HPD09/04/2026§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE (NOT 6 INCHES FROM CEILING) LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''NORTH''
HPD09/04/2026§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE (NOT 6 INCHES FROM CEILING) LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''NORTH''
HPD08/05/2025§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE BRICK AND MORTAR AT NORTH EXTERIOR WALL (BUILDING FACADE) AT ALL STORIES
HPD06/08/2025§ 27-2005 ADM CODE MAKE SAFE BY PROPERLY REPAIRING THE STRUCTURAL DEFECT CRACKED BRICK AND MORTAR JOINTS AT NORTH EXTERIOR WALL, 6TH STORY,(NORTH WEST CORNER)
HPD05/28/2025HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
HPD05/28/2025HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
HPD03/13/2025§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE BRICK AND MORTAR AT NORTH EXTERIOR WALL (FRONT FACADE)
DOB12/23/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/26/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD10/22/2023HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
HPD10/22/2023HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTH
HPD02/15/2023§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROXIMATELY 20 SQ FEET AT EAST WALL IN THE BATHROOM LOCATED AT APT 1P, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
DOB12/22/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/06/2021V-DOB VIOLATION - ACTIVE
DOB01/06/2021V-DOB VIOLATION - ACTIVE
DOB01/04/2020V-DOB VIOLATION - ACTIVE
DOB01/04/2020V-DOB VIOLATION - ACTIVE
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
DOB06/01/2016FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB09/23/2015FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB05/30/2014VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
DOB08/15/2012VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2010 CAT 1 INSP/TST
DOB01/13/1997V-DOB VIOLATION - ACTIVE
ECB06/30/2026AT TIME OF INSPECTION, OCCUPIED 6-STORY BUILDING OBSERVED WITH SIDEWALK SHED AT EXPOSURES 1 AND 4. MUDSILLS OBSERVED BURIED IN GROUND. MULTIPLE SHED PANELS WERE LOOSE AND LEANING. FAILURE TO PROPERLY MAINTAIN SHearing held — result not yet published$2K proposed
ECB04/23/2026RESPONDING TO A 311 COMPLAINT.UPON INSPECTION OF THE MOTOR ROOM THERE IS NO DLM INSTALLED AS PER 3.10.12 APPENDIX K CEASE USE INSTALL AND CONTACT NYCDOB. FOR RE-INSECTIONHearing held — result not yet published$1K proposed
ECB04/23/2026RESPONDING TO A 311 COMPLAINT, UPON INSPECTION OF THE MOTOR FIND THAT THERE'S NO DML INSTALLED AS PR CODE DLM 3.10.12 OF APPENDIX CODE CLASS 2Hearing held — result not yet published$625 proposed
ECB08/05/2025RTS CLASS1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITIONNothing owed — awaiting certificate of correction
ECB08/05/2025CLASS 2 ITEMS: NO SERVICE TO ROOF, PROVIDE. MISSING HALL BUTTON AT ROOF LEVEL, INSTALL. HOIST MACHINE PRODUCE VERY LOUD SQUEEKING NOISE EVERY TIME WHEN ELEVATOR STOPS, INVESTIGATE AND REPAIR. IN-CAR ALARM BUTTONothing owed — awaiting certificate of correction
