HPD09/16/2026§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
ECB08/05/2025CLASS 2 ITEMS: MISSING MAINTANANCE LOG, PROVIDE. CATEGORY 1 TEST TAG OUTDATED, CONDUCT THE TEST AND UPDATE THE TAG. MISSING LANDINGS BRAILLE TAGS, PROVIDE. IN-CAR LIGHT PANEL CRACKED, REPLACE. NO MOTOR ROOM LIG$625 due
ECB07/28/2025FAILURE TO MAINTAIN BUILDING EXTERIOR WALL OR APPURTENANCES.NOTE AT TIME OF INSPECTION OBSERVED AT EXP#1 MULTIPLE STEP CRACK AT PARAPET LEVEL SPALLING MORTAR JOINTS.EXP#1 OBSERVED MULTIPLE CRACKED WINDOWS.EXP#2$5K due
ECB07/17/2025FTM: ATOI, OBSERVED AT EXPO.#1 WINDOW A/C UNITS INSTALLED WITHIN FIRE ESCAPE FROM 2ND TO 6TH FLOOR LEVELS, RESTRICTING MEANS OF EGRESS IN THE EVENT OF AN EMERGENCY. AT EXPO.#3, VERTICAL CRACKS OBSERVED IN BUILD$1K due
ECB02/26/2025AT TIME OF INSPECTION OF A 6-STORY BUILDING OBSERVED NO SIGN OF CONSTRUCTION ACTIVITIES SIDEWALK SHED ERECTED EXP#1 AND 4.DURING MY INSPECTION I NOTICED SIDEWALK SHED DOES NOT MEET BC3307.6.4.9 AVOID INTERFEREN$2K due
DOB02/12/2025EWO OBSERVED EXP1 S.ELEV AND EXP4 E.ELVE STEP/VERTICAL CRACK @ PARAPET /TOP AND SEVERAL LOCAT. NO SAFETY MEASURES IN PLACE. REMEDY:IMMEDLY PROVIDE ADEQUATE SAFETY MEASURES (SIDEWAK SHED) @ EXP 1&4 SOUTH & EAST ELEVATION FULL LENGTH (EAST 190ST & CRESTON AVE) TO SECURE PUBLIC SAFE TY. IMMEDIATELY REPAIR DEFECTIVE FACADE UNDR NYS PE/RA SUPERVISION
HPD04/09/2024§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR AT COMPACTOR CLOSET, 6th STORY
DOB07/21/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/20/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/04/2020V-DOB VIOLATION - ACTIVE
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB07/29/2015FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB01/02/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB12/13/2011VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
ECB03/13/2025CLASS 1 ITEM: NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BUILDING CODE. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATNothing owed — awaiting certificate of correction
ECB02/12/2025FAILURE TO MAINTAIN BUILDING EXTERIOR WALL(S) OR APPURTENANCES. NOTE:-AT THE TIME OF INSPECTION, OBSERVED AT EXPO #1 AND 4 SOUTH(EAST 190 STREET) AND EAST(CRESTON AVENUE) ELEVATION STEP/VERTICAL CRACK AT PARAPENothing owed — awaiting certificate of correction
ECB02/04/2025CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL OR EMAILTHE D.O.B. EIR@BUILDINGS.NYC.GOV. ELEVATOR DIVISION AT (212) 3Nothing owed — awaiting certificate of correction
ECB12/10/2024RESPONDING, TO A 311 ELEVATOR COMPLAINT. UPON INSPECTION, RECURRING VIOLATIONS WAS ISSUED, FOR NO DLM INSTALLED IN CONTROLLER, FILE APPLICATION WITH NYCDOB, THEN INSTALL DLM THEN FILE TEST WITH NYCDOB, / LOWERNothing owed — awaiting certificate of correction
ECB05/03/2024RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF THE SINGLE DEVICE IN THE BUILDING A CLASS 1 RECURRING VIOLATION ISSUED FOR THE FOLLOWING, CAR DOOR RESTRICTOR ALTERED, / NO DLM INSTALLED IN CONTROLLERNothing owed — awaiting certificate of correction
ECB08/03/2023AGGRAVATED II CONDITION. RESPONDENT HAS A HISTORY OF FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDERS. RESPONDENT FAILED TO COMPLY WITH THE COMMISSIONER'S ORDERS TO FILE CERTIFICATES OF CORRECTION FOR 8 OPEN ECNothing owed — awaiting certificate of correction
