ECB08/03/2026FAILURE TO MAINTAIN PARKING STRUCTURE IN SAFE CONDITION. AT TIME OF INSPECTION ON AN OCCUPIED PARKING STRUCTURE CONSISTING OF 01 LEVEL BELOWGRADE, OBSERVED CRACKED/SPALLED CONCRETE CEILING, CRACKED BEAMS AT GRA$1K due
ECB08/08/2025FAILURE TO SECURE PUBLIC SAFETY AND MAKE THE BUILDING STRUCTURE AND APPURTENANCES CONFORM TO THE PROVISION OF THE ADMINSTRATIVE CODE AFTER UNSAFE NOTIFICATION FILED BY QPSI. AS NOTED: AT TIME OF INSPECTION ON A$25K due
ECB07/09/2025FAILURE TO MAINTAIN PARKING STRUCTURE IN SAFE CONDITION. AS NOTED AT TIME OF INSPECTION ON AN OCCUPIED PARKING STRUCTURE CONSISTING OF (1) LEVEL BELOW THE BUILDING, OBSERVED SOME CRACKED ON THE BEAM AND WALLS A$630 due
DOB03/05/2025FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/23/2024FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 IN 2023
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
HPD09/10/2021§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONING UNIT PROTRUDING BEYOND WINDOW SILL AT 2ND, 3RD, 4TH, 5TH AND 6TH STORY BALCONIES, WEST STACK , NORTH SIDE ,BUILDING FRONT YARD, MORE THAN 4 INCHES INTO THE PATH OF THE FIRE ESCAPE.
HPD09/10/2021§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONING UNIT PROTRUDING BEYOND WINDOW SILL AT 2ND, 3RD, 4TH, 5TH AND 6TH STORY BALCONIES, WEST STACK , SOUTH SIDE ,BUILDING FRONT YARD, MORE THAN 4 INCHES INTO THE PATH OF THE FIRE ESCAPE.
HPD06/09/2021HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6B, 6th STORY, APARTMENT AT SOUTH , SECTION AT NORTH
HPD01/29/2019§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
HPD01/29/2019§ 27-2018 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM SOUTH AT WEST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB06/03/2013FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/03/2012FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB01/01/2012FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD08/31/2011§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE FOYER LOCATED AT APT 5A, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT NORTH
HPD08/31/2011§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM SOUTH AT WEST WALL IN THE FOYER LOCATED AT APT 5A, 5th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT NORTH
HPD03/24/2010§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) SOUTH WALL IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 3K, 3rd STORY, 3rd APARTMENT FROM SOUTH AT WEST
DOB04/02/2007V-DOB VIOLATION - ACTIVE
DOB04/02/2007V-DOB VIOLATION - ACTIVE
DOB04/02/2007V-DOB VIOLATION - ACTIVE
DOB04/02/2007V-DOB VIOLATION - ACTIVE
DOB01/29/2007V-DOB VIOLATION - ACTIVE
DOB01/29/2007V-DOB VIOLATION - ACTIVE
DOB01/29/2007V-DOB VIOLATION - ACTIVE
DOB01/29/2007V-DOB VIOLATION - ACTIVE
DOB04/12/2002V-DOB VIOLATION - ACTIVE
DOB04/12/2002V-DOB VIOLATION - ACTIVE
HPD05/27/1999§ 27-2005, 2007 ADM CODE AND DEPT. RULES AND REGULATIONS. REMOVE THE ENCUMBRANCE OBSTRUCTING EGRESS FROM FIRE ESCAPES AIR CONDITIONERS 3 THRU 6 STYS BALCONIES FRONT SOUTH
DOB08/29/1995V-DOB VIOLATION - ACTIVE
DOB06/29/19902
DOB10/12/19891
ECB12/02/2024FAILURE TO SUBMIT THE REQUIRED PARKING STRUCTURE INITIAL OBSERVATION REPORT FOR AN EXISTING PARKING STRUCTURE OR A PERIODIC INSPECTION OF A PARKING STRUCTURE(PIPS) REPORT DOCUMENTING THE CONDITIONS OF PSID#B000Nothing owed — awaiting certificate of correction
