DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB06/21/2021V-DOB VIOLATION - ACTIVE
DOB06/22/2020V-DOB VIOLATION - ACTIVE
DOB06/26/2019V-DOB VIOLATION - ACTIVE
DOB04/05/2019VIOLATION ISSUED TO ELEVATOR - FAILURE TO FILE CATEGORY 1 2017 INSPECTION/TEST
DOB06/19/2018V-DOB VIOLATION - ACTIVE
DOB09/15/2017VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2016 INSPECTION/TEST
DOB06/15/2017V-DOB VIOLATION - ACTIVE
DOB12/01/2016VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2015 INSPECTION/TEST
DOB06/21/2016V-DOB VIOLATION - ACTIVE
DOB11/20/2015VW-VIOLATION WORK WITHOUT PERMIT - ACTIVE
DOB06/10/2015VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2014 INSPECTION/TEST
DOB10/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2013 INSPECTION/TEST
DOB10/21/2014RETURN TO SERVICE OR FILE FOR PERMIT TO DISMANTEL
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
DOB09/10/2013VW-VIOLATION WORK WITHOUT PERMIT - ACTIVE
DOB10/01/2012VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2011 INSPECTION/TEST
DOB03/02/2012V-DOB VIOLATION - ACTIVE
DOB12/13/2011VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
DOB03/24/2011V-DOB VIOLATION - ACTIVE
DOB10/08/2010V-DOB VIOLATION - ACTIVE
DOB07/23/2010VW-VIOLATION WORK WITHOUT PERMIT - ACTIVE
DOB02/27/2009V-DOB VIOLATION - ACTIVE
DOB03/21/2008V-DOB VIOLATION - ACTIVE
DOB04/02/2007V-DOB VIOLATION - ACTIVE
DOB11/28/2006V-DOB VIOLATION - ACTIVE
DOB02/25/2004V-DOB VIOLATION - ACTIVE
DOB01/13/1997V-DOB VIOLATION - ACTIVE
ECB04/30/2026RE-ISSUE #35725194N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: ON THE 4TH FLOOR RM #S 462, 483, 487, 409 ALL HAVE KICK-STOPNothing owed — awaiting certificate of correction
ECB04/30/2026RE-ISSUE #35725195P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PERBC 1006.1; 27-381. NOTED: EMERGENCY LIGHTS WERE NOT OPERATIONAL AT THENothing owed — awaiting certificate of correction
ECB04/30/2026RE-ISSUE 35725192J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: IN GAS METER ROOM THERE ARE STEP CRACKS APPROX: 10-12 ON CMU BLOCKS ALSO SECTION OF CMU BLOCKS WERE REMOVED SO PIPE COULD FIT. ENothing owed — awaiting certificate of correction
ECB04/30/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE-STOPPING PER BC 712.3; 27-345. NOTED: IN ELECTRIC METER ROOM, FIRE-STOPPING IS MISSING AROUND PIPES THAT GO THRU CMU BLOCKS ABOVE THE DOOR. REMEDY:Nothing owed — awaiting certificate of correction
ECB04/30/2026RE-ISSUE #35725193L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FIRE-PROOF INTERIOR DOORS DO NOT SELF-CLOSE PROPERLY AT 4TH FLR-STAIRCASE "A" AND "B". 3RD FLR-STAIRCASE "A" AND "B". 2ND FLR-SNothing owed — awaiting certificate of correction
ECB04/30/202628-301.1. RE-ISSUE #35725196R. UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 20% PER FDNY 2008 CODE; FC 803.3.2. NOTED: OBSERVED BANNERS IN CORRIDORS NEAR RM #387,2MD FLR-ARTWORK HANGING IN RM #251, BANNothing owed — awaiting certificate of correction
ECB09/03/2025REISSUE#35683046Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.DOOR BROKEN OR NOT SELF-CLOSING.GLASS DOORS AT EXIT 13,14,15 DO NOT CLOSE,DOORS AT ROOM 268,409E AND 409H & B DOORS DO NOT CLOSE MISSING HNothing owed — awaiting certificate of correction
ECB09/03/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J).NOTED:DURING INSPECTION OBSERVED KICK STOPS ON CLASSROOM DOORS AT 4TH FL,R-467,464.REM:PROVNothing owed — awaiting certificate of correction
