DOB02/24/2010V-DOB VIOLATION - ACTIVE
ECB02/06/2026OBSERVED ON THE GROUND FLOOR SPRINKLER HEAD OBSTRUCTED ALSO NO FIRE STOP PROTECTION AROUND PIPE PENETRATION. WATER FOUNTAIN AND WASTE LINE GOING THROUGH ELECTRICAL ROOM WHICH IS CONTRARY TO CODE SECTIONS EC 110Nothing owed — awaiting certificate of correction
ECB02/06/2026OBSERVED NOT HAVING PROPER GAS APPLIANCE SHUT OFF VALVES FOR COOKING EQUIPMENT AND HOT WATER HEATERS. VENTS TO HOT WATER HEATER EXHAUST AND GAS DRYERS NOT USING THE PROPER MATERIAL. USING PVC WASTE LINES FOR WANothing owed — awaiting certificate of correction
ECB02/06/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. DETECTED GAS LEAK AT BOILER ROOM. LOCATED ON FIRST FLOOR., REPAIR AND/REPLACENothing owed — awaiting certificate of correction
ECB10/15/2021DRAFT IND.CANNOT RUN CONTINOUS MUST BE NTERLOCKED ,AND COMBUSTION AIR FAN TO BE INTERLOCKED,THIS IS A WATER HTR WITH H STAMPNothing owed — awaiting certificate of correction
ECB10/15/2021GAS LINE TO REGULATOR TO BE HARD PIPED,FLUEPIPE TO BE WELDED (FEDERAL BLR) REMOVE STOPPER ON BAROMETRIC DAMPER ,INTER LOCK COMB AIR FAN,CORRECT VIOLATION AND SEND IN CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB07/24/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: FAILURE TO COM PLY WITH LAW FOR DRAINAGE SYSTEM PER PC 702.1: 27-911. OBSERVED ON 7/24/18 AT ABOVE ADDRESS SINK IN THE MAINTENANCE ROOM BEING DRAINED INNothing owed — awaiting certificate of correction
ECB07/11/201824B,50A,50B,50C-AO SMITH MODEL HW1340 LP HOT WATER BOILER. 50A)MISSING MANUAL RESET LOW WATER CUT-OFF. 50B)FRESH AIR FAN NOT INTERLOCKED WITH BOILER. 50C)TERMINATION OF CHIMNEY TO BE AT LEAST 3FT AWAY FROM FRESNothing owed — awaiting certificate of correction
ECB08/18/2017FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35272426Y ISSUED ON 07-11-17 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01.FOR WORK W/O PERMIT AT LAUNDRNothing owed — awaiting certificate of correction
ECB07/11/2017WORK W/OUT A PERMIT. OBSERVED IN LAUNDRY ROOM ON MAIN FLR (1 STORY) GAS PLUMBING CONNECTIONS MADE TO DRYERS W/OUT PERMIT. PHOTOS TAKEN. REM: OBTAIN ALL REQUIRED PERMITS.Nothing owed — awaiting certificate of correction
ECB07/11/2017FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED FROM DOB RECORDS THAT NO TEST WAS PERFORMED ON PLUMBING GAS CONNECTIONS MADE TO DRYERS IN LAUNDRY ON MAIN FLR. PHOTO TAKEN. REM: PERFORM TEST.Nothing owed — awaiting certificate of correction
ECB01/13/2017RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPEMTN. AT TIME OF MY INSPECTION I OBSERVED IN THE LAUNDRY ROOM COMMERCIAL GAS FIRED DRYERS BEINGSUPPLIED GAS WITH FLEXIBLE RESIDENTIAL GAS HOSES.PHOTO TAKEN.RMDY:COMNothing owed — awaiting certificate of correction