ECB07/23/2026NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 FAILURE-TO-MAINTAIN VIOLATION #39145007N ISSUED 4/15/2025 CITING HOLE PENETRATIONS THROUGHOUT THE BUILDING. AT INSPECTION, FIRESTOPPING HAD BEEN NEWLY INSTALLED$1K due
ECB01/02/2026OBSERVED ON THE ROOF, SIX FLOOR AND BASEMENT LACK FIRESTOPPING AT PENETRATIONS THROUGH WALLS FOR PIPE LINES. ON THE 11 TH FLOOR STAIRCASE STANDPIPE CAP IS OBSTRUCTED BY ELECTRICAL LINE. ON FLOORS 11, 6,7,8,9 SP$1K due
ECB01/02/2026OBSERVED ON THE 9TH AND 7TH FLOOR SINKS NOT OPERATIONAL. ON THE SIX FLOOR DRINKING FOUNTAIN DRAIN IS NOT INSTALLED PROPERLY. FIRST FLOOR BASEMENT USING PLASTIC CAPS ON STANDPIPE. FIRE PUMP ROOM INSTALLED PIPING$1K due
ECB12/30/2025CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION$1K due
HPD03/31/2024§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTIRE APARTMENT LOCATED AT APT 418, 4th STORY, 5th APARTMENT FROM EAST AT SOUTH
HPD01/08/2024HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES AT COMMUNITY BATHROOM, 4th STORY
DOB02/22/2022FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
ECB04/15/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATIONS THROUGHOUT THE BUILDING. POTENTIAL FIRE HAZARD., PROVINothing owed — awaiting certificate of correction
ECB04/15/2025CLASS 2 ITEMS: CATEGORY 1 TEST TAG EXPIRED. CLEAN ENTIRE PIT AREA.Nothing owed — awaiting certificate of correction
ECB04/14/2025FOUND A ROCKMILL MP125 STEAM BOILER SLIGHT LEAK FROM INSIDE THE BOILER/FRESH AIR FAN PROVING SWICTH NOT WORKING PROPELY/ SAFETEY VALVE DRAINTERMINATION TIED TOGETHER AND WITH THREADS AT THE END/BODY DRAIN MISSINothing owed — awaiting certificate of correction
ECB04/14/2025FOUND ON SITE A TEMPORARY OIL TANK OUTSIDE PERMIT #M00807169-LA NOT SIGNED OF. PERMIT FILLING UNDER PENALTY REVIEW., MAINTAIN BOILER; CORRECT ALL VIOLATING CONDITION/ SUBMIT CERIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB01/16/2024AS PER PROVISION OF LAW 28-301.1. FAILURE TO MAINTAIN PLUMBING SYSTEM. FOUND LAVATORY WASTE ON 4TH FL. WOMEN'S ROOM LEAKING AND FAWCETT LOOSE AS PER P.C. 702.1 AND 602.3., REMOVE NON-COMPLYING MATERIAL OR EQUIPNothing owed — awaiting certificate of correction
ECB01/13/2023FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #906681.REMEDY:SUBMIT ACCEPTABLE REQUIRED TENothing owed — awaiting certificate of correction
ECB01/05/2023I OBSERVED IN VARIOUS RESTROOMS AND THE KITCHENS ON FLOORS 4 THROUGH 10 DEFECTIVE, MISWIRED, GFCI OUTLETS, ALSO NOTED IN THE KITCHEN THE OUTLET BOX DISCONNECTED AND UNSECURED., INSTALL GFC1 PROTECTION; PROPERLYNothing owed — awaiting certificate of correction
ECB01/05/2023OBSERVED: AT EXPOSURE #1&4,EXIT DOORS, ROOF LEVEL EXIT DOOR AND ELEVATOR ROOM DOOR, DO NO SELF-CLOSING PROPERLY DUE OVERLAPPING DOOR LEAVES, OR SELF CLOSING SYSTEM., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB01/05/2023I OBSERVED IN THE BASEMENT AREA NEAR THE ELECTRICAL ROOM ROMEX WIRING PASSING THROUGH A WALL SUPPLYING POWER TO A FAN IN A STORAGE CLOSET, ALSO NOTED A DEFECTIVE FLEXIBLE CORD PASSING AROUND A DOORWAY,ALSO NOTENothing owed — awaiting certificate of correction
