ECB02/06/2026OBSERVED THROUGHOUT THE BUILDING NO TRAP WRAP INSULATION FOR TRAPS IN BATHROOMS. FOURTH FLOOR TWO SHOWERS NOT OPERATIONAL. BASEMENT SPRINKLER HEADS OBSTRUCTED. GAS DRYER LACKS A DEDICATED APPLIANCE SHUTOFF VALUNothing owed — awaiting certificate of correction
ECB05/08/2025FAILURE TO MAINTAIN, AT TIME OF INSPECTION, I OBSERVED FIRE PUMP IN FUEL TANK ROOM, PROHIBITED BY NYC BC 913.2.1 SECTION 3., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/02/2024I OBSERVED ON THE ROOF TOP LEVEL, A BX CABLE EXTENDED FROM THE WALL ABOVE THE EXIT DOOR NOT TERMINATED AS REQUIRED. ALL WIRING SHALL BE TERMINATED IN AN ACCEPTABLE JUNCTION BOX., COMPLY WITH ECNothing owed — awaiting certificate of correction
ECB01/02/2024OBSERVED IN THE BASEMENT/CELLAR INADEQUATE VENTILATION IN THE GAS METER ROOM., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB12/07/2023I OBSERVED ON THE ROOFTOP THE RACEWAY AND JUNCTION BOXES SUPPLYING POWER TO VARIOUS EXHAUST FANS UNSUPPORTED AND LAYING ALONG THE ROOF AREA., SECURE/SUPPORT PER ECNothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT ROOF LEVEL, WATERPROOFING MEMBRANE SHOWS DETACHMENT/HOLES AND OTHER FAILURES THAT ALLOW WATER PENETRATION INTO THE BUILDING., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB12/06/2022GAS METER ROOM NOT PROPERLY VENTED, AS PER APPENDIX E OF THE 2014 FGC AN OPENING TO THE OUTSIDE AIR IN THE WALL OF SUCH ROOM OR SPACE, PROVIDED THE FREE AREA OF THE OPENING IS NOT LESS THAN 30 SQUARE INCHES., RNothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT EXPOSURE # 2 & 3 FACADE, SEVERAL CRACKS IN DIFFERENT LOCATIONS. PREVIOUS VIOLATION # 39063664Y, MAINTAIN EXTERIOR BUILDING WALLNothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT ROOF LEVEL,BUCKHEAD, CEILING DAMAGES DUE WATER PENETRATION, ALSO, LOSS OF CORNERS OF THE EXTERIOR METAL COVERING (EXTERIOR SIDE) PREVIOUS VIOLATION # 39063665X., MAINTAIN EXTERIOR BUILDING WALLNothing owed — awaiting certificate of correction
ECB07/08/2022NO VENTILATION IN THE GAS METER ROOM. AS PER FGC GAS METER ROOMS SHALL BE PROPERLY VENTILATED., REPAIR AND/OR REPLACEHearing held — result not yet published$2K proposed
ECB06/08/2022CRACKS IN FACADE ON EXP1(HAS SHED), EXP2, EXP3 REAR., MAINTAIN EXTERIOR BUILDING WALLNothing owed — awaiting certificate of correction
ECB06/08/2022BULKHEAD AT ROOF LEVEL, PLASTER FALLING WATER IS COMING IN FROM ROOF. TEMPORARY BLUE NYLON TARP PLACE OVER FULL ROOF BEING HELD DOWN BY SAND BAGS THAT ARE ALL BROKEN NOW, TARP HAS BEEN RIPPED APART AND IS MOSTLNothing owed — awaiting certificate of correction
ECB05/31/2022UNSAFE UNSUITABLE ELECTRICAL WIRING,EQUIPMENT IN USE.I OBSERVED AT THEROOF LEVEL OVER THE EXIT DOORS,ARMORED CABLE THATS POKING OUT AND SUBJECT TO ALL WEATHER ELEMENTS.ARMORED CABLE IS NOT INTENDED TO BE EXPOSENothing owed — awaiting certificate of correction
ECB01/12/2022FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION NOTED: CELLAR GAS METER ROOM DOES NOT HAVE NATURAL AND/OR MECHANICAL VENTILATION. REMEDY: COMPLY WITH CODENothing owed — awaiting certificate of correction
