ECB04/20/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: MISSING WIRE MESH GLASS PANEL IN STAIRWELL E EXIT 10 3RD FLOOR TO 2ND FLOOR AND CRACKED GLASS UPPER VISION PANEL IN SMALL CAFETERIA AREA SPACE OBSERNothing owed — awaiting certificate of correction
ECB04/20/2026REISSUE ON ECB #35720684N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE RATED CLASSROOM AND SMOKE DOORS NOT SELF-CLOSING PROPERLY DUE TO BINDING, MISSING AND/OR FAULTY HARDWARE ON CLASSROONothing owed — awaiting certificate of correction
ECB04/20/2026REISSUE ON ECB#35720685P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY EXIT DISCHARGES AND EXIT SIGNS NOTNothing owed — awaiting certificate of correction
ECB04/20/2026REISSUE ON ECB#35720686R EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR EMERGENCY EXIT DOORS NOT SELF-CLOSING PROPERLY DUE TO BINDING,MISSING ANDOR FAULTY HARDWARE ON 1ST FLOOR EXIT 5,1ST FLOOR EXIT 7 AND 1ST FLOORNothing owed — awaiting certificate of correction
ECB04/20/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROBIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: INSTALLATION ON PERMANENT DOOR KICK STOPS ON FIRE RATED CLASSROOMS 412, 400 AND 1Nothing owed — awaiting certificate of correction
ECB04/20/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE RATED SMOKE DOORS AND CLASSROOM DOOR NOT SELF-CLOSING DUE TO BINDING, MISSING AND/OR FAULTY HARDWARE ON SMOKE DOOR. AT EAST ENTRANCE AND SMOKENothing owed — awaiting certificate of correction
ECB07/11/2025EXIT DOOR NOT SELF-CLOSING PROPERLY AT THE TIME OF INSPECTION. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 1ST FLOOR EXIT-7, 8, 10, EXIT-11, AT 3RD FLOOR GYM 1 EXIT DOOR, 1ST FL STAIR "A" 1 EXIT DOOR, 1ST FNothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE 335692278M DATE OF ISSUE: 10-01-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 4TH FL. ROOM, 400B, 405, 408, 410, 419, 422, 425, AND THIRD FNothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35693377K DATE OF ISSUE: 10-01-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGESAND PUBLIC CORRIDORS PER BC 1006.1; 27-381 AT 1ST FL. CAFETERIA 2 EMERNothing owed — awaiting certificate of correction
ECB10/01/2024REISSUE #35676302N. OBSERVED AT 1 FLOOR SMOKE EXIT 7, 8, 10 AND EXIT 11 DOORS ARE NOT CLOSING CORRECTLY. REMEDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB10/01/2024REISSUE #35676301L. OBSERVED AT 4 FLOOR BY ROOM 402, 400, 3FL. GYM, 1FL. AUDITORIUM AND STAGE RIGHT EMERGENCY LIGHTS ARE NOT LIGHTING. REMEDY: REPAIR/REPLACE LIGHTING.Nothing owed — awaiting certificate of correction
ECB10/01/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AT 4 FLOOR 400B, 405, 408, 410, 419, 422, 425, 427 3FL. 305, 307, FL. 203, 225, 288, 1FL. 123 AND 127 DOORS ARE NOT CLOSING CORRECTLY. REMEDY: REPNothing owed — awaiting certificate of correction
ECB06/30/2023EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION. AT THE TIME OF INSPECTION OBSERVED THAT AT 3RD FLOOR GYM ONE EXIT DOOR, AT 1ST FLOOR STAIR "A" ONE EXIT DOOR, 1ST FLOOR EXIT-8 (INSIDE) ONE EXIT DONothing owed — awaiting certificate of correction
ECB06/30/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381. AT THE TIME OF INSPECTION OBSERVED THAT AT 3RD FL GYM 4 EMERGENCY EXIT LINothing owed — awaiting certificate of correction
ECB06/30/2023REISSUE #35665112Z DATE OF ISSUE:07.20.2022 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT VARIOUS LOCATIONS THROUGH ENTIRE BUILDING OBSERVED SEVERAL CLASNothing owed — awaiting certificate of correction
ECB07/20/2022RE-ISSUE #35591726Y-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT VARIOUS LOCATIONS THROUGHOUT ENTIRE BUILDING OBSERVED SEVERAL CLASSROOM DOORS WITH DEFECTIVE/MISSING DOOR CLOSERS #427 #425 #40Nothing owed — awaiting certificate of correction
ECB08/23/2021RE-ISSUED #35498570K FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNERNOTED:AT 4TH FL DOOR #427,425,419,417,415,413;AT 3RD FL ENTIRE DOORS AT 2ND FL ENTIRE DOORS;AT 1ST FL ROOM #125,121,122,123 & 125 MISSING/BNothing owed — awaiting certificate of correction
ECB06/16/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED OBSERVED CLASSROOM DOORS ST 4TH FLOOR ROOM 427,425,419,417,415,413,311,405,403,401,402,3RD FLOOR ROOM 301,302,303,307,313,315,317,319,319,322,326,325,Nothing owed — awaiting certificate of correction