ECB04/06/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR SUMMONS 39143636R., FILE A CERTIFICATE OF CORRECTION$6K due
ECB12/29/2025OBSERVED ON FLOORS 2 THROUGH 6 OPEN WASTE LINES IN STORAGE ROOMS. FIFTH FLOOR HAS PVC WASTE LINE . IN THE BASEMENT, WASTE AND SPRINKLER LINES PENETRATE WALLS AND CEILINGS WITHOUT FIRE STOPPING; TOILETS IN BATHR$1K due
ECB12/29/2025CLASS 2: EMERGENCY PHONE INOPERATIVE, PROVIDE 2 WAY COMMUNICATION SERVICE. IN-CAR CITY ID TAG MISSING, PROVIDE. REPAIR OIL LEAKING PISTON SEAL.$625 due
ECB12/29/2025OBSERVED IN BASEMENT SPRINKLER HEADS ARE OBSTRUCTED BY LIGHT FIXTURES AND IMPROPERLY INSTALLED. DRAIN LINE CLOGGED. WATER LINES RUN THROUGH THE ELECTRICAL ROOM, AND E BIKE, GASOLINE AND SNOW BLOWER ARE STORED I$1K due
ECB12/29/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1 (2014 CODE); 27-542; BC 1008.2 (2022). OBSERVED PAPER EXIT SIGN AT$2K due
ECB12/29/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ELECTRICAL BIKE AND GAS POWERED SNOW BLOWER STORED AT BASEMENT LEVEL. POTENTIAL FIRE HAZARDS., REPAIR AND/REPLACE$2K due
ECB04/02/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLD PENETRATIONS ON 2ND FLOOR HALLWAY AREA BETWEEN APT 2B AND 2C. ALSO$2K due
DOB11/13/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB08/07/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB07/25/2024CATEGORY 1 TEST TAG EXPIRED. ADJUST CAR DOOR PROPERLY TO FULLY OPEN. IN-CAR COMMUNICATION INOPERATIVE.$625 due
DOB03/20/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB09/02/2020FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
ECB09/09/2025REISSUE: 35688646N DATE OF ISSUE: 09-20-2025. EXIT DOOR NOT SELF-CLOSING PROPERLY. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 4TH FL. STAIRWAY "A" 1 EXIT DOOR, 2ND FL. STAIRWAY "B" 1 EXIT DOOR, 1ST FLOOR SNothing owed — awaiting certificate of correction
ECB09/20/2024REISSUE#356721175L-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED NUMEROUS FIREPROOF SELF-CLOSING DOORS AT VARIOUS LOCATIONS THAT ARE NOT CLOSING PROPERLY DUE TO DILAPIDATED DOOR FRAME ANDNothing owed — awaiting certificate of correction
ECB08/28/2024EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION.AT FIRSTFLOOR MULTIPURPUS ROOM MAIN ENTRANCE TWO EXIT DOORS AND 4TH FLOOR STAIR A ONE EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION.Nothing owed — awaiting certificate of correction
ECB06/03/2024RESPONDING TO A 311 COMPLANT UPON INSPECTION OF ONE DEVICE IN THE BUILDING ONLY ELEVATOR IN BUILDING WAS OUT OF SERVICE CREATING HAZARDOUS CONDITION AS PER1RCNY 11-02 IN A 7 STORY BUILDING. REMEDY; RESTORE TO SNothing owed — awaiting certificate of correction
ECB05/15/2024ONLY ELEVATOR IN THE BUILDING OUT OF SERVICE. RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDOB. AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB01/08/2024ELEVATOR CURRENTLY OUT OF SERVICE IN THE BASEMENT; RESTORE TO SERVICENothing owed — awaiting certificate of correction
ECB10/31/2023I OBSERVED IN THE REAR OF THE BUILDING A SUMP PUMP SITTING IN THE DRAIN PLUGGED INTO AN EXTENSION CORD WRAPPED IN PLASTIC AND PASSING THROUGH THE WALL, THEN SPLICED TO AN ORANGE EXTENSION CORD TO SUPPLY POWER WNothing owed — awaiting certificate of correction
ECB10/31/2023I OBSERVED IN THE BASEMENT BATHROOM AND THE MAIN ELECTRICAL ROOM FAILURE TO PROVIDE GFCI PROTECTION AS REQUIRED AS CODE. PHOTOS TAKEN., INSTALL GFC1 PROTECTION; PROVIDE GFCI OR GFCI PROTECTION.Nothing owed — awaiting certificate of correction
ECB08/29/2023EMERGENCY EXIT DOORS DID NOT SELF-CLOSE AND LATCH, LOCATED AT ROOF LEVEL, STAIRCASE, (2&3) AND DOOR KNOB HARDWARE WAS REMOVED LEAVING THE FPSC DOOR UN-FIRERATED, REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB08/29/2023ROOF BUBBLING WAS FOUND THROUGHOUT THE ROOF AS NOTED IN PAST OATH/ECB VIOLATIONS, (SERVED 02/09/2022 VIO NO.39055802N & 09/28/2021 VIO NO.39048345L)., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB02/09/2022LAYERS OF THE ROOF ARE SEPARATING & CRACKING, PUFFING UP LIKE A LARGE BALLOONS ALL OVER ROOF, LETTING WATER INTO STAIRCASE 1 ON THE 5TH FLOOR FROM THE ROOF DURING RAIN. PATCHING HAS BEEN DONE IN A FEW AREAS WATNothing owed — awaiting certificate of correction
ECB09/28/2021LAYERS OF THE ROOF ARE SEPARATING AND CRACKING, PUFFING UP LIKE A LARGE BALLOONS ALL OVER ROOF, LETTING WATER UNDER 1ST LAYER OF THE ROOF. PATCHING HAS BEEN DONE IN A FEW AREAS., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB02/13/2020NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL DLM AND, PERFORM AND FILE TEST WITH NYCDOB.Nothing owed — awaiting certificate of correction
ECB05/02/201836,50A,50B,50C,50D-AS PER CLASS 2(B254) 28-301.1. FAILURE TO MAINTAIN. 36)BOILER NOT REGISTERED. 50A)NO MANUAL RESET LOW WATER CUT-OFF INSTALLED. 50B)NO SPILL SWITCH INSTALLED. 50C)FLUE PIPING NOT SEALED AT CONNothing owed — awaiting certificate of correction