DOB05/01/2026Ftm bldg.time of inspectn obsrved@ EXP1, long vertical crck on ground fl. Along w/ additional crcking@ multi location, including the parpet level & rusted/damaged watertable w/ expose masonry. @ exp 2 crck obsrvd @ several locations & spalling stucco. @ exp 4,damaged coping stone & overgrowth of vegetation observd. Remdy: repair &/or replace
ECB04/20/2026Failure to file acceptable amended cycle 7C and 8C report indicating correction of unsafe conditions described in initial facades report required by 28-302.5 for control #816814. Remedy: file acceptable report.$1K due
DOB09/23/2025Failure to maintain building exterior in a code compliant manner.note at time of inspection,observed at EXP1 multiple cracks in parapet.at w ater table(metal)rusting/holes and appear to show up leaned brick.at e XP2 observed multiple cracks in stucco at various levels and spalling at EXP4 observed overgrowth of vegetation.remedy:repair or replace
DOB12/23/2024Failure to certify correction on immediately hazardous (class 1) ECB violation
ECB10/21/2024Failure to maintain exterior facade and appurtenances. Notes: (1)deteriorated water table and brick masonry, loose brick masonry at exposure#1 east elevation. (2) cracked/spalling masonry and brick at north/eas$12K due
HPD03/16/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT NORTH FIRE DOOR AT PUBLIC HALL, 1st STORY
HPD03/16/2024§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT FLOOR AT PUBLIC HALL, 1st STORY
DOB02/22/2024Failed to file FISP cycle 9C technical report by 2/21/2024
HPD04/07/2023§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY2 identical filings
HPD04/07/2023§ 27-2046.1 hmc: post a proper notice of carbon monoxide detecting device requirements, in a form approved by the commissioner, in a common area of a class a multiple dwelling near inspection certificate or provide notice to tenants in a private dwelling.
HPD04/07/2023§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD04/07/2023§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD04/07/2023§ 27-2026 ADM CODE REPAIR THE LEAKY AND/OR DEFECTIVE FAUCETS AT BATHTUB IN THE BATHROOM LOCATED AT APT 2, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
HPD04/07/2023§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
HPD10/25/2021§ 27-2104 ADM code post and maintain a proper sign on wall of entrance story showing the registration number assigned by the department and the address of the building. At public hall
ECB10/05/2021Failure to maintain exterior building wall or appurtenances at exposure 2 spalling masonry at various locations.at exposure parapet level spalling on both sides.rem:maintain exterior building wall.$6K due
HPD07/15/2019§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD. AT PUBLIC HALL, 1st STORY
HPD07/15/2019§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD07/15/2019§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY
HPD07/15/2019§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL, 1st STORY
HPD07/15/2019§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY
HPD07/15/2019§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX MISSING AT PUBLIC HALL, 1st STORY
HPD07/10/2017§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
HPD07/10/2017§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY
HPD07/10/2017§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM SIGN MISSING AT PUBLIC HALL, 1st STORY
HPD07/10/2017§ 27-2045 ADM CODE POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAIL BOX SIGN MISSING AT PUBLIC HALL, 1st STORY
HPD07/10/2017§ 27-2046.1 HMC: POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN A PRIVATE DWELLING. AT PUBLIC HALL, 1st STORY
HPD01/06/2011SECTION 27-2070 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF GAS TO THE FIXTURES KITCHEN STOVE LOCATED AT APT 2, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
ECB05/08/2025Failure to submit an acceptable required cycle 9C report of critical examination documenting condition of exterior wall and appurtenances required by 28-302.4 for control #916814. Remedy: submit acceptable requNothing owed — awaiting certificate of correction
ECB10/13/2020No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix K3 of the 2014 nycbc. This is a controller feature which ensures passenger safety. Remedy : file application, install dlmNothing owed — awaiting certificate of correction
ECB10/21/2019Holes in boiler room walls. No boiler room access sign visable from front door of building. Correct violating conditions and submit a certificate of correction.Nothing owed — awaiting certificate of correction
ECB03/25/2019Failure to maintain exterior building walls and appurtenances. As noted at time of inspection i observed on EXP1 east elevation cracks in parapet stucco cracked terra cotta around several windows; damaged corroNothing owed — awaiting certificate of correction
ECB03/15/2017B265 as per class 2 (B265) 28-202.7 failure to file a complete boilerinspeciton as per DOB. Submit a current B09 report.Nothing owed — awaiting certificate of correction
ECB05/31/2011Failure to maintain exterior building wall. Defect is: cement stucco is cracked & spalling below roof north exposure 4 & front exposure 1,& section of cement stucco is cracked & missing at 4TH story south exposNothing owed — awaiting certificate of correction
ECB05/29/2001Work without a permit. Work noted: new interior partition partition, floor and ceiling being installed. Existing bumb waiter shaft not properly sealed at 1ST fl. Ne apt. Remedy: obtain permit from bldg. Dept.Nothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB06/20/2023Violation issued-failure to file 2019 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2025). This one is not shown as answered
DOB06/20/2023Violation issued-failure to file 2018 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2025). This one is not shown as answered
DOB04/06/2018Violation issued for failure to file annual boiler 2016 inspection reportThe owner has filed since: boiler inspection reports are on file for later years (latest 2025). This one is not shown as answered
DOB01/26/2018Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tstThe owner has filed since: Category 1 elevator reports are on file for later years (latest 2025). This one is not shown as answered
DOB02/24/2017Violation issued for failure to file annual boiler 2015 inspection reportThe owner has filed since: boiler inspection reports are on file for later years (latest 2025). This one is not shown as answered
Old · issued 3+ years ago and still listed by DOB; nothing on the city's records either way
DOB01/06/2021Failure to certify correction on immediately hazardous (class 1) ECB violationIssued 2021; DOB's record still lists it as active
DOB06/26/2019Failure to certify correction on immediately hazardous (class 1) ECB violationIssued 2019; DOB's record still lists it as active
DOB05/01/2019Facade safety program: facade (DOB violation)Issued 2019; DOB's record still lists it as active