ECB07/17/2023OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O. NOTED: AT CELLAR LEVEL OBSERVED 2 CLASS A APARTMENTS BOTH APARTMENTS INCLUDE 3 PC BATHROOMS AND KITCHENS AND ARE OCCUPIED CONTRARY TO THAT ALLOWED BY C OF O 2497- WNothing owed — awaiting certificate of correction
ECB07/17/2023WORK WITHOUT PERMIT. NOTE: AT CELLAR LEVEL JANITORS APARTMENT INSTALLED A WALL TO SPLIT THE APARTMENT INTO 2 APARTMENTS. CREATED A THREE PCS BATHROOM WITH COLD & HOT DRAIN, ALSO A SINK IN KITCHEN WITH COLD & HONothing owed — awaiting certificate of correction
ECB06/29/2023CLASS 1 ITEM: NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BUILDING CODE. THIS IS A FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION, INSTALNothing owed — awaiting certificate of correction
ECB04/13/2023NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN APPENDIX K OF THE 2014 BUILDING CODES; REMEDY INSTAL DLM FILE AND PERFORM TEST WITH NYC DOBNothing owed — awaiting certificate of correction
ECB12/03/2022CLASS 1 VIOLATION ISSUED, RESPOND TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF DEVICE AND NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCB, REMEDY;Nothing owed — awaiting certificate of correction
ECB09/14/2022NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN APPENDIX K OF THE 2014 BUILDING CODES, REMEDY INSTALL DLM FILE AND PERFORM TEST WITH NYC DOB; NO FIREMEN SERVICE INSTALLED AS REQUIRED IN APPENDIXNothing owed — awaiting certificate of correction
ECB06/13/202242M07,08N10:42-M-7 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY:FILEAPPLICATION,INSTALL DLM. 08-N-10=ELEVATOR NOT WORKING/GOING TO BASEMENNothing owed — awaiting certificate of correction
ECB05/13/2022CLASS 1 VIOLATION RECURRING, ISSUED , NO DLM, NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; FILE APPLICATION. INSTALL DLM AND PERFORM ANDNothing owed — awaiting certificate of correction
ECB04/22/2021NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL DLM AND PERFORM AND FILE TEST WITH NYCDOB. STAIRS TO MACHINE ROOM MISSING STEP, REPAIR.Nothing owed — awaiting certificate of correction
ECB10/20/2020NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL DLM AND PERFORM AND FILE TEST WITH NYCDOB.Nothing owed — awaiting certificate of correction
ECB04/30/201508V10,70O02,70Z09,42Q03,39O02,56F10,39X10,68M07,68M07,10M10. 08-REPAIRFLOOR STOPS; 70-REMOVE WATER AND CLEAN PIT; 39X10-WORKLIGHT; 68-LAST ELEV CO MAINTENANCE LOG MONTHLY ENTRY AUG 2013 FOUND NO OTHER RECORDSNothing owed — awaiting certificate of correction
ECB05/06/201329R11 - REPLACE DOOR OPERATOR W/O OBTAINING A WORK PERMIT FROM DOB.Nothing owed — awaiting certificate of correction
ECB10/03/201297X10. ONLY ELEVATOR IN BLDG IS OUT OF SERVICE. THEREBY CREATING CONDITIONS DANGEROUS TO HUMAN LIFE - AS PER 1RCNY11-02.Nothing owed — awaiting certificate of correction
ECB07/05/2011CELLAR APT SUBDIVIDED CREATING AN ADDITIONAL CLASS A APT W/ FULL BTRM AND KTCN THEREBY INCREASING THE BLDG OCCUPANCY GAS RANGE AND GAS CONNECTIONS PRESENT REM: DISCONTINUE THE ILLEGAL USE OF AMEND THE C/ONothing owed — awaiting certificate of correction