DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB09/12/2025FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.-NOTE: AT TIME OF INSPECTION I OBSERVED OBJECTS ON FIRE ESCAPE LANDINGS AT EXP #2 NORTH, #3 EAST MULTI LOC.-EXP #2 NORTH-DEFECTIVE FIRE ESCAPE DROP LADDER IS DETA$1K due
ECB09/12/2025FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES.-NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 WEST, #2 NORTH, #3 EAST, #4 SOUTH-CRACKED/SPALLING BRICK AT PARAPET LEVEL MULTI LOC.-EXP #1 WEST, #2 NO$5K due
ECB07/31/2025FAILURE TO FILE REQUIRED ANNUAL BOILER INSPECTION REPORTS FOR LOW-PRESSURE BOILER 20000011097Y0001 IN ACCORDANCE WITH THE RULES OF THE DEPARTMENT. 1RCNY 103-01(D)(1) REQUIRES THAT AN ANNUAL INSPECTION REPORT FO$3K due
HPD02/23/2025§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOUSEHOLD ITEMS BLOCKING ACCESS TO FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD02/23/2025§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT NORTH, SOUTH, EAST WALLS AND INTERIOR DOOR FRAME IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' ORIGINAL VIOLATION 17716696 ISSUED 23-FEB-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
HPD02/23/2025HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
DOB09/23/2024VIOLATION ISSUED-FAILURE TO FILE 2023 EXTERNAL LOW PRESSURE INSPECTION
HPD07/08/2024HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD07/08/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 30SQ FT AT CEILING AND ALL WALLS IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD07/23/2023§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st CLOSET FROM SOUTH AT WEST WALL DOOR FRAME IN THE 3rd PRIVATE HALLWAY LOCATED AT APT 5G, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2800'', 1st FROM EAST AT SOUTH
HPD07/23/2023§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM EAST AT SOUTH WALL, 1st DOOR FRAME FROM EAST AT SOUTH WALL IN THE FOYER LOCATED AT APT 5G, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2800'', 1st FROM EAST AT SOUTH
HPD07/23/2023§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM EAST AT SOUTH WALL, 1st RISER FROM SOUTH AT WEST WALL IN THE BATHROOM LOCATED AT APT 5G, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''2800'', 1st FROM EAST AT SOUTH
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
DOB06/30/2023VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
DOB04/25/2023VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
DOB12/01/2022FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
HPD07/12/2021HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6E, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
DOB02/17/2021V-DOB VIOLATION - ACTIVE
DOB03/05/2020V-DOB VIOLATION - ACTIVE
HPD07/15/2019§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES LOWER PRESSURE AT WASH BASIN AND BATHTUB IN THE BATHROOM LOCATED AT APT 6E, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH
HPD05/24/2019§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... APPROX 15 SQUARE FEET AT ALL WALLS IN THE BATHROOM LOCATED AT APT 2A, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT NORTH ORIGINAL VIOLATION 13089723 ISSUED 24-MAY-19 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE ''27-2017.3a(5)(a) or (b).