ECB07/18/2025FAILURE TO MAINTAIN. OBSERVED AT EXPOSURE#4, FACADE AT THE 6TH FLOOR HAS MULTIPLE CRACKS AND IS IN NEED OF REPAIR, MAINTAIN EXTERIOR BUILDING WALL; REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB07/18/2025WORK WITHOUT A PERMIT. OBSERVED ON FLOORS 1-6, NEWLY/RECENTLY INSTALLED ELECTRICAL PULL BOX AND EMT CONDUILT, OBTAIN ALL PERMITS; OBTAIN ALL PERMITSHearing held — result not yet published$1K proposed
ECB03/13/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 1 ITEM: NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BUILDING CODE. THIS IS A CONTROLLENothing owed — awaiting certificate of correction
ECB02/04/2025CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL OR EMAILTHE D.O.B. EIR@BUILDINGS.NYC.GOV. ELEVATOR DIVISION AT (212) 3Nothing owed — awaiting certificate of correction
ECB01/24/2025WORK WITHOUT A PERMIT. OBSERVED ON FLOORS 1-6, NEWLY/RECENTLY INSTALLED ELECTRICAL PULL BOX AND EMT CONDUIT, OBTAIN ALL PERMITS; OBTAIN PERMITNothing owed — awaiting certificate of correction
ECB01/24/2025FAILURE TO MAINTAIN. OBSERVED AT EXPOSURE#4, AT THE 6TH FLOOR FACADE. MULTIPLE CRACKS, IN NEED OF REPAIR., MAINTAIN EXTERIOR BUILDING WALL; REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB01/24/2025FAILURE TO MAINTAIN. OBSERVED ON FLOORS 1-6, NEWLY/RECENTLY INSTALLED EMT CONDUIT DOES NOT HAVE FIRE STOPPING., PROVIDE/MAINTAIN FIRE STOPPING; PROVIDE/MAINTAIN FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB10/22/2024RESPONDING, TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION, DEVICE. DEVICE IS FOUND OUT-OF-SERVICE, AS PER 1 RCNY 11-02.THIS DEVICE PROVIDE SERVICE IN 7 STORY BUILDING,REMEDY,RESTORE TO SERVICE IMMEDIATELY AND NONothing owed — awaiting certificate of correction
ECB03/15/2024DOOR ZONE RESTRICTOR BYPASSED. REPAIR EXCESSIVE GAPBETWEEN CAR AND HOISTWAY SILL. IN-CAR COMMUNICATION AND FANARE INOPERATIVE.REPLACE MISSING IST FLOOR DOOR RELEASE ROLLER. REPLACE ALL WORN DOOR RELEASE ROLLERSNothing owed — awaiting certificate of correction
ECB02/09/2024AT TIME OF INSPECTION OBSERVED EXTERIOR ROOF LEVEL BRICKS PARAPET WALL INSTATE OF DISREPAIR CONDITIONS WITH HORIZONTAL, VERTICAL AND STEP CRACKS ON ENTIRE LENGTH ON EXPO # 01 & 04. ALSO OBSERVED RUSTY WINDOW LINothing owed — awaiting certificate of correction
ECB01/11/2024RESPONDING ON A 311ELEVATOR COMPLAINT, UPON INSPECTION, CLASS 1 VIOLATION WAS FOUND FOR , NO DOOR LOCK MONITORING INSTALL IN CONTROLLER, REMEDY; FILE APPLICATION WITH NYCDOB INSTALL THE DEVICE THEN FILE TEST WINothing owed — awaiting certificate of correction
ECB09/14/20237-J-1C/U; 42-M-5R/C; 59-BB-5; 42-D-6; 99-BB-7. C/U(7)-CAR DOOR MECHICAL SFETY EDGE VERY DIFFICULT TO REACH. MUST ADJUST TO EASILY REACH IT. R/C(42) NO DLM INSTALLED ON THIS CONTROLLER AS MANDATED BY 3/10/2012 ONothing owed — awaiting certificate of correction
ECB09/12/2023FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE IN AN UNSAFE WORKING CONDITION AND A CEASE USE ORDER WAS ISNothing owed — awaiting certificate of correction