ECB10/15/2021CRACKS IN FACADE ON EXP1(HAS SHED), EXP2, EXP3 REAR., MAINTAIN EXTERIOR BUILDING WALLNothing owed — awaiting certificate of correction
ECB10/15/2021BULKHEAD AT ROOF LEVEL, PLASTER FALLING WATER IS COMING IN FROM ROOF. TEMPORARY BLUE NYLON TARP PLACE OVER FULL ROOF BEING HELD DOWN BY SAND BAGS THAT ARE ALL BROKEN NOW, TARP HAS BEEN RIPPED APART AND IS MOSTLNothing owed — awaiting certificate of correction
ECB06/30/2021FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO NATURAL OR MECHANICAL VENTILATION IN GAS METER ROOM AT CELLAR. REMEDY: MAINTAIN BUILDING AS PER CODENothing owed — awaiting certificate of correction
ECB04/01/2021FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER - NO NATURAL ON MECHANICAL EXHAUST IN PLACE AT CELLAR GAS METER ROOMNothing owed — awaiting certificate of correction
ECB02/19/2021FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTE FAILURE TO PROVIDE FRESH AIR TO GAS METER RM@CELLAR LEVEL.PROVIDE FRESH AIR VENTILATION.Nothing owed — awaiting certificate of correction
ECB12/15/2020FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.FAILURE TO PROVIDE FRESH AIR TO GAS METER ROOM AT CELLAR LEVEL.PROVIDE FRESH AIR VENTILATION.Nothing owed — awaiting certificate of correction
ECB09/25/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTE AT CELLAR LEVEL IN GAS METER ROOM NO NATURAL FRESH AIR VENTILATION PROVIDED. REMEDY: REPAIR AND OR REPLACE PROVIDE FRESH AIR VENTILATIONNothing owed — awaiting certificate of correction
ECB02/21/2020FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED:AT TIME OF INSPECTION I OBSERVED AT CELLAR LEVEL AT GAS METER ROOM NO NATURAL OR MECHANICAL VENTILATION NEED TO PROVIDE PROPER VENTILATION IN GAS METNothing owed — awaiting certificate of correction
ECB01/09/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER - NOTED AT CELLAR GAS METER ROOM NO NATURAL OR MECHANICAL VENTILATION. REMEDY: REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB11/23/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT CELLAR GAS METER ROOTS NOT NATURAL OR MECHANICAL VENTALATION.REM:COMPLY WITH CODE.Nothing owed — awaiting certificate of correction
ECB10/09/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE AT CELLAR LEVEL AT GAS METER ROOM NO VENTILATION FOR FRESH AIR AS PER CODE.REMEDYREPAIR AND/OR REPLACE(SUPPLY FRESH AIR VENTILATION).Nothing owed — awaiting certificate of correction
ECB10/04/2019I OBSERVED ON THE ROOFTOP UNSUPPORTED METAL RACEWAYS BOTH RIGID TYPE( INTERMEDIATE CONDUIT) AND FLEXIBLE TYPE(SEALTITE), COMPLY WITH ECNothing owed — awaiting certificate of correction
ECB10/04/2019NO VENTILATION IN THE GAS METER ROOM. , REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB09/20/2019NOTED: OBSERVED AT EXPOSURE #1, HORIZONTAL CRACKS ALONG THE LENGTH OF THE RAMP, VERTICAL CRACKS AT EXPOSURE #2 FROM GRADE LEVEL UP TO THE SECOND STORY, VERTICAL CRACKS AT REAR EXPOSURE #3 NEXT TO ROOF'S DRAINNothing owed — awaiting certificate of correction
ECB07/31/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED: AT CELLARGAS MOTOR ROOM HAS NO NATURAL OR MECHANICAL VENTILATION AS PER GAS FULL CODE APPENDIX E4.Nothing owed — awaiting certificate of correction