ECB11/10/2009FAILURE TO PROVIDE ELEVATOR'S LANDING SIGN THAT SHALL READ"IN CASE OF FIRE USE STAIRS UNLESS OTHERWISE INSTRUCTED"AT THE ELEVATOR BANK ON FLOOR 2 TO 6.FAILURE TO PROVIDE 3INCH MINIMUM HIGH ALPHABETIC LETTER OFNothing owed — awaiting certificate of correction
ECB01/15/200808V01,11L10,39P07.11L10-ELEVATOR DOES NOT TAKE A 6FL CALL.Nothing owed — awaiting certificate of correction
ECB01/15/200839P07,15M07.PROVIDE ACCESS TO MOTOR ROOM.15M07-PROVIDE ELEV CERTIFICATE ON SIGNAGE IN ELEVATOR.Nothing owed — awaiting certificate of correction
ECB10/13/2006CEASE USE, HAZARDOUS. 09H11,17H11,20Q07,21J01,16R09,39P16,05I10,10H11,16F10. 9, 17-H-11 BSMT. 21-J-01 BSMT. 16-R-09, ILLEGAL BSMT HOISTWAY CLOSURE. 21-J-09, SHAKING BSMT HOIST DOOR STOPS CAR IN FLIGHT,Nothing owed — awaiting certificate of correction
ECB09/29/200583X10/17H11/27J01. 27-J,17-H; LOBBY HOISTWAY DOORNothing owed — awaiting certificate of correction
ECB08/23/200585BB05/08V01/10H11/17H11/32D06/38O02/66O02. 85-BB-05-CURRENT 5 YEAR TEST TAG EXPIRED. 08-V-01-ELEVATOR DOES NOT STOP LEVEL ON FLOORS 6,2,1. 10-H-11-CAR DOOR GIBS ARE WORN. 17-H-11-HOISTWAY DOOR GIBS ON FLOORS 4Nothing owed — awaiting certificate of correction
ECB08/23/2005CEASE USE/HAZARDOUS. 25M07/10H11/17H11/20I11/28M07/08V01/21M07/38O02/66O02. 25-M-07-CAR RUNNING WITHOUT EMERGENCY ESCAPE HATCH IN PLACE BEFORE RETURNING TO SERVICE CALL CHIEF DONAL FRANKLIN AT (212)566-5539 TONothing owed — awaiting certificate of correction
ECB08/06/200406N10/16L10 06-N, CAR RUNS WITH CAR DOOR OPEN, 16-L REPAIR LOBBY HATCHWAY DOOR. CEASE USE OF THIS DEVICE. CALL 212- 566-5519 FOR APPOINTMENTFOR REINSPECTION WHEN REPAIRS ARE MADE.Nothing owed — awaiting certificate of correction
ECB06/16/200416L10,17H11,20Q03,21J01,24X10,28A10,28Q03,16B10,63D06,63M07,40D06,41G11,41I11,60R09,41A06,85R05.16-L-LOBBY HOISTWAY DOOR HANGERS.17-11-LOBBY AND BSMT. 20-Q-BSMT.21-J-01-SHAKING BSMT HOIST DOOR STOPS CAR ALSONothing owed — awaiting certificate of correction
ECB06/15/200424X10,39O02,40D06,41G11,60R09,66O02,41D06,85R05,84T15,84D06,84L11.60-R-REMOVE ILLEGAL HOOK UP.41-D-SECURE HANGING TIMER.85-R-GOV TAG NG. 84-T-CITY ID #'S ON CONTROLLER AND MACHINE 84-D-SMOKE HOLE GRATE.84-L-EMPNothing owed — awaiting certificate of correction
ECB03/04/200380B07-08V01-18M07-07B01-05I11-62O02-67O02-32M07-21L11-80O02-55M07. 80-M POSTCERT IN CAR AS PER RULE 27-1004A-1004B. 18-M 6 FLOOR GUARD 07-B ADJUST SAFTEY EDGE REPLACE MISSING COVER 05-I DOOR EDGE CAR GATE DAMAGNothing owed — awaiting certificate of correction
ECB03/04/200380B07-05M07-10M07-07B01-08V01-62O02-67O02-39D06. 80-B POST CERT IN CAR AS PER ROLE 27-1004A OR 1004B 05-M-GLASS MISSING (VISION) 10-M 2 GIB 07-B ADJUST DOOR SAFEY EDGE 39-D POPERLY SECURE HANGING TIMER RELAY.Nothing owed — awaiting certificate of correction
ECB05/15/199216M,57O,30O,28H,07L, #16-REPLACE NYLON GUIDE ON SHAFTWAY DOOR TO ELEMINATE PLAY ON SAME OR REPLACE SHAFTWAY DOORS SADDLE. #07-REPAIR OR REPLACE SAFATY EDGE.Nothing owed — awaiting certificate of correction
ECB05/15/199216H,28H,30O,57O, #16-REPLACE WITH PROPER NYLON GUIDE OR REPLACE SHAFTWAY DOOR SADDLE.Nothing owed — awaiting certificate of correction
ECB04/04/199117L,37J,06J,55X,57O,58O,59O,58J,74R,74M,(74A)INSTALLED NEW CAR ENCLOSURE PANELS W/O A PERMIT (74B)CAPACITY PLATENothing owed — awaiting certificate of correction