DOB08/01/2024FAILURE TO CORRECT SWARMP CONDITIONS
DOB02/22/2024FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
ECB02/22/2024FAILURE TO TAKE AND PROVIDE ADEQUATE SAFETY MEASURES SUCH AS SIDEWALK SHED FENCE ECT.FISP 3 FILING UNSAFE ON 02/13/2024 BY QE/RA.NOTE:AS DATE OF INSPECTION THERE ARE NO SAFETY MEASURE IN PLACE.REM:TAKE AND PROV$25K due
HPD03/10/2004§ 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF RODENTS EVIDENCE OF RATS THROUGH OUT AT PUBLIC HALL, 1st STORY
ECB03/13/2026FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES.-NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 WEST (1)CRACKED STUCCO UNDERSIDE ABOVE RECESSED ENTRANCE (2)CRACKED/SPALLING TERRACOTTA/MASONRY AT BANDNothing owed — awaiting certificate of correction
ECB12/23/2025NOTED CONCRETE ENTRY RAMP AT ENTRANCE IN DISREPAIR AND GLASS AT ENTRY DOOR NORTH COURTYARD OFF 25TH STREET REPAIRED WITH PLYWOOD., REPAIR AND/REPLACE; REPAIR.Nothing owed — awaiting certificate of correction
ECB09/17/2025FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED AT EXP #1 WEST, #2 NORTH, #3 EAST, #4 SOUTH-CRACKED, INADEQUATE REPAIRS, SPALLING TERRACOTTA MULTI LOC.-EXP #2Nothing owed — awaiting certificate of correction
ECB03/06/2025AT TIME OF INSPECTION I OBSERVED SIDEWALK SHED IN PLACE AT EXPOSURE # 1 UPON REVIEW THE DEPARTMENT RECORD TO VERIFY COMPLIANCE IT SHOWS THAT THE SIDEWALK SHED PERMIT HAD EXPIRED SINCE 01-15-2025Nothing owed — awaiting certificate of correction
ECB03/06/2025AT TIME OF INSPECTON I OBSERVED SIDEWALK SHED INSTALLED ON EXPOSURE # 1 WITHOUT SIGNS OR PROJECT INFORMATION PANEL ON THE SHED PARAPET, TO DISPLAY THE NAME AND THE CONTACT INFORMATION OF THE OWNER OR THE GENERNothing owed — awaiting certificate of correction
ECB02/04/2025FAILURE TO TAKE/PROVIDE REQUIRED ACTION TO SECURE PUBLIC SAFETY AT THECONCRETE CRACKED EXPOSURE 1 NORTH ELE, EAST ELE, CRACKED/BROKEN WINDOWEXPOSURE 1 NORTH ELE AS PER #TR6-902936-9C-I1 WITH NO ADEQUATE PROTECTNothing owed — awaiting certificate of correction
ECB12/30/2024FAILURE TO TAKE/PROVIDE REQUIRED ACTION TO SECURE PUBLIC SAFETY AT A DESIGNATED UNSAFE BUILDING FACADE AS PER TECHNICAL REPORT #TR6-902934-9C-I1. REMEDY: TAKE SAFETY MEASURES AS PER 1RCNY 103-04.Nothing owed — awaiting certificate of correction
ECB12/28/2024FAILURE TO PROVIDE ADEQUATE SAFETY MEASURES SUCH AS SHED, NETTING,.. ECT WHERE REQUIRED TO PROTECT PUBLIC AND PROPERTY FROM DOCUMENTED UNSAFE FACADE AS PER 1RCNY 103-04. REPORTED FILED AS UNSAFE BY QEWI(PE/RA)Nothing owed — awaiting certificate of correction
ECB06/11/2024FAILURE TO MAINTAIN. AT TIME OF INSPECTION, EXPRESS ELEVATORS Q4 AND Q5 ARE OUT OF SERVICE CREATING DELAYS FOR RAPID RESPONSE TEAMS PROVIDING CRITICAL CARE BETWEEN, AND ADA USAGE, FLOORS 18-21. ELEVATOR MANAGEMNothing owed — awaiting certificate of correction
ECB06/03/2024FAILURE TO MAINTAIN BUILDING WALLS & APPURTENANCES.AT TIME OF INSPECTION OBSERVED DEFECTED MORTAR JOINTS DAMAGED MASONRY,RUSTED METAL DECOR WINDOW SILL AT EXP #1 WEST ELEVATION.& DEFECTED MORTAR JOINTS AT EXP2Nothing owed — awaiting certificate of correction