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB04/04/2018FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
HPD07/18/2017§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION CONSISTING OF SHEETROCK PARTITION ERECTED AT CENTER CREATING 2 LIVING SPACES. IN THE 1st ROOM FROM EAST LOCATED AT APT 3N, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
HPD04/17/2017§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2M, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB11/16/2016FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB11/14/2016VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
HPD05/17/2015§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2M, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
DOB10/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2013 INSPECTION/TEST
DOB07/19/2014WORK WITHOUT A PERMIT; WORK NOTED IN CELLAR NEW GAS PIPING, VALVES, FITTINGS WERE INSTALLED & CONNECTED TO 3 GAS DRYERS WITH NO PERMIT FILLED WITH THE DEPT OF BUILDINGS REMEDY: OBTAIN A PERMIT
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
HPD04/01/2013§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2M, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
HPD04/08/2011§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6M, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT SOUTH
HPD12/01/2009§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION ERRECTED PARTITION WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 5J, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTH
HPD11/24/2009§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION PARTITION WALL ERRECTED FROM FLOOR TO CEILING WITH DOOR CREATING ADDITIONAL ROOM IN THE 1st ROOM FROM NORTH LOCATED AT APT 2E, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
HPD11/24/2009§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION PARTITION WALL ERRECTED FROM FLOOR TO CEILING WITH DOOR CREATING ROOM IN THE 3rd ROOM FROM NORTH AT WEST LOCATED AT APT 6L, 6th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTH
HPD10/02/2009§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION , CONSISTING OF WOOD STUD, SHEETROCK WALL WITH DOOR ERECTED FLOOR TO CEILING CREATING AN ADDITIONAL ROOM IN THE 2nd ROOM FROM NORTH AT WEST LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD08/14/2008§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE PRIVATE HALLWAY LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD07/14/2008§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION ,WOOD STUDS AND SHEETROCK PARTITION WALL ERECTED FROM FLOOR TO CEILING CREATING ROOM IN THE 2nd ROOM FROM NORTH LOCATED AT APT 5H, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH
DOB06/16/2008V-DOB VIOLATION - ACTIVE
DOB08/02/2007V-DOB VIOLATION - ACTIVE
HPD02/28/2007§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION SHEETROCK AND STUD ERECTED FROM FLOOR TO CEILING CREATING ADDITONAL ROOM IN THE 2nd ROOM FROM NORTH LOCATED AT APT 6H, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
DOB11/13/2006V-DOB VIOLATION - ACTIVE
DOB10/01/2005V-DOB VIOLATION - ACTIVE
HPD01/05/2005§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM WEST AT NORTH WALL IN THE ENTRANCE FROM NORTH LOCATED AT APT 5K, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH
DOB03/19/2003V-DOB VIOLATION - ACTIVE
DOB02/27/2001V-DOB VIOLATION - ACTIVE
HPD08/23/1999§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION PARTITION ERECTED AT CENTER ROOM SUBDIVIDING ROOM IN 2 2ND STY NORTHEAST APT 2B NORTH SECTION. , SECTION '' ''
ECB01/03/2018CU-05M07; 68B07,67X10,26D6,44H11,52I11,35Q03,39R09,41L10,39X10. 05M07-MISSING DOOR RESTRICTOR. THIS IS A SAFETY ITEM TO ENSURE PASSENGERS SAFETY; CU68B07-PROVIDE MAINTENANCE CONTROL PROGRAM; 26D6-PROPERLY SECNothing owed — awaiting certificate of correction
ECB08/19/201605M07,67L10,05J10,16J10,39002,70002,40P16. DOOR RESTRICTOR MISSING.PROVIDE,COMMUNICATION DEFECTIVE REPAIR. CAR DOOR MISALIGNED REPAIR,HOISTWWAY DOOR MISALIGNED,REPAIR.CAR TOP DIRTY CLEAN.PIT DIRTY CLEAN,MACHINENothing owed — awaiting certificate of correction
ECB05/18/201505M07;60Q03;67X10;77B07; 05-M-07 PROVIDE CAR DOOR RESTRICTOR (ZONE LOCK) 67-X-10 REPAIR COMMUNICATION IN CAR (TELEPHONE) PROVIDE CODE COMPLIANT 24" TOE GUARD FOR THE UNDERSIDE OF PLATFORM.Nothing owed — awaiting certificate of correction
ECB03/24/2015RESIDENCE ALTERED (FOR OCCUPANCY) AS A DWELLING FOR MORE THAN THE # OFFAMILIES LEGALLY (APPROVED # OF FAMILIES) AUTHORIZED BY THE C OF O OR OFFICIAL RECORDS. ILLEGAL OCCUPANCY NOTED AT BASEMENT LEVEL CREATED ANothing owed — awaiting certificate of correction
ECB12/08/201435Q03,39O02,39X10,4010,52M07,50Q03,67X10,68B07,70O02,71X10,76X10,76Q03,77B07. 35Q03-INSTALL COVERS FOR ELECTRICAL BOXES TOP OF CAR; 38X10-REPAIR LIGHT TOP OF CAR; 40I10-REPAIR MOTOR ROOM FLOOR; 52M07-PROVIDENothing owed — awaiting certificate of correction
ECB10/20/201470O02,39O02,40O02,70Q03,40D06,41D06,41D06,41L10,56Y10,44H10,52K10,67X10,68M07,100M07,99U05,39Y02,050710. 70Q04-COVER FOR SUMP PUMP HOLE; 40D06-SMOKE HOLE COVER; 41-REPAIR DOOR AND PROVIDE DOOR LOCK; 44-UNEVENNothing owed — awaiting certificate of correction
ECB07/29/2014FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: PLUMBING FIXTURES ARE NOT PROPERLY VENTED. SINK LOCATED IN THE GAS METER ROOM IS CONNECTED TO DRAIN LINE HAVING THE VENT NOT CONNECTED TO HOUSE VENTING SYSNothing owed — awaiting certificate of correction
ECB07/29/2014BC903.2.10.6 FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHEREREQUIRED: IN CELLAR THERE ARE 3 GAS DRYERS, HAVING NO SPRINKLER COVER-AGE TO STOP A LINT FIRE FROM SPREADING.RMDY: PROVIDE A SYSTEM OF AUTONothing owed — awaiting certificate of correction
ECB07/29/2014WORK W/O PERMIT WORK NOTED: IN CELLAR NEW GAS PIPE AND VALVES,FITTINGSWERE INSTALLED AND CONNECTED TO 3 GAS DRYERS WITH NO PERMIT FILED WITHTHE DOB. RMDY: OBTAIN PERMIT OR RESTORE TO LEGAL CONDITION.Nothing owed — awaiting certificate of correction
ECB07/29/2014GAS APPLIANCES AND/OR APPURTENANCES INSTALLED IN A PROHIBITED LOCATIONIN CELLAR GAS DRYERS & WASH MACHINES ARE INSTALLED IN GAS METER ROOM. AS PER APPENDIX E (33#3) ANY TYPE OF EQUIPMENT SHALL NOT BE IN A GASNothing owed — awaiting certificate of correction
ECB08/07/201340D02,52K10,40D06,68M07,08V10,39O02,52M07,67X10,44H10,98U15,39Y02,97O02,70D02. 40D06-SMOKE HOLE COVER; 68-ELEV CO MAINTENANCE LOG SCHEDULE NOT FOUND IN MOTOR ROOM; 08-ELEV RELEVELING AT FLOOR STOPS; 52M07-SPINNothing owed — awaiting certificate of correction