ECB08/10/2023AGGRAVATED II CONDITION. RESPONDENT HAS A HISTORY OF FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDERS. RESPONDENT FAILED TO COMPLY WITH THE COMMISSIONER'S ORDERS TO FILE CERTIFICATES OF CORRECTION FOR 20 OPEN ENothing owed — awaiting certificate of correction
ECB06/29/2023CLASS 1 ITEMS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITINothing owed — awaiting certificate of correction
ECB06/29/2023CLASS 1 ITEM: NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BUILDING CODE. THIS IS A FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION, INSTALNothing owed — awaiting certificate of correction
ECB09/14/2022NO FIREMENS SERVICE INSTALLED IN CONTROLLE AS MANDATED IN APPENDIX K . REMEDY: INSTALL FIREMENS SERVICENothing owed — awaiting certificate of correction
ECB04/28/202242M07,02X10 AND 14M11 NO DOOR LOCK MONITORING INSTALL IN CONTROLLER ASMANDATED BY 3.10.12 OF APPENDIX K3 OF 2014 NYC BUILDING CODE.REMEDY:FILE APPLICATION & INSTALL.REPAIR OUTSIDE COMMUNICATION IN CAR(TELEPHONENothing owed — awaiting certificate of correction
ECB09/07/2021CLASS 1 VIOLATION ISSUED ITEMS,/ NO DOOR LOCK MONITORING SYSTEM IN CONTROLLER AS MANDATED BY 3.10.12 APPENDIX K3 OF THE 2014 NYCBC, FILE APPLICATION, INSTALL DLM, CLASS 2 VIOLATION ISSUED ITEMS ARE, CAR DOOR SINothing owed — awaiting certificate of correction
ECB01/04/201767X10,05L01,06Q03,07L10,40P07,34O02.29L10. 05-ADJUST CAB DOOR FROM SLAMMING; 06-INSTALL MISSING COVERS FOR 1ST FLOOR, 4THE FLOOR, 6TH FLOOR DOOR LOCKS; 07-SAFETY EDGE MECHANICAL NOT ABLE TO REOPEN; 34-CLEAN ENTNothing owed — awaiting certificate of correction
ECB03/11/2016*07X10,56M07,64M07,41D06,29M07,02X10,70O02,71B07,03M07. *07X10-REPAIRSAFETY EDE; 56M07-PROVIDE HOIST ROPE GUARD; 64M07-PROVIDE MISSING HOIST MOTOR DEVICE#; 41D06-PROPERLY SECURE MOTOR ROOM DOOR; 29M07-PROVIDENothing owed — awaiting certificate of correction
ECB07/01/2015CU-05L10,CU-08V01,CU-42G11. 70O02,68M07,67M10. 05-CAR DOOR SLAMS ON CLOSING AT FLOOR STOPS DOOR NOT OPENING,CAUSING ENTRAPMENT; 08-FLOOR STOPS EXCESSIVELY OUT LEVEL; 42-FUSES WIRE JUMPED ON CONTROLLER; 68-PER 8Nothing owed — awaiting certificate of correction
ECB01/05/201567M10,68B07,41T07,08V10,21Q03,05M10,70O02,44H10,05L10,56O0256Y10,40O02,97E10. 21-PROVIDE COVERS FOR LOBBY,BASEMENT, 3RD, 4TH AND 6TH FLRS; 05M10-CAR DOOR RESTRICTOR; 05-PROVIDE SLOW DOWN WHEN CLOSING; 97E10-ELENothing owed — awaiting certificate of correction
ECB10/21/201470O02,21Q03,11X10,08V10,41T07,68M07,42G11,56F10,56O02. 21-INTERLOCK COVERS MISSING,BASEMENT, 2ST AND 4TH FLRS; 11-ELEVATOR NOT RESPONDING TO2ND FLOOR CAB BUTTON; 68-NO ELEV CO MAINTENANCE MONTHLY LOG FOUND INNothing owed — awaiting certificate of correction
ECB06/17/2014B251.41T07,21Q03,06L10,40O02,24K10,08B07,08V10,02X10,67M07,05E10,38O02,34O02,98U15,44H10,56O02,59O02,73O02,74O02.21:PROVIDE COVERS FOR LOBBY,3,4,6 FL INTERLOCK AND BASEMENT.06:PROVIDE SLOW CLOSING.24:CAR POSITINothing owed — awaiting certificate of correction