ECB01/05/2023I OBSERVED IN THE CORRIDORS ON ALL FLOORS, FAILURE TO PROPERLY TERMINATE THE RACEWAYS SUPPLYING POWER TO THE CEILING LIGHTS AND EMERGENCY LIGHTING THE WIREMOLD RACEWAYS ARE NOT MECHANICALLY CONNECTED AS REQUIRENothing owed — awaiting certificate of correction
ECB01/05/2023OBSERVED: AT ROOF LEVEL, ELEVATOR ROOM, VARIOUS OPENINGS DUE TO PENETRATION OF PIPES THROUGH WALLS, WALL DAMAGE WITHOUT FIRE STOPPING PROVIDED., PROVIDE/MAINTAIN FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB05/25/2022AT CELLAR LEVEL, UTILITY ROOM, VARIOUS OPENINGS DUE TO PENETRATION OF PIPES THROUGH CEILINGS AND WALLS WITHOUT FIRE STOPPING PROVIDED, PROVIDE/MAINTAIN FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB05/25/2022AT 6TH/5TH FL, CORRIDORS AND STAIRCASE A&B WITHOUT EMERGENCY LIGHTS INTALLED. ALSO, AT 5TH FL STAIR B & 6TH FL FRONT ELEVATOR, EXISTING EMERGENCY LIGHTS WERE NOT OPERATIONAL WHEN TESTED, REPAIR/REPLACE LIGHTINGNothing owed — awaiting certificate of correction
ECB05/25/2022AT EXPOSURE #1&2,EXIT DOORS DO NO SELF-CLOSING PROPERLY DUE OVERLAPPING DOOR LEAVES, OR MISSING SELF CLOSING SYSTEM., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB05/25/2022AT 6TH/5TH FL, STAIRCASE B METAL STAIR WITH DETERIORATED AND BROKEN STEPS, REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB10/28/2021I OBSERVED IN THE GAS METER ROOM LOCATED IN THE BASEMENT CRACKED AND ALSO BROKEN CAST IRON SANITARY PIPING AND FITTINGS., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/06/2021PUMP LEAKING . CORRECT VIOLATING CONDITION & SUBMIT A CERTIFICATE OF CORRECTION.Nothing owed — awaiting certificate of correction
ECB05/31/2018FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 5/31/18AT ABOVE ADDRESS. NO ADEQUATE VENTILATION IN GAS METER ROOM. RMDY: REPAIR AND OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/31/2018ELECTRICAL WORK W/O A PERMIT. I OBSERVED IN THE MAIN ELECTRICAL ROOM IN THE BASEMENT THE INSTALLATION OF A FIRE PUMP SERVICE SWITCH AND ON THE 4TH AND 9TH FLOOR THE RETROFIT OF EXISTING ELECTRICAL PANELS WITHNothing owed — awaiting certificate of correction
ECB05/31/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT ROOF IN WATERTOWER ROOM,BRICK COLUMN NEXT TO WATER TANK HAS LOOSE BRICKS,CRACKED BRICKS AND ENTIRE COLUMN DETACHED FROM WALL.REM:REPAIR AND/OR REPLACE CONothing owed — awaiting certificate of correction
ECB05/31/2018I OBSERVED IN THE WATER METER ROOM. THE GROUNDING ELECTRODE CONDUCTOR EXTREMELY DETERIORATED AT THE CONNECTION ON THE WATER PIPE. PHOTOS TAKEN. RMDY: PROVIDE PROPER CLEAN CONNECTION ON THE WATER PIPE AS PERNothing owed — awaiting certificate of correction
ECB05/31/2018I OBSERVED ON THE ROOF AT STAIR BA AND INSIDE THE 5TH AND 6TH FLOOR JANITORIAL CLOSETS; RACEWAYS NOT SUPPORTED AND SUBJECTED TO DAMAGE. PHOTOS TAKEN. RMDY: PROVIDE PROPER SUPPORT OF RACEWAYS.Nothing owed — awaiting certificate of correction
ECB08/18/2017OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.C OF O #77527 INDICATES 5TH-9TH STORIES TO BE 35 BEDROOMS;WASH ROOM;TOILETS & SHOWER ROOMS. NOTED: ON 5TH FL ROOM 505 IS OCCUPIED AS OFFICENothing owed — awaiting certificate of correction
ECB04/05/2016OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS CERTIFICATE OF OCCUPANCY #M77527 INDICATES 5TH THROUGH 9TH FLRS TO BE 35 BEDROOMS; WASHROOMS, TOILET AND SHOWER ROOMNothing owed — awaiting certificate of correction