HPD03/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST WALL IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT SOUTH WALL IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION AT HEAT RISER IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGE IN THE ENTRANCE LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING ANDALL WALLS IN THE PRIVATE HALLWAY LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE KITCHEN LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE AT HEAT RISER PIPE IN THE BATHROOM LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE COUNTER TOP AT SOUTH WALL IN THE KITCHEN LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING, NORTH AND SOUTH WALL IN THE FOYER LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD03/03/2026§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOORS TILES IN THE PRIVATE HALLWAY LOCATED AT APT 1J, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
HPD10/02/2025§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AT COMPACTOR DOOR AT PUBLIC HALL, 6th STORY
HPD04/22/2025§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST
HPD04/22/2025§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR TILE IN THE KITCHEN LOCATED AT APT 6K, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD04/22/2025§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW LOWER SASH SPRING BALANCE IN THE KITCHEN LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST
HPD08/17/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BASE CABINET DOORS AT NORTH WALL IN THE KITCHEN LOCATED AT APT 6K, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/17/2024§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE 1st BATHROOM FROM EAST AT SOUTH LOCATED AT APT 6K, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/17/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET AT EAST WALL IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 6K, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 17201819 ISSUED 17-AUG-24 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
HPD08/17/2024HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/17/2024§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET IN THE 1st BATHROOM FROM EAST AT SOUTH LOCATED AT APT 6K, 6th STORY, 2nd APARTMENT FROM NORTH AT EAST
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
DOB06/20/2023VIOLATION ISSUED-FAILURE TO FILE 2018 EXTERNAL LOW PRESSURE INSPECTION
HPD09/27/2021§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
HPD05/08/2019HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 4E, 4th STORY, 2nd APARTMENT FROM EAST AT SOUTH
DOB04/06/2018VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2016 INSPECTION REPORT
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
HPD01/23/2018§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ESCUTCHEON PLATE AT RISER IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST
HPD01/23/2018§ 27-2026 ADM CODE REPLACE THE BROKEN OR DEFECTIVE AND OR REGLAZE PORCELIN FINISH AT BATHTUB IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM NORTH AT EAST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB02/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/10/2015VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2014 INSPECTION/TEST
DOB06/10/2015VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2014 INSPECTION/TEST
DOB05/02/2015FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD09/22/2014§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM SOUTH AT WEST WALL IN THE FOYER LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT EAST
HPD09/22/2014§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM WEST AT NORTH WALL, 1st DOOR FRAME FROM WEST AT NORTH WALL, EAST WALL, WEST WALL IN THE BATHROOM LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT EAST
HPD09/22/2014§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING IN THE KITCHEN LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT EAST
HPD09/09/2014§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM WEST AT NORTH WALL, 1st DOOR FRAME FROM WEST AT NORTH WALL IN THE BATHROOM LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD09/09/2014§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM SOUTH AT WEST WALL, 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE FOYER LOCATED AT APT 5J, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
DOB05/01/2014FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/03/2012FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB04/21/2004V-DOB VIOLATION - ACTIVE
DOB05/17/1993V-DOB VIOLATION - ACTIVE
ECB03/11/2011FAILURE TO MAINTAIN EXTERIOR BLDG SOUTH ELEVATION EXP#4 OBSERVE LOOSE MASONRY BARKS WOOD STORED ON FACADE SILLS FLOWER POTS STORED ON FIRE ESCAPE LANDING AND BLOCKING PATHWAY STEP CRACKS AND DISPLACEMENT IN PARNothing owed — awaiting certificate of correction
ECB10/23/2009LOCAL LAW REPORT FILED AS UNSAFE BY ARCHITECT /ENGINEER NO AMENDED REPORT WAS FILED.UNSAFE CONDITIONS REQUIRE SAFETY PROVISIONS FOR THE PUBLIC AS PER 27-129(D)1 RCNY 32-03 (B)(5)(I)NO SIDEWALK SHED FENCE NETTINNothing owed — awaiting certificate of correction
ECB02/23/200585BB05/51H11/43H10/63M07/52B14Nothing owed — awaiting certificate of correction
ECB11/17/20035J1/10M11/11L10/25L6/25X10/16L10/34Q3 5J1=TOO MUCH GAP BETWEEN CAR DOOR AND CAR POST 10M11=REAR GIB 11L10=NO HOLD 25L6=TO CODE 25X10=RELOCATE PIPE TO RUN BOX 16L10=SLAMS 2 & 3 FLS 34Q3-UNDER CARNothing owed — awaiting certificate of correction
ECB11/17/20033M7/12M7/16L10/20Q3/25L6/28Q3/34Q3/39Y2/41G11/55Y14/60U15/60M7/83U15/85U5 3M7-CAPACITY PLATE 12M7-CAR TOP 16L10-SLAMS 2,4,5 & 6 FLS 25L6-SECURE TO CODE 34Q3=CAR TOP 41G11=#5 FUSE 60M7-CAMPANY NAME 83U15=TAG DEVNothing owed — awaiting certificate of correction
ECB10/03/1996FAILURE TO MAINTAIN THE INTERIOR FLOOR SUPPORT SYSTEM FOR APARTMENTS 1KX1L: HALLWAY X BATHROOM FLOORS ARE DROPPING BY APPROXIMATELY 3-4 INCHES. REMEDY: OBTAIN A PERMIT AND MAKE REPAIRS.Nothing owed — awaiting certificate of correction
ECB02/28/1996FAILURE TO MAINTAIN THEINTERIOR FLOOR SUPORT SYSTEM WITHIN APARTMENT 1K; EAST BATHROOM FLOORHAS DROPPED APPROX. 3' INCHES 1/8 HORIZONTAL CRACKS ALONG CORRIDOR AND BATHROOM WALL TO CEILING CONNECTION. ALSO APPRNothing owed — awaiting certificate of correction
ECB02/08/1996FAILURE TO MAINTAIN THE INTERIOR FLOOR OF APARTMENT 1I THE LIVING ROOM FLOOR AT THE NORTHEAST CORNER IS SAGGING BY APPROX 1-2 INCHES REMEDY OPEN THE DEFECTIVE AREA AND CALL FOR A DEPARTMENT OF BUILDINGS INSPECNothing owed — awaiting certificate of correction
ECB10/10/199514M,35P,57O,. 35 PROVIDE MEANS OF ACCESS IN ACCORDANCE WITH RS-18 RULE 101.3.Nothing owed — awaiting certificate of correction
ECB08/08/199114M,15C,35O,50Y,53M,40#,57O,40 PERFORM 5YR TEST AND PROPERLY TAGNothing owed — awaiting certificate of correction
ECB08/08/199173X,73 RESTORE TO SERVICE SO PROPER INSPECTION CAN BE MADE BY THIS DEPARTMENT.Nothing owed — awaiting certificate of correction