ECB06/16/2014B251.41T07,40O02,56O02,59O02,73O02,74O02,39O02,68B07,67M10,21Q03,05L10,24X10,70O02,08V10,42D06.68:FOUND NO ELEV MAINT LOG ENTRIES FOR ENTIRE YEAR 2014.67:EMERG PHONE IN ELEV OAB.21:COVER MISSING BASEMENT 1&4 FLNothing owed — awaiting certificate of correction
ECB04/01/2014B251.41T07,40O02,42G11,98BB15,68B07,56F10,56O02,70O02,21Q03,05L10,08Y10,97L10.42:FUSES WIRE JUMPED ON CONTROLLER.68:ELEV CO MAINTENANCE LOG SHOWS NO ENTRIES FOR JAN,FEB,MARCH 2014.56:REPAIR BACKLASH.21:BASEMENTNothing owed — awaiting certificate of correction
ECB08/05/201399BB05,98BB05,15I10,21Q03,70O02,40O02,41T07,08V10,42G11,68M07,16L10,21L10. 21-BASEMENT,LOBBY,2ND AND 4TH FLR INTERIOR COVERS MISSING;42-FUSEWIRES JUMPED ON CONTROLLER; 68-NO ELEV CO MAINTENANCE LOG FOUND IN MOTNothing owed — awaiting certificate of correction
ECB08/05/201321L10,16L10,99BB05,98L15,41T07,42G11. 16L10-2ND FLOOR HOISTWAY DOOR OPENS WITH NO ELEVATOR AT FLOOR PRESENT; 42G11-FUSE WIRE JUMPED ON CONTROLLER; PLEASE CALL 212/566-5594 BEFORE RETURNING ELEV. TO SERVICENothing owed — awaiting certificate of correction
ECB05/09/201372M10,40O02,99U05,68M07,42G11,98U05,56Y10,02X10,08V10,21Q03,70O02,32H 10,14M10. 02X- ALARM NOT WORKING FOR ALARM BUTTON. 21- BASEMENT LOBBY 2ND,3RD AND 4TH FLR, PROVIDE COVERS. 68- AS PER (ASME) A17.1 8.6.1.2.Nothing owed — awaiting certificate of correction
ECB05/08/201372M10,70O02,71X10,21Q03,24X10,29L10,16L10,21L10,99BB05,68M07,40O02,56O02,56Y10,15I10,100M07,42G11,08V10,98BB05. CU-72- PROVIDE PIT STOP SWITCH AS PER APPROX K-3. 21- COVERS FOR BSMT, LOBBY AND 4TH FLRS.Nothing owed — awaiting certificate of correction
ECB12/05/201270O02,72M10,21Q03,11X10,24X10,08V10,40O02,56O02,68M07,98U15,08E10. 72-REQUIRED AS PER APPNDX-K. 21Q- INTERLOCK COVERS MISSING BASEMENT, 1ST ,2ND,3RD AND 4TH FLR INTERLOCKS. 11- ALARM BUTTON NOT OPERATIONAL.Nothing owed — awaiting certificate of correction
ECB12/05/201270O02,72M10,98BB05,40O02,56Q02,68M07,21Q03,15I10,08V10. 68- NO MAINTENANCE LOG BY ELEVATOR CO. FOUND IN MOTOR ROOM. 21- BASEMENT,1ST,2ND AND4TH FLR INTERLOCK COVERS MISSING. 08- REPAIR ALL FLRS, FLR STOPS.Nothing owed — awaiting certificate of correction
ECB12/30/201199U15,100MO7,40M07,70O02,72M10,21L10: 100M07-CAPACITY PLATE IN ELEVATOR CAB; 40M07-ELEVATOR COMPANY MAINTENANCE LOG, 21L10-PULL ON 5TH FL HOISTWAY DOOR STOPS ELEVATOR IN FLIGHT.Nothing owed — awaiting certificate of correction
ECB07/07/201021Q03,29Q03,39X10,39Q03,60Q03,68M07,69M07,70O02,71X10,71Q03,77Q03,98BB05,99U15.(21Q03)INSTALL COVER FOR BSMNT ENTER LOCK.(39X10)REPAIR LIGHTTOP OF CAR.(39Q03)INSTALL COVER FOR LIGHT TOP OF CAR.(77Q03)INSTALL GNothing owed — awaiting certificate of correction
ECB06/02/201024X10,29Q03,21Q03,35Q03,39X10,39Q03,42D06,52M07,56Q03,60Q03,68M07,69M07,77Q03,98U15,99U15.24-X-10 REPAIR HAUP.I.,35-Q-03 INSTALL COVERS FOR ELECTRICAL BOX TOP OF CAR,39-X-10 REPAIR LIGHT TOP OF CAR,39-Q-03 INSTNothing owed — awaiting certificate of correction
ECB01/22/201008/V/10,21/Q/03,24/X/10,70/O/02,98/BB/05,99/U/05,23/X/10-08-V-10-REPAIR ALL FLR STOPS B-THROUGH 6TH FLRS/21-Q-03-LOBBY BSMT & 4TH FLR INTERLOCK COVERS MISSINGNothing owed — awaiting certificate of correction