HPD10/24/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 1D, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST
HPD10/24/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 1K, 1st STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD10/24/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 6G, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 1J, 1st STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''SOUTH'', 1st FROM EAST AT SOUTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 2A, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'', 1st FROM WEST AT NORTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH'', 1st FROM EAST AT SOUTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTRH'', 1st FROM WEST AT NORTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 5P, 5th STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH'', 1st FROM EAST AT SOUTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 6M, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''SOUTH'', 1st FROM EAST AT SOUTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 1F, 1st STORY, 4th APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH'', 1st FROM WEST AT NORTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'', 1st FROM WEST AT NORTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 5J, 5th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''SOUTH'', 1st FROM EAST AT SOUTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 5B, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''NORTH'', 1st FROM WEST AT NORTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH'', 1st FROM EAST AT SOUTH
HPD10/11/2025§ 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''SOUTH'', 1st FROM EAST AT SOUTH
HPD08/18/2025§ 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.
HPD08/18/2025§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
HPD08/15/2025§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN ENAMEL GLAZE AT BATHTUB IN THE BATHROOM LOCATED AT APT 6J, 6th STORY, 2nd APARTMENT FROM EAST AT SOUTH
ECB07/01/2025FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE:-AT TIME OF INSPECTION, I OBSERVED EXP #1 WEST, #2 NORTH, #3 EAST-OBJECTS OBSTRUCTING FIRE ESCAPE LANDINGS MULTI LOC. REMEDY: REMOVE ALL OBSTRUCTIONS FROM A$1K due
DOB07/01/2025EMERGENCY WORK ORDER DUE TO CRACKED/BROKEN WINDOW GLASS WITH LOOSE MATERIAL @ EXP 2 NO. REMEDY: IMMEDIATELY TAKE & PROVIDE ADEQUATE SAFET MEASURES TO SECURE/PROECT PUBLIC. ADDITIONALLY REMOVE ALL LOOSE MATERIAL AND MAKE IMMEDIATE REPAIRS OF ALL CRACKED/BROKEN WINDOWS UNDER THE FULL SUPERVISION OF A NYS LICENSED PROFESSIONAL
ECB07/01/2025FAILURE TO MAINTAIN BUILDING EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 WEST-CRACKED/SPALLING BRICK/MORTAR JOINTS AT PARAPET LEVEL AT FRONT COURTYARD SETBACK AT WEST FACIN$5K due
ECB06/13/2025RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION, CLASS 1 VIOLATION ISSUED FOR, NO CERTIFICATE OF COMPLIANCE FROM PERMIT# X00434171 FILE IN THE YEAR 2020, FOR DLM, REMEDY, FILE APPLICATION WITH NYCDOB,..$1K due
HPD06/09/2025§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQFT AT CEILING IN THE BATHROOM LOCATED AT APT 4C, 4th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
HPD06/01/2025§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE LAMINATE FLOOR TILE IN THE 3rd ROOM FROM NORTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT NORTH
HPD06/01/2025§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT NORTH
HPD06/01/2025§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT NORTH
HPD06/01/2025§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER SASH AT 2ND WINDOW FROM NORTH AT EAST IN THE 3rd ROOM FROM NORTH LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT NORTH
HPD06/01/2025§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ.FT AT CEILING AND EAST WALL IN THE BATHROOM LOCATED AT APT 6A, 6th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT NORTH ORIGINAL VIOLATION 17931719 ISSUED 01-JUN-25 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
HPD01/27/2025§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD01/27/2025§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD01/27/2025§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE WATER SUPPLY PIPE AT SINK IN THE KITCHENETTE LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD01/27/2025§ 27-2024 ADM CODE PROVIDE ADEQUATE SUPPLY OF HOT WATER FOR THE FIXTURES AT BATHTUB IN THE BATHROOM LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD01/27/2025§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH WALL IN THE KITCHENETTE LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''NORTH''
HPD01/02/2025HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 3H, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION ''SOUTH''
DOB12/01/2024FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB08/21/2024FAILURE TO MAINTAIN EXTERIOR BLDG WALL. SPALLING,CRACKED & LOOSE BRICKS AT EXP 1(W ELEV),EXP 2(N ELEV)&4 (S ELEV).BROKEN WINDOW GLASS @ EXP 1&2.FIRE ESCAPES/EGRESS BLOCKED BY OBJECTS.INADEQUATE AC UNIT AT ALL EXPOSURES. REMEDY: MAINTAIN EXTERIOR WALL. REMOVE ALL OBJECTS IN THE FIRE EXIT
