ECB02/13/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORRECTION ON FILE FOR VIO#35668475L AS OF 2/13/26., FILE A CERTIFICATE OF$1K due
ECB02/13/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. NO CERTIFICATE OF CORECTION ON FILE FOR VIO#35668476N AS OF 2/13/26., FILE A CERTIFICATE OF$1K due
ECB05/10/2025CONTRARY TO OCCUPANCY. CERTIFICATE OF OCCUPANCY STATES 1 FL TO BE USEDAS COMMERCIAL NOW CONVERTEDINTO A SOCIAL CLUB, LOUNGE AND PUBLIC ASSEMBLY. NO PERMITS ISUED FOR USE OF 1FL AS A PUBLIC ASSEMBLY PLACE. CO #1$3K due
ECB05/10/2025FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. OBSERVED OPENAND UNCLAPPED GAS LINE AT KITCHEN CREATING A HAZARDOUS CONDITION FOR TENANT ABOVE AND ADJACENT PROPERTIES. ALL GAS LINES/VALVES MUST BE CAPP$3K due
ECB06/30/2023NOTED, CONDITION ON METAL LINTELS ROTTED AND CORRODED OVER WINDOWS AT 2ND AND 3RD FLOORS, SEE NOV #35116265H.$3K due
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
HPD03/19/2021§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING AT PUBLIC HALL, 3rd STORY
HPD03/19/2021§ 27-2005 ADMIN. CODE: REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 3rd STORY
HPD03/19/2021§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING AND NORTH WALL AT PUBLIC HALL, 1st STORY
HPD03/19/2021§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF ELECTRIC EXTENSION CORDS AT ALL STORIES AT PUBLIC HALL
DOB11/08/2019VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2017 INSPECTION REPORT
HPD04/19/2018§ 27-2091 HMC, § 302 MDL : APARTMENTS HAVE BEEN ISSUED A COMMISSIONER'S ORDER AND OCCUPANTS ARE IN NEED OF RELOCATION SERVICES. APARTMENTS CANNOT BE RE-OCCUPIED UNITL THE COMMISSIONER'S ORDER IS REVOKED AFTER HPD INSPECTION OF APARTMENTS. COMMISSIONERS ORDER # 18/0066 IN THE ENTIRE APARTMENT LOCATED AT APT 2, 2nd STORY
HPD04/19/2018§ 27-2091 HMC, § 302 MDL : APARTMENTS HAVE BEEN ISSUED A COMMISSIONER'S ORDER AND OCCUPANTS ARE IN NEED OF RELOCATION SERVICES. APARTMENTS CANNOT BE RE-OCCUPIED UNITL THE COMMISSIONER'S ORDER IS REVOKED AFTER HPD INSPECTION OF APARTMENTS. COMMISSIONERS ORDER # 18/0068 IN THE ENTIRE APARTMENT LOCATED AT APT 2, 3rd STORY
HPD04/19/2018§ 27-2091 HMC, § 302 MDL : APARTMENTS HAVE BEEN ISSUED A COMMISSIONER'S ORDER AND OCCUPANTS ARE IN NEED OF RELOCATION SERVICES. APARTMENTS CANNOT BE RE-OCCUPIED UNITL THE COMMISSIONER'S ORDER IS REVOKED AFTER HPD INSPECTION OF APARTMENTS. COMMISSIONERS ORDER # 18/0065 IN THE ENTIRE APARTMENT LOCATED AT APT 3, 3rd STORY
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB02/24/2017VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2015 INSPECTION REPORT
DOB10/01/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2014 INSPECTION REPORT
DOB09/23/2015FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB03/03/2015VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2013 INSPECTION REPORT
HPD04/23/2014§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR THE CEILING IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 2, 2nd STORY
HPD04/23/2014§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. LOCATED AT APT 2, 2nd STORY
HPD04/23/2014§ 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF RODENTS ,RATS AT PUBLIC HALL
HPD04/23/2014§ 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCKING DEVICE AT PUBLIC HALL, 1st STORY
HPD04/23/2014§ 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 2, 2nd STORY
HPD01/17/2014§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT THE CEILING AT PUBLIC HALL, 2nd STORY
HPD01/17/2014§ 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCKING MECHANISM ON DOOR AT STREET ENTRANCE AT PUBLIC HALL
HPD01/17/2014§ 27-2046.1 HMC: REPAIR OR REPLACE THE CARBON MONOXIDE DETECTING DEVICE(S). MISSING LOCATED AT APT 3, 3rd STORY, APARTMENT AT WEST
HPD01/17/2014§ 27-2005,2007 ADMIN. CODE: FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR GATES FROM WINDOW TO FIRE ESCAPE (PADLOCKABLE GATE) IN THE 2nd ROOM FROM EAST AT NORTH LOCATED AT APT 3, 3rd STORY, APARTMENT AT WEST
