGRESS WALKWAY OBSTRUCTED WITH MULTIPLE VARIOUS ITEMS BOXES, CHAIRS, NETS ETC... REMEDY: COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE ECB #35719707Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT(1ST FL) AUDITORIUM EMERGENCY LIGHTS NONothing owed — awaiting certificate of correction
ECB06/26/2026REISSUE ECB #35719705P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT(ROOF) CHIMNEY WITH MULTIPLE STEP CRACKS THROUGHOUT VARIOUS AREAS. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/22/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.LACK OF EMERGENCY LIGHTS FOR EXITS,EXIT DISCHARGES AND PUBIC CORRIDORS PER BC 1006.1;27-345.EMERGENCY LIGHT#31 IS NOT WORKING.REM:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB08/06/2025FOUND EASTMOND PLW-165 STEAM DUEL FUEL BOILER INOPERATIVE AT TIME OF INSPECTION. FAIL TO MAINTAIN BOILER. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB07/14/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPIANT MANNER. NOTED: AT(ROOF) MECHANICAL RM(4TH FL) RM 440, 432, 430 AND HALLWAY NEAR RM 430 WITH WATER DAMAGE/STAINING SPALLING OF PLASTER/PAINT OF CEILING/WALLS/FLOOR TNothing owed — awaiting certificate of correction
ECB07/14/2025EXIT DOOR NOT SELF-CLOSING. NOTED: AT(4TH FL) STAIRS D, C, B AND E(3RDFL) STAIR F(2ND FL) STAIR E, HALLWAY SMOKE DOORS NEAR RMS 214, 233 AND250(1ST FL) STAIRS C,A AND EXIT G(BASEMENT) CAFETERIA, STAIRS F, E ANDNothing owed — awaiting certificate of correction
ECB07/14/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT(4TH FL) GYM, LOCKER LMS(1ST FL) AUDITORIUM EMERGENCY LIGHTS NNothing owed — awaiting certificate of correction
ECB06/05/2025REISSUE ECB #35682780Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT(ROOF) CHIMNEY AND EXP 3 FACADE/WALL WITH STEP CRACKSTHROUGHOUT VARIOUS AREAS. REMEDY: COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB06/05/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED: AT(1ST FL) CAFETERIA AND AUDITORIUM EMERGENCY LIGHTS NOT WORKINGNothing owed — awaiting certificate of correction
ECB06/05/2025EXIT DOOR NOT SELF-CLOSING NOTED:(BULKHEAD) STAIRCASE C DOOR IN DISREPAIR/NOT CLOSING WHEN TESTED. REMEDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB05/09/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NOTED: AT(BULKHEAD) STAIR C AND(4TH FL) LIBRARY WITH DAMAGE/STAINING AND SPALLING OF WALLS/CEILING. REMEDY: COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB06/05/2024REISSUE #35672375X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF MY INSPECTION I OBSERVED CEILING THROUGHOUT IN DISREPAIR SECTIONS WITH BROKEN AND MISSING PANELS AND TRACK SHEET ROCK DETACHNothing owed — awaiting certificate of correction
ECB06/05/2024REISSUE #3567238L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF MY INSPECTION I OBSERVED THE EXTERIOR FOUNDATION MASONRY WALL MULTIPLE EXPOSURES HAVE MISSING SPALLING IN AREA WITH VERTICALNothing owed — awaiting certificate of correction
ECB06/04/2024REISSUE #35674661X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF MY INSPECTION I OBSERVED AT EXPOSURE #3 FACADE AND CHIMNEY HAS CRACK/SPLALLING BRICKS AND DELAMINATION THROUGHOUT NEED TO MANothing owed — awaiting certificate of correction
ECB06/04/2024REISSUE #35674663J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF MY INSPECTION I OBSERVED AT THE 4TH FLOOR AT STAIR B ROOM 424 BY ROOM 454 ON THE 3RD FLOOR GYM DOOR ON 2ND FLOOR AT ROOM 223Nothing owed — awaiting certificate of correction
ECB01/02/2024OBSERVED EASTMAN PLW-125 BOILER DUAL FUEL BURNER=CEASE USE BOILER CORRECT ALL HAZARDOUS CONDITIONS IMMEDIATELY AND RECORD A CSD-1 TEST, COMBUSTION ANALYSIS REPORT AND A FLUE SMOKE TEST REPORT CALL DOB 212602058Nothing owed — awaiting certificate of correction
ECB01/02/2024OBSERVED EASTMAN PLW-125 BOILER DUAL FUEL BURNER MALFUNCTION=CEASE USE BOILER CORRECT ALL HAZARDOUS CONDITIONS IMMEDIATELY AND RECORD A CSD-1 TEST, COMBUSTION EFFICIENCY ANALYSIS REPORT AND A FLUE SMOKE TEST RENothing owed — awaiting certificate of correction
ECB04/07/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:OBSERVED AT EXP #3 FACADE & CHIMNEY HAS STAIRCRACKS,SPALLING BRICKS & DELAMINATION THROUGHOUT.REMEDY:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/27/2022ALL BOILERS NEED INSULATION ON BOILER SHELL. CORRECT VIOLATING CONDITION & SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB07/08/2022BOILER MANHOLE LEAKING/VAC SYSTEM PUMP IS DEFECTIVE/HWH FLUE INSULATION LOOSE AND OPEN ON TOP;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONHearing held — result not yet published$625 proposed
ECB07/08/2022BOILER WATER FEED PUMP IS LEAKING/WATER FEED TANK WATER FEEDER HAS LEAKING PIPES/OIL TANK SIGN NOT DISPLAYED;CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONHearing held — result not yet published$500 proposed
ECB05/11/2022VACUUM PUMP AND WATER TANK FEED PUMPS ARE LEAKING. MODULATING HONEYWELL FEED VALVE IS CORRODED. CORRECT VIOLATING CONDITION AND SUMBIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
Public elementary, junior or senior high · Owner of record: NYC DEPARTMENT OF EDUCATION · 146,256 sf lot · 2.51 FAR built · Flood zone X