ECB01/16/2024FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 7C AND 8C REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN INITIAL FACADES REPORT REQUIRED BY 28-302.5 FOR CONTROL #802937. REMEDY: FILE ACCEPTABLE REPORT.Nothing owed — awaiting certificate of correction
ECB05/16/2023FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. OBSERVED BROKEN GLASS WINDOWS AND VERTICAL BRICK CRACKS ON EXPOSURE#1 WEST ELEVATION. OBSERVED VERTICAL BRICK CRACKS,SPALLED BRICKWORK,AND CRACKEDNothing owed — awaiting certificate of correction
ECB05/16/20233307.6.5 FAILURE TO MAINTAIN SIDEWALK SHED AS REQUIRED BY CODE. OBSERVED MISSING PARAPET PANEL AND DAMAGED MUDSILLS ON EXPOSURE #2 NORTH ELEVATION. REMEDY: MAINTAIN SIDEWALK SHED IN CODE COMPLIANT MANNERNothing owed — awaiting certificate of correction
ECB05/16/2023EXPIRED SIDEWALK SHED PERMIT. PERMIT # M00129247-I1-SH (EXPIRED 3/5/2023) REMEDY: RENEW PERMITNothing owed — awaiting certificate of correction
ECB06/01/2021TERMINATION VENT MISSING SCREENS AS PER MC-1305.7.3,FUEL OIL STORAGE EQUIPMENT NOT AS PER CODE MC-106.5; MC-MISC, COMPLY WITH NOTICE OF VIOLATION; CORRECT ALL VIOLATING CONDITIONS AND SUBMIT CERT.OF CORRECTIONNothing owed — awaiting certificate of correction
ECB12/30/2020O DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY : FILE APPLICATION, INSTALL DLM ANothing owed — awaiting certificate of correction
ECB03/07/2018FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #702934.REM:SUBMIT REQUIRED TECHNICAL REPORT.Nothing owed — awaiting certificate of correction
ECB03/07/2018FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #702928.REM:SUBMIT REQUIRED TECHNICAL REPORT.Nothing owed — awaiting certificate of correction
ECB03/07/2018FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #702937.REM:SUBMIT REQUIRED TECHNICAL REPORT.Nothing owed — awaiting certificate of correction
ECB12/07/2015FAILURE TO FILE AN ACCEPTABLE TECHNNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS:PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED BY ARTICLE 28.302 AND THE DOB RULES AND REGULATIONS.RMDY:Nothing owed — awaiting certificate of correction
ECB04/09/2008LOCAL LAW REPORT FILED AS "UNSAFE"; UNSAFE CONDITION EXISTED & NO MEASURES TAKEN TO SECURE SAFETY OF PUBLIC AS PER 27-129(D) & 1RCNY32-03(B)(5)(I). NO SIDEWALK SHED, FENCE, NETTING OR STREET CLOSURE WASNothing owed — awaiting certificate of correction
ECB04/09/2008SEC. 27-129(D)(1)(A). LOCAL LAW REPORT FILED AS "UNSAFE"; UNSAFE CONDITION EXISTED & NO MEASURES TAKEN TO SECURE SAFETY OF PUBLIC AS PER 27-129(D) & 1RCNY32-03(B)(5)(I). NO SIDEWALKK SHED, FENCE. NETTING ORNothing owed — awaiting certificate of correction
ECB01/18/200883## 83-# FINALIZE APPLICATION OR WITHDRAW APPLICATION & REMOVE DEVICNothing owed — awaiting certificate of correction
ECB01/18/200883## 83-# FINALIZE APPLICATION OR WITHDRAW APPLICATION & REMOVE DEVICENothing owed — awaiting certificate of correction
ECB06/29/1988WORKING WIHTOUT A PERMIT. WORK NOTED AT THE 13 STORY LOBBY EAST INSTALLED A SET OF NON FIRE RATED WOOD DOORS. IN CORRIDER. PARTITION WALL OF SHEET WORK. REMEDY: REMOVE NON FIRE RATED WOOD DOORS FORTH WITH.Nothing owed — awaiting certificate of correction
Hospital, sanitarium, mental institution · 753,175 sf lot · 2.82 FAR built · Flood zone X500