HPD09/12/2013§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE FRONT DOOR LOCK AT LOBBY
DOB02/27/2013FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD12/31/2010§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF NO ELECTRICITY SUPPLIED TO FIXTURES AT BATHROOM LOCATED AT APT 2, 2nd STORY
HPD12/31/2010§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF NO ELECTRICITY SUPPLIED TO FIXTURES AT KITCHEN LOCATED AT APT 2, 2nd STORY
HPD12/01/2009§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE RADIATOR SHUT OFF VALVE AT THE RADIATOR AT NORTH IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 2, 2nd STORY
HPD12/01/2009§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE ENTIRE APARTMENT LOCATED AT APT 2, 2nd STORY
HPD12/01/2009§ 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM WINDOW TO FIRE ESCAPE OR PROVIDE APPROVED TYPE GATE .. IN THE KITCHEN LOCATED AT APT 2, 2nd STORY
HPD12/01/2009§ 27-2045 ADM CODE REPAIR OR REPLACE THE SMOKE DETECTOR MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 2, 2nd STORY
HPD12/01/2009§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING CERAMIC TILES ON THE WALLS IN THE BATHROOM LOCATED AT APT 2, 2nd STORY
HPD05/05/2005§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF PAINT CHIP SINK BATHROOM, 3RD STORY APT 2.
HPD05/05/2005§ 27-2005 ADMIN. CODE: REFIT WINDOW SASHES NORTH ROOM 3 STORY APT. 2.
HPD05/05/2005§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING BATHROOM 2ND STY. APT. 1.
HPD05/05/2005§ 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE LIGHT SWITCH WALL FRONT NORTH ROOM, 3RD STORY APT 2.
HPD05/05/2005§ 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE WINDOW GLASS UPPER SASH KITCHEN 3RD STY APT 2.
HPD05/05/2005§ 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES KITCHEN AND BATHROOM FIXTURES 3RD STY APT 2.
HPD05/05/2005§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING KITCHEN, 3RD STORY APT 2.
HPD05/05/2005§ 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES 3 STY. APT. 2.
HPD05/05/2005§ 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE CEILING LIGHT SWITCH 1 FROM EAST ROOM 3 STY. APT. 2.
HPD05/05/2005HMC ADM CODE: § 27-2018.4 ABATE THE NUISANCE CONSISTING OF VERMIN MICE & ROACHES THROUGHOUT APT, 3RD STORY APT 2.
HPD05/05/2005§ 27-2026 ADMIN. CODE: REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET BATHROOM 3 STORY APT. 2.
HPD05/05/2005§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING FRONT SOUTH ROOM, 3RD STORY APT 2
HPD05/05/2005§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING WEST ROOM 3 STORY APT. 2
HPD05/05/2005§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF CONCEALED WATER LEAK CEILING WEST ROOM 3 STY. APT. 2.
HPD05/05/2005§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF CONCEALED WATER LEAK CEILING BATHROOM 2ND. STY. APT. 1
HPD05/05/2005§ 27-2013 ADMIN. CODE: PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WALLS & CEILINGS THROUGHOUT APT, 3RD STORY APT 2.
HPD01/13/2005§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL, 1st STORY
HPD01/13/2005§ 27-2046.1, 2046.2 HMC: PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES. IN THE FOYER LOCATED AT APT 3, 3rd STORY
HPD08/17/2004§ 27-2005 ADMIN. CODE: REMOVE THE ILLEGAL FASTENING PADLOCKED DOOR AT SCUTTLE CLOSET. AT PUBLIC HALL, 3rd STORY
HPD07/09/2004§ 27-2024 ADMIN. CODE: PROVIDE ADEQUATE SUPPLY OF COLD WATER FOR THE FIXTURES KITCHEN SINK & BATHROOM TUB, 3RD STORY APT 2.
HPD07/09/2004§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILING 2 STORY PUBLIC HALL.
HPD07/09/2004§ 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE BATHROOM 3 STORY APT. 2.
HPD07/09/2004§ 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE DOOR BELL FROM STREET TO 3RD STORY APT 2.
HPD07/09/2004§ 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE WEST ENTRANCE DOOR TO 3 STORY APT. 2.
HPD07/09/2004§ 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES SINK KITCHEN & WASH BASIN BATHROOM, 2ND STORY APT 1.