HPD03/11/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER WINDOW SASH TO FIRE ESCAPE WINDOW IN THE KITCHEN LOCATED AT APT 5F, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH''
HPD03/11/2024§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF MAIN GAS LINE PIPING INSTALLED UNDERNEATH DROPLADDER PREVENTING FROM DESCENDING AT BUILDING FRONT INNER COURT WEST
HPD03/11/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE GLASS AT UPPER WINDOW SASH AT PUBLIC HALL, 2nd STORY, SECTION ''SOUTH''
HPD03/11/2024§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 5F, 5th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''NORTH''
DOB03/04/2024EMERGENCY WORK ORDER DUE TO THE FOLLOWING OBSERVED:AT EXP1 WEST ELEV C RACKED STUCCO MASONRY AROUND WINDOWS,BULGING AT 6/7TH WINDOWS AT NW OF EXP1.DETERIORATED LINTEL ON NW&SW PARAPET LEVEL AT FRONT COURTYARD.DET ERIORATING STUCCO AT ENTRANCE.REMEDY:IMMEDIATELY REMOVE LOOSE HAZARDOU S MATERIAL NOTED & PROVIDE SAFETY MEASURES(SWS)UNDER A LIC PROFESSION
DOB12/01/2023FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB05/11/2022FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD02/07/2022§ 27-2056.7, 27-2056.8, 27-2056.9 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY PERFORMING ACTIVITIES NECESSARY TO ABATE TESTED LEAD-BASED PAINT FROM REQUIRED WINDOW AND/OR DOOR FRICTION SURFACES FOR APARTMENT AND MAKE FLOORS SMOOTH AND CLEANABLE, POSITIVE LEAD-BASED PAINT IN AN APARTMENT WITH A CHILD UNDER SIX LOCATED AT APT 3P, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH
HPD02/07/2022§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF FURNITURE OBSTRUCTING THE FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 3P, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH
HPD02/07/2022§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st RISER FROM NORTH AT EAST WALL, 1st WINDOW FRAME FROM NORTH AT EAST WALL, 2nd WINDOW FRAME FROM NORTH AT EAST WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 3P, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH
HPD02/07/2022§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM SOUTH AT WEST WALL IN THE BATHROOM LOCATED AT APT 3P, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH
HPD02/07/2022§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM WEST AT NORTH WALL, 1st WINDOW FRAME FROM NORTH AT EAST WALL IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 3P, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH
HPD02/07/2022§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 3P, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH
HPD02/07/2022§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) EAST WALL IN THE FOYER LOCATED AT APT 3P, 3rd STORY, 4th APARTMENT FROM WEST AT NORTH , SECTION AT SOUTH
ECB01/06/2022UPON INSPECTION THE DEVICE WAS FOUND OUT OF SERVICE ON THE TOP LANDING WITH THE DOOR CLOSED. RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB. AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION.$6K due
DOB12/22/2021FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB09/22/2021C/U;C/U 8V1;C/U 16L10;C/U 34E10,59BB5,42M5:C/U 8-V-1=FLOOR STOPS EXCESSIBLY OFF LEVEL ADJUST/C/U 16-L-10=BASEMENT HOISTWAY DOOR,DOOR SLAMS TOO HARD AND FAST REPAIR/C/U 34-E-10=ELEVATOR RUBBING ONTO HOISTWAY OR$6K due
DOB04/29/2021FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB09/02/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB11/14/2018FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD04/11/2018§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT SOUTH STACK FRONT 6TH STORY
HPD04/11/2018§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT SOUTH STACK FRONT 3RD STORY
HPD04/11/2018§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONER AT SOUTH STACK FRONT 5TH STORY
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/01/2012FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB12/21/1989VP-VIOLATION UNSERVED ECB-ACTIVE
DOB12/21/1989V-DOB VIOLATION - ACTIVE
ECB04/03/2020CLASS 1, NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTNothing owed — awaiting certificate of correction
ECB08/20/201802X10,67X10,64M07,70O02,31V10-02X10)REM: REPAIR ALARM SYSTEM IN CAR AND CALL NYCDOB FOR RETURN TO SERVICE. 67X10)REM: REPAIR IN CAR PHONE AND CALL NYCDOB FOR RETURN SERVICE. 64M07)REM: PROVIDE AND INSTALL IN CANothing owed — awaiting certificate of correction
ECB07/09/2015FENCE EXCEEDS PERMITTED HEIGHT.NOTED INSTALLATION OF A SOLID FENCE GATE OF RIGHT SIDE YARD.FENCE EXCEEDS THE HEIGHT PERMITTED ON A RESIDENTIAL DISTRICT R7-1 FENCE IS APPROX.10'HIGH.REM:CONFORM FENCE TO CODENothing owed — awaiting certificate of correction
ECB08/28/2009FAILURE TO MAINTIAN BLDG IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR &/OR HARDWARE FOR BC1008.1.8;27-371(J) NOTED:NORTH BULKHEAD DOOR MISSHAPEN & DOES NOT CLOSE PROPERLY.LOCKING MECHANISM IS DEFECTIVE.REMENothing owed — awaiting certificate of correction