ECB06/20/201140Y02 56Y02 56Y10 99BB05 42G11 38Y02 06Q03 70Q02 71X10. 42-FUSE WIRE JUMPED ON CONTROLLER. 06-DOOR OPERATOR LIMIT BOX COVER MISSING. 71-REPAIR DAMAGED PIT LIGHTING.Nothing owed — awaiting certificate of correction
ECB10/13/200950/ RESPONSE TO "B"COMPLAINT #2135819,REGARDING A DEFECTIVE BOILER ON THE PREMISES.BLDG SUPERINTENDENT DISREGARDED INSPECTOR'S REQUEST TO EXAMINING THE BOILER & REFUSE TO GAIN ACCESS TO THE BOILER RM.RESP'DNothing owed — awaiting certificate of correction
ECB09/18/200998BB6.40O2.56Y13.41D6.16L10.41D06 PROVIDE LOCK FOR DOOR 29O3 TOP OF CAR DOOR OPERATOR LIMIT BX 16L10 ALL HOISTWAY DOORS HAVE EXCESSIVE BOTTOM ARM PLAYNothing owed — awaiting certificate of correction
ECB07/02/2009FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER. NOTED: AT 2ND FLOOR BATHROOM APT 2A SECTION OF FIRE-RATED CEILING COLLAPSED OVER BASTHTUB, AT 6TH FLOOR BATHROOM APT 6A, FLOOR SAGGING AND DISPLACED, AT "Nothing owed — awaiting certificate of correction
ECB02/27/2009B254,4B,15,16,21A,25,34,38,40,50,50A,50B,50C,50D,50E,50F. 50 BOILER SAFETY VALVE NOT PIPED TO FLR. 50A EXPOSE WIRES ON BURNER 50B CHIMNEY NEED CLEANING. 50C AROUND CHIMNEY NOT SEAL 50D OIL ON BOILER ROOM FLRNothing owed — awaiting certificate of correction
ECB07/14/2008B354,16,32A,34A,50,50A,50B,50C,50D,50E,50F,50G,50H,50I,50J. 50 REAR SIGHT GLASS MISSING 50A FRONT CLEANOUT DOOR NOT SEALED. 50C DISCHARGE PIPE MISSING ON POP SAFETY VALVE. 50D FAN BLADE MISSING ON FRESH AIRNothing owed — awaiting certificate of correction
ECB06/18/200886U05.40D06.41G11.34Q03.32H10.83O02.28Q03.16L10.21Q03.39D06.41G11 5 FUSES OPN THE CONTROLLER ARE WIRE JUMPED 34Q03 WIRE EXPOSED LEFT SIDE OFCONTROLLER 32H10 CTW ROLLERS ARE WORN 16L10 5 FL HOISTWAY DOOR EXCESSINothing owed — awaiting certificate of correction
ECB01/30/200812Q10.83L10.27H11.31H11.5L10.39P7. 12Q CAR LIGHTS UNGUARDED 83C NOISE IN HOISTWAY WHEN TRAVELING 27H CAR GUIDE SHOES NEED TO BE REPLACED 5L CAR DOOR DOESN'T OPEN ALL THE WAYNothing owed — awaiting certificate of correction
ECB01/24/200834A,B,50A,B,C.50A-SAFETY ON TOP OF BOILER IS LEAKING & NEED TO BE PIPETO GROUND.50B-RELIEF VALVE FOR COLD SIDE OF COIL IS MISSING.50C-MISSING COVERS FOR CONTROLS ON TOP OF BOILER.Nothing owed — awaiting certificate of correction
ECB05/01/200740D06,39O02,86U05,55Y13,38O02,38Y02,59X10,28Q03.Nothing owed — awaiting certificate of correction
ECB08/10/200683X10 RETURN ELEVATOR TO SERVICE FOR PROPER INSP OF ELEVATOR. NOTIFY DOB WHEN ELEVATOR IS PUT BACK INTO SERVICE.Nothing owed — awaiting certificate of correction
ECB09/19/200383X10 #83 YOU MUST RETURN THIS DEVICE BACK TO SERVICE SO A PROPER INSPECTION CAN BE CONDUCTED.Nothing owed — awaiting certificate of correction
ECB09/04/200210D06/05J11/08M07/09H12/14M07/57O02/03O02/31Q03/15L11/37Q03/35O02. 05 EXCESSIVE GAP AT RETURN POST. 03 CLEAN OIL. 31 TOP OF CAR BOX COVER. 15 5TH FL H/D SLAMSON CLOSE. 37 WIRES EXPORSED SIDE OF CONTROLLER, PROVNothing owed — awaiting certificate of correction
ECB04/10/199873X,14I,03M,57O,57Z,#03MT=CAPACITY PLATE #73X11 MAKE REPAIRS AND RETURN TO SERVICE.Nothing owed — awaiting certificate of correction