HPD08/07/2026§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD08/07/2026HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD08/07/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ. FT AT WEST WALL AND CEILING IN THE BATHROOM LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD08/07/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE 1st WINDOW FRAME FROM SOUTH AT WEST WALL IN THE KITCHEN LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD08/07/2026§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 1st ROOM FROM NORTH AT EAST, THE BATHROOM , THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD08/07/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN ENAMEL GLAZE AT BATHTUB IN THE BATHROOM LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD08/07/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH WALL IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
HPD08/07/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGE AT DOOR IN THE ENTRANCE LOCATED AT APT 4E, 4th STORY, 3rd APARTMENT FROM WEST AT NORTH
ECB03/17/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SUMMONS 39154324L, FILE A CERTIFICATE OF CORRECTION$1K due
ECB03/17/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SUMMONS 39154326P, FILE A CERTIFICATE OF CORRECTION$1K due
ECB07/21/2025UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER: VIOLATION # 39118045K WAS ISSUED ON 6/27/2024 BY INSPECTOR BADGE # 2790 FOR FTM ELEVATOR OR CONVEYING SYSTEM. RESPONDING ELEVATOR COMPLAINT. UPON INSP$12K due
ECB07/21/2025UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER: VIOLATION # 39114012X WAS ISSUED ON 5/10/2024 BY INSPECTOR BADGE # 3203 FOR FTM ELEVATOR OR CONVEYING SYSTEM. INSPECTOR OBSERVED NO DOOR LOCK MONITOR$12K due
ECB07/21/2025UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONER'S ORDER: VIOLATION# 39118994M WAS ISSUED ON 7/12/2024 BY INSPECTOR BADGE # 3681 FOR FTM ELEVATOR OR CONVEYING SYSTEM. INSPECTOR OBSERVED CAR COMMUNICATION INOP$6K due
DOB12/11/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB12/11/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB05/29/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD04/16/2024§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) SOUTH WALL IN THE 3rd ROOM FROM NORTH LOCATED AT APT 2H, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB08/07/2023AT TIME OF MY INSPECTION I OBSERVED A 6 STORY OCCUPIED BUILDING WITH A SIDEWALK SHED.I NOTICED THAT IN ENTRANCE OF BUILDING A SIDEWALK SHED DECK THAT DOESNT REACH TIGHT TO FACADE ALLOWING A GAP APPORX.4 FEET WI$1K due
ECB08/07/2023AT TIME OF MY INSPECTION I OBSERVED A 6 STORY OCCUPIED BUILDING WITH SIDEWALK SHED MISSING INFORMATION PANEL.THIS CREATES A UNSAFE SITUATION NOT HAVING BUILDING ADDRESS IN CASE OF EMERGENCY.PROVIDE INFORMATION$1K due
DOB07/27/2021V-DOB VIOLATION - ACTIVE
HPD05/26/2021§ 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.
HPD03/29/2021§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
DOB01/07/2021CYCLE 9B UNSAFE REPORT FILED
DOB01/07/2021CYCLE 8B UNSAFE REPORT FILED
DOB01/07/2021CYCLE 9B FAILURE TO CORRECT SWARMP CONDITIONS
HPD08/20/2020§ 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.
HPD12/24/2019§ 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.
DOB07/31/2018FAILED TO FILE FISP CYCLE 8B TECHNICAL REPORT BY 02/21/2018
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
DOB08/30/2013FAILED TO FILE FISP CYCLE 7B TECHNICAL REPORT BY 08/21/2012
DOB08/28/1991VP-VIOLATION UNSERVED ECB-ACTIVE
ECB04/29/2026CEASE USE ITEMS: (1) DOOR RESTRICTOR DEVICE IS INOPERATIVE, IN VIOLATION OF (ASME A17.1/CSA B44 2.12.5). (2) MACHINE BRAKE PADS EXHIBIT UNEVEN WEAR, INDICATING IMPROPER MAINTENANCE, AND BRAKE MAINTENANCE TAG ISHearing held — result not yet published$1K proposed
ECB08/05/2025CLASS 2:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION,EMERGENCY PHONE INOPERATIVE,CONNECT PHONE TO 24HRS EMERGENCY SERVICE.ELEVATORNothing owed — awaiting certificate of correction
ECB05/21/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE ONLY DEVICE IN THE SECTION OF THE BUILDING IS FOUND TO BE OUT OF SERVICE, CREATINNothing owed — awaiting certificate of correction
ECB02/05/2025(05-A-10) CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/DISABLED AND RENDERED (MISSING) INOPERATIVE. THIS IS A SAFETY DEVICE TO ENSURE ELEVATOR PASSENGERS' SAFETY. REPAIR RESTRICTOR AND CONTACT NYNothing owed — awaiting certificate of correction
ECB08/26/2024RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION CEASE USE ITEM FOUND, CAR DOOR RESTRICTOR ALTERED TO MAKE IT NOT TO WORK, REMEDY; REPAIR THEN CONTACT NYCDOB FOR RESTORE TO SERVICE RE-INSPECTION,,,,,,,,,Nothing owed — awaiting certificate of correction
ECB07/12/2024IN-CAR COMMUNICATION INOPERATIVE. PROVIDE EMERGENCY STAIRWAY SIGNS ON FLOORS, 5,3,2,1. PROVIDE ACCESS TO ELEVATOR MACHINE ROOM.Nothing owed — awaiting certificate of correction
ECB05/10/2024NO DOOR LOCK MONITORING INSTALLED IN CONTROLLER AS MANDATED IN APPENDIX K OF 2014 BUILDINGS CODES; REMEDY INSTALL DLM IN CONTROLLER AND PERFORM TEST WITH NYC DOB; EMERGENCY PHONE NOT WORKING; REPAIR; MISSING MINothing owed — awaiting certificate of correction
ECB11/20/2023RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION CLASS 1 VIOLATION ISSUED RECURRING VIOLATION ISSUED FOR, NO DOOR LOCK MONITORING (DLM ) , REMEDY; FILE APPLICATION AND INSTALLED DLM............CLASS 2 VINothing owed — awaiting certificate of correction
ECB08/16/2023FAILURE TO CERTIFY: FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR NOV 39056774J. REMEDY: FILE CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB07/08/2023AT THE TIME OF INSPECTION, OBSERVED ERECTED SIDEWALK SHED AT EXPOSURE 1 WITHOUT PARAPET INFORMATION PANEL. G.C FAILED TO COMPLY WITH BC 3301.9Nothing owed — awaiting certificate of correction
ECB06/23/2023CEASE USE ITEM: HOIST CABLES DAMAGED, REPLACE HOIST CABLES. CLASS 2 ITEMS: PRINTS FOR THE CONTROLLER MISSING, PROVIDE. LIGHT IN THE OVERHEAD SPACE IN DISREPAIR, REPAIR. MACHINE ROOM DOOR IN DISREPAIR, PROVIDE DNothing owed — awaiting certificate of correction
ECB03/10/2022CLASS 1 VIOLATION ISSUED DLM, NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3,REMEDY; FILE APPLICATION, INSTALL DLM AND PERFORM AND FILE TEST WITH NYCDOB. CLASS 2 VIOLNothing owed — awaiting certificate of correction
ECB05/30/201228-116.4.1: 44R11,97R07: 97R07;OPERATING DEVICE WITHOUT A CERT OF COMPLIANCE. NO REPORT OF INSPECTION SUBMITTED TO DOB & WITNESSING OF TEST BY DOB. REM:CONTACT YACRUZ@BUILDINGS.NYC.GOV TO SCHEDULE TEST APPT TONothing owed — awaiting certificate of correction