ECB09/03/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED DURING TIME OF INSPECTION OBSERVED EMERGENCY LIGHT DOES NOT TURN ON WHNothing owed — awaiting certificate of correction
ECB09/03/202528-301.1 UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 20% PER FDNY 2008 CODE;FC 803.3.2.NOTED:DURING INSPECTION OBSERVED HANGING BANNERS NEAR ROOM 363 ON 3RD FLR AND IN 3RD FLR CLASSROOM RM#365 THERE WNothing owed — awaiting certificate of correction
ECB09/03/2025REISSUE#35683047K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.CELLAR LEVEL GAS METER ROOM,ELECTRICAL ROOM,STEP CRACKS IN WALL SECTION OF BLOCK CMU MISSING,FIRE STOP NOT DONE IN SOME AREA AND BOILER RONothing owed — awaiting certificate of correction
ECB09/24/2024REISSUE 35673035Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. DOOR BROKEN OR NOT SELF-CLOSING. GLASS DOORS AT EXIT 13, 14, 15 DON'T CLOSE, DOORS AT ROOM 268, 409E, AND 409H AND B DOORS DON'T CLOSE MNothing owed — awaiting certificate of correction
ECB09/24/2024FAILURE TO MAINTAIN BUILDING IN OCDE-COMPLIANT MANNER. CELLAR LEVEL GAS METER ROOM, ELECTRICAL ROOM STEP CRACKS IN WALL SECTION OF BLOCK CMUMISSING, FIRESTOP NOT DONE IN SOME AREA AND BOILER ROOM METAL GRATES HNothing owed — awaiting certificate of correction
ECB07/26/2024IN CAR PHONE NOT WORKING.Nothing owed — awaiting certificate of correction
ECB07/26/2024DEVICE WAS REMOVED AND HAS A ACTIVE STATUS ON BIS.Nothing owed — awaiting certificate of correction
ECB06/03/2024FOUND KEWANEE BOILER WITH MISSING DOG BOLTS ON BOILER DOORS, SAFETY RELIEF VALVES MISSING PULL CHAINS.Nothing owed — awaiting certificate of correction
ECB05/28/2024FOUND KEWANEE BOILER WITH MISSING DOG BOLTS ON BOILER DOORS, SMOKE ALARM ON BREECHING NOT OPERABLE AND WIRING EXPOSED, FITTING ON SIDE OF BOILER CORRODED.Nothing owed — awaiting certificate of correction
ECB05/10/2023REISSUE#35663127M-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTE:OBSERVED AT VARIOUS LOCATIONS OF THE OCCUPIED SCHOOL BUILDING,INTERIOR EXIT & EXIT ACCESS DOORS EXPLICITLY AT ROOM 409E,387,389,312,SNothing owed — awaiting certificate of correction
ECB06/23/2022REISSUE#35584197M.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED ALUMINUM SMOKE DOORS AT EXITS 13,14,15;CORRIDOR DOORSBY EXIT 4 NEXT TO ROOM 268,BY ROOM 251 ARE NOT SELF-CLOSING.DOORS ARENothing owed — awaiting certificate of correction
ECB03/29/2022FOUND EXPOSED WIRING, PULL CHAIN MISSING ON SAFETY RELIEF VALVE, GLASS GAUGE GUARDS MISSING, BOLTS AND LATCHES MISSING ON BOILER DOORS.Nothing owed — awaiting certificate of correction
ECB07/27/2021REISSUED#35502123H FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: ALUMIUM SMOKE DOORS AT EXIT 13,14&15 WERE NOT SELF CLOSING DUE TO DEFECTIVE HARDWARE. REMEDY: REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/17/2020FAILURE TO MAINTAIN BUIDLING IN CODE COMPLIANT MANNER NOTED OBSERVED ALUMINUM SMOKE DOORS AT EXIT 14 AND 15 WERE NOT SELF CLSOING DUE TO DEFECTIVE HARDWARE REPAIR AND OR REPLACENothing owed — awaiting certificate of correction
ECB06/01/199373X RESTORE ELEVATOR SERVICE SO PROPER INSPECTION CAN BE MADE BY THIS DEPT OR REMOVE SAME DEVICE AND FILE WITH THIS DEPT FOR REMOVAL PERMITNothing owed — awaiting certificate of correction