ECB08/16/2019AN UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER OF TEH COMMISSIONER FAILURE TO CORRECT AND CERTIFY SUMMONS #3537962N ISSUED ON 1-8-19 FOR BROKEN RACEWAY ON ROOF TOP COMPLY WITH EC CODE/OBTAIN PERMIT$12K due
DOB01/13/1997V-DOB VIOLATION - ACTIVE
ECB02/06/2026OBSERVED A POWERFLAME BURNER MODEL WCR3-G-20 SERIAL # 082287282 INSTALLED WITHOUT A PERMIT. OBTAIN THE PROPER PERMIT AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB01/11/2023FOUND POWERFLAME GAS FIRED BURNER MODEL # WCR3-G-20, SERIAL # 082287282 BEING INSTALLED WITHOUT A PERMIT ON A WEIL MCLAIN MODEL 1288 BOILER. OBTAIN THE PROPER PERMIT AND SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB12/08/2022CIRCULATOR LEAKING, NO FITTINGS/THREADS ON EXPANSION TANK RELIEF VALVE DISCHARGE PIPING TERMINATION, NO THREADS ON RELIEF PIPING TERMINATION FOR BACKFLOW PREVENTER. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT ANothing owed — awaiting certificate of correction
ECB12/08/2022OBSERVED ACTIVE WATER LEAK ON PUMP IN THE BOILER ROOM THAT IS LOCATED IN THE CELLAR. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATINGNothing owed — awaiting certificate of correction
ECB01/26/2022UNLAWFUL ACTS FAILURE TO COMPLY W/COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP WAS MADE TO CORRECT OR CERTIFY ECB #'S 35634552X & 35379762NREMEDY:COMPLY W/COMMISSIONER'S ORDERSNothing owed — awaiting certificate of correction
ECB01/11/2022I OBSERVED ACTIVE WATER LEAK AT THE EXPANSION TANK LOCATED IN THE BOILER ROOM AT CELLAR/BASEMENT LEVEL, BOILER #2 MISSING SITE GLASS AT REAR., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB11/04/2021UNLAWFUL ACTS.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.FAILURETO CORRECT & CERTIFY SUMMONS ECB#35423759H & ECB#35379762N.UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPNothing owed — awaiting certificate of correction
ECB10/15/2021AIR SEPERATOR LEAKING, NO FITTINGS/THREADS ON EXPANSION TANK RELIEF DISCHARGE PIPING TERMINATION.Nothing owed — awaiting certificate of correction
ECB08/04/2021AN UNLAWFUL ACT. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS #35346375M AND SUMMONS #35379762N. REMEDY: COMPLY WITH CODENothing owed — awaiting certificate of correction
ECB06/26/2021UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS #35379762N AND SUMMONS #35346375M. REMEDY: COMPLY WITH CODENothing owed — awaiting certificate of correction
ECB02/21/2020REMOVE THREADS ON RELIEF VALVE DISCHARGE PIPING FOR EXPANSION TANKS AND BACKFLOW PREVENTER, PLUG OR CAP OPEN VALVES, AUTOVENT LEAKING. RESOLVE VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB02/21/2020BOILER RELIEF VALVE LEAKING, REMOVE THREADS ON DISCHARGE PIPING FOR RELIEF ON EXPANSION TANKS AND BACKFLOW PREVENTER, AUTO VENT LEAKING, CAP OR PLUG ALL OPEN PIPING. RESOLVE VIOLATING CONDITIONS AND SUBMIT A CENothing owed — awaiting certificate of correction
ECB01/28/2020FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER- I OBSERVED NO BALL DRIP INSTALLED BETWEEN THE FIRE DEPARTMENT CONNECTION AND THE CHECK VALVE. AS PER BC 2014 4.8.2.2, REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB10/17/2019UNLAWFUL ACTS UNABLE TO COMPLY WITH AN ORDER OF THE COMMISSIONERS.RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT AND CERTIFU ECB#36379762N.REMEDY:COMPLY WITH COMMISSIONERS ORDERS.Nothing owed — awaiting certificate of correction
ECB06/24/2019UNLAWFUOL ACTS FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORDS INDICTE NO APPLICATION WAS MADE TO CORRECT AND CERTIFY REMOVALOF VIOLATION CONTAINED IN SUMMONS #35379762N. REMEDY:COMPLY WITHNothing owed — awaiting certificate of correction