ECB06/08/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE: AT BASEMENT LEVEL GAS METER ROOM NO FRESH AIR VENTILATION. OBSERVED. REMEDY: REPAIR AND REPLACE.Nothing owed — awaiting certificate of correction
ECB05/18/2019FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT TIME OF INSPECTION NOTED AT CELLAR GAS METER ROOM NO VENTIATION PROVIDED. RMDY: REPAIR/REPLACE.Nothing owed — awaiting certificate of correction
ECB04/15/2019FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED SPALLLING PLASTER AT STAIR "A" BULKHEAD SOME PLASTER HAVE FALLEN ONTO THE LANDING, SPALLING PLASTER WITHIN SHOWER ROOMS ACROSS FROM UNIT 4-Nothing owed — awaiting certificate of correction
ECB04/15/2019FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED: OBSERVED THROUGHOUT EXPOSURE #1 T VARIOUS LOCATIONS-CRACKS THROUGH BRICKS, BROKEN STONE NEAR ENTRANCE, CRACKS ALONG THE SIDE OF RAMP, CRACKED AND SPNothing owed — awaiting certificate of correction
ECB04/05/2019FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 4/5/19 AT ABOVE ADDRESS NO VENTILATION IN GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. REMEDY: REPAIR AND OR REPLACENothing owed — awaiting certificate of correction
ECB03/23/2019FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANER AT TIME OF INSPECTIONNOTED AT CELLAR GAS METER ROOM HAS NO VENTALATION FOR FRESH AIR.REM:COMPLY WITH CODENothing owed — awaiting certificate of correction
ECB01/14/2019FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION,I OBSERVED AT CELLAR LEVEL AT GAS METER ROOM HAS NO FRESH AIR VENTILATION NEED TO COMPLY W/SUMMONS & PROVIDE FRESH AIR VENTS.Nothing owed — awaiting certificate of correction
ECB12/03/2018FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED: CELLAR LEVEL,GAS METER ROOM HAS NO FRESH AIR VENT. REMEDY: COMPLY WITH SUMMONS PROVIDE FRESH AIR VENTS.Nothing owed — awaiting certificate of correction
ECB09/27/2018FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:AT EXP#3 THERE ARE SEVERAL VERTICAL CRACKS AT BUILDING WALL. CRACKS ARE FROM CELLAR UP TO 2ND STORY IN VARIOUS LOCATIONS. RMDY: MAINTAIN EXTERIORNothing owed — awaiting certificate of correction
ECB09/27/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 9/27/18 AT ABOVE ADDRESS NO FRESH AIR VENT IN GAS METER ROOM LOCATED IN THE BASEMENT. REMEDY: REPAIR AND OR REPLACENothing owed — awaiting certificate of correction
ECB03/08/2018FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.OBSERVED IN CELLAR NO VENTILATION IN THE GAS METER ROOM AS IS REQUIRED SEE:FGV (APPROX) (&) SECTION 4.REM:REPAIR &/OR REPLACE.PHOTOS TAKEN.Nothing owed — awaiting certificate of correction
ECB09/22/2016FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES.DEFECT NOTED:PREMISES EXTERIOR BRICK WALL AT EXP3 (REAR) HAS APPROX 2"WIDE VERTICAL/STEP CRACKS AT VARIOUS LOCATION FROM CELLAR (GROUND) LEVEL TO 2ND FLOOR LVLNothing owed — awaiting certificate of correction
Home for indigent children, aged, homeless · 11,900 sf lot · 4.24 FAR built · Flood zone X