HPD07/09/2004§ 27-2010, 2011, 2012 ADMIN. CODE: REMOVE THE ACCUMULATION OF REFUSE AND/OR RUBBISH AND MAINTAIN IN A CLEAN CONDITION THE HOUSEHOLD ITEMS SCUTTLE CLOSET, 3RD STORY PUBLIC HALL.
HPD07/09/2004§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF NO ELECTRIC SERVICE PROVIDED TO LIGHT FIXTURES ALL STORIES PUBLIC HALL.
HPD07/09/2004§ 27-2005 ADMIN. CODE: REMOVE THE ILLEGAL FASTENING CHAIN AND LOCK ABLE TO BE LOCKED AT IRON GATE ENTRANCE TO BUILDING.
HPD07/09/2004§ 27-2013 ADMIN. CODE: PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILING AND WALLS THROUGHOUT 3RD STY APT 2.
HPD07/09/2004§ 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES 2ND. STORY APT. 1 KITCHEN AND BATHROOM.
HPD07/09/2004§ 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE WINDOW GLASS LOWER SASH REAR ROOM 3RD STY APT 2.
HPD07/09/2004§ 27-2005 ADMIN. CODE: PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILE WALL BATHROOM 3RD STY APT 2.
HPD07/09/2004HMC ADM CODE: § 27-2018.4 ABATE THE NUISANCE CONSISTING OF VERMIN MICE AND ROACHES THROUGHOUT 3RD STY APT 2
HPD07/09/2004§ 27-2005 ADMIN. CODE: REPLACE WITH NEW THE BROKEN OR DEFECTIVE MARBLE DOOR SADDLE ENTRANCE TO BATHROOM 3RD STY APT 2.
HPD07/09/2004§ 27-2010, 2011, 2012 ADMIN CODE: CLEANSE TO THE SATISFACTION OF THIS DEPARTMENT THE FLOORS AND STAIRS ALL STORYS PUBLIC HALL.
HPD07/09/2004§ 27-2031 ADMIN. CODE: PROVIDE HOT WATER AT ALL HOT WATER FIXTURES SINK KITCHEN & WASH BASIN BATHROOM, 3RD STORY APT 2.
HPD07/09/2004§ 27-2005 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN UNIFORM COLOR CEILINGS & WALLS, THROUGHOUT 3RD STORY APT 2.
HPD07/09/2004§ 27-2026 ADMIN. CODE: REPAIR THE BROKEN OR DEFECTIVE CONNECTION WASTE LINE KITCHEN SINK 3RD STY APT 2.
HPD07/09/2004§ 27-2005 ADMIN. CODE: PROPERLY REPAIR THE BROKEN OR DEFECTIVE LOCKING DEVICE ENTRANCE DOOR TO BUILDING.
HPD07/09/2004HMC ADM CODE: § 27-2018.4 ABATE THE NUISANCE CONSISTING OF VERMIN MICE AND ROACHES 3 STORY APT .2.
HPD07/09/2004§ 27-2005 ADMIN. CODE: PROPERLY SECURE THE LOOSE MAILBOXES TO WALL AT VESTIBULE.
HPD07/09/2004§ 27-2005 ADMIN. CODE: ABATE THE NUISANCE CONSISTING OF OF GATE ON FIRE ESCAPE WINDOW LOCK REAR ROOM, 3RD STORY APT 2.
HPD06/09/2003§ 27-2005 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE BUILING ENTRANCE DOOR. AT PUBLIC HALL, 1st STORY
ECB06/30/2015FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTE:BRICK WORK CRACKED AND MORTAR JOINTS ISSING AT 2ND AND 3RD STORY AT FRONT OF BUILD ING.METAL LINTELS ROTTED AND CORRODED OVER WINDOWS AT 2ND AND 3RD FLRSNothing owed — awaiting certificate of correction
ECB11/30/2012FAILURE TP MAINTAIN ACCESSORY SIGN. ILLUMINATED 3X5FT BOX ACCESSORY SIGN IS OFF BRACKETS & BEING HELD BY A SINGLE BOLT ATTACHED TO THE BLDG.SIGN IS OVER MAIN ENTRANCE & PUBLIC SIDEWALK. REMEDY: REMOVE SIGN.Nothing owed — awaiting certificate of correction
ECB05/22/199925A,25B,48A,48B,49. 25A-RETURNS CORRODED. 25B-RETURNS LEAKING. 48A-WATER GAUGE GLASS DIRTY. 48B-WATER GAUGE GLASS LEAKING. 49-FLUE PIPE NOT PROPERLY SEALED TO CHIMNEY BASE.Nothing owed — awaiting certificate of correction
ECB05/13/1998BoilersNothing owed — awaiting certificate of correction