ECB01/29/2019B254,15,32A,45A,50A,50B. WEIL MCLAIN BOILER MDL #1288: 50A-MOTORIZED LOUVER NOT OPERABLE; 50B-CIRCULATOR LEAKING WATER. RMDY: REPAIR VIOLATING CONDITIONS AND SUBMIT CERTIFICATE OF CORRECITON.Nothing owed — awaiting certificate of correction
ECB01/08/2019FAILURE TO PROVIDE (GFCI)GROUND FAULT CIRCUIT INTERRUPTER PROTECTION AS REQUIRED. OBSERVED RECEPTACLE OUTLET OF THE TGFCI TYPE IN OUTDOOR LOCATIONS ON ROOFTOP AREAS AND REAR COURTYARD. REMEDY:COMPLY WITHNothing owed — awaiting certificate of correction
ECB01/08/2019UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS DEVICES MATERIALS APPLIANCES OR WIRING IN USE. OBSERVED ON ROOFTOP ABOVE STAIRWAY "C" BROKEN RACEWAYS WITH EXPOSED ENERGIZED CONDUCTORS SUPPLIENothing owed — awaiting certificate of correction
ECB09/13/2018UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT AND CERTIFY REMOV AL OF VIOLATION CONTAINED IN SUMMONS #35346375M. RMDY: COMPLY WITH COMNothing owed — awaiting certificate of correction
ECB07/13/2018UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED ON ROOFTOP ABOVE STAIRWAY "C" BROKEN RACEWAYS IT UNSUPPORTED WITH EXPOSED, ENERGIZEDNothing owed — awaiting certificate of correction
ECB07/13/2018FAILURE TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS CABLE ASSEMBLIES/BOXES/CABINETS/FITTINGS.OBSERVED IN STAIRWELLS THROUGHOUT BLDG INSTALLATION OF EMERGENCY LIGHTS WITH RACEWAYS TERMINATEDNothing owed — awaiting certificate of correction
ECB01/23/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER; FAILURE TO COMPLY WITH LAW FOR DRAINAGE SYSTEM PER PC 702.1; 27-911. OBSERVED AT DIFFERENT LOCATIONS AROUND THE BUILDING ROOF LEADERS NOT TIED INTO THE DRANothing owed — awaiting certificate of correction
ECB07/17/2017ELECTRICAL WORK W/O A PERMIT. OBSERVED NEW PANELS AND JUNCTION BOXES THROUGHOUT HALLS. ALSO NOTED EXISTING PANELS DISCONNECTED, AND REMOVEDOBSERVED IN ELECTRICAL CLOSETS IN CORRIDORS. ALS NOTED NEW PANELS ANDNothing owed — awaiting certificate of correction
ECB07/17/2017UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT, MATERIALS APPARATUSDEVICE APPLIANCE OR WIRING IN USE. OBSERVED EXPOSED ENERGEIZED WIRES ON ROOFTOP AS WELL AS LIGHT FIXTURES, USED AS RACEWAYS THROUGHOUT BLDGNothing owed — awaiting certificate of correction
ECB07/17/2017FAILURE TO PAINT DEDICATED SPRINKLER PIPING/VALUES IN ACCORDANCE WITH SECTION. OBSERVED IN BOILER ROOM UNPAINTED FIRE SPRINKLER MAIN PIPING.REM: PAINT DEDICATED SPRINKLER PIPING/VALUES AS PER SECTION REQUIREMENNothing owed — awaiting certificate of correction
ECB07/17/2017FAILURE TO PROVIDE (GFCI) GROUND FAULT CIRCUIT INTERRUPTER PROTECTION AS REQUIRED. OBSERVED RECEPTACLE OUTLETS NOT OF THE GFCI. TYPE IN WET LOCATION AREAS AS REQUIRED IN LAUNDRY ROOM, BOILER ROOM, AND OUTSIDENothing owed — awaiting certificate of correction
ECB01/18/2017FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION I OBSERVED ON THE FIRST FLOOR OF THE BLDG TWO FIRE DEPT CHECK VALVES AND THE PIPING FROM THE FIRE DEPT CONNECTION TO THE CHECK VALVES W/NNothing owed — awaiting certificate of correction
ECB01/18/2017FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION I OBSERVED IN THE CELLAR NO TEST TEE INSTALLED ON THE WATER SERVICETO THE BLDG. (DOMESTIC/POTABLE) PER 603.3 OF NY CPC. RMDY: REPAIR AND/Nothing owed — awaiting certificate of correction
ECB10/26/2016FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER, REINSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC102.3; 27-902. @ TIME OF INSP, 1:16PM, ON 10/26/16 @ THE ABOVE PLACE OF OCCURENCE ADDRESS I OBSERNothing owed — awaiting certificate of correction