ECB10/24/2018B254,15,16,32A,50A,50B,50C,50D weil mclain bl r mdl CG6175,000 btu input; 15,16,32A,50A, combustible storage; 50B-relief discharge not piped to safe location; 50C- missing clean out at chimney base; 50D-supporNothing owed — awaiting certificate of correction
ECB07/24/2018Cease use. 4A,6A,15,16,32A,37,38,50A-c,51. Found 1-weil mclain cg-6 boiler. (51)hazardous condition,relief valve corroded & not functional.(50A)spill switch missing & wires jumped out.(50B)basement cluttered w/Nothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB11/14/2025Violation issued-failure to file 2024 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered
DOB06/30/2023Violation issued-failure to file 2020 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered
DOB06/30/2023Violation issued-failure to file 2021 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered
DOB06/20/2023Violation issued-failure to file 2019 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered
Old · issued 3+ years ago and still listed by DOB; nothing on the city's records either way
DOB04/05/2019.due to fireIssued 2019; DOB's record still lists it as active