DOB11/14/2025Violation issued-failure to file 2024 external low pressure inspection2 identical filings
ECB03/17/2026Reissue on ECB #35724755J. Failure to maintain building in code-compliant manner. Noted: fire rated smoke doors and classrooms not self-closing due to missing hardware binding or faulty hardware on smoke door bNothing owed — awaiting certificate of correction
ECB03/17/2026Failure to maintain building in code-compliant manner. Noted: storage of janitorial carts and products, combustible materials(cardboard) andmiscellaneous items in small electrical switch gear, rooms on the 5THNothing owed — awaiting certificate of correction
ECB03/17/2026Exit door not self-closing. Noted: emergency exit exterior doors not self-closing due to faulty hardware or door binding on exterior door exit 8 1ST floor exterior door from cafeteria 1ST floor, exterior door sNothing owed — awaiting certificate of correction
ECB03/17/2026Failure to maintain building in code-compliant manner. Noted: verticalstep crack on building roof chimney and a deteriorating roof coping stone with spalling concrete and portions missing. Remedy: repair and/orNothing owed — awaiting certificate of correction
ECB03/17/202628-301.1. Reissue on ECB #35724754H. Failure to provide ventilation togas meter room per P115.6(1968 code) fgc appendix e(E4)(2014 code). Noted: observed in the old portion of building cellar level in gas meterNothing owed — awaiting certificate of correction
ECB03/17/2026Failure to maintain building in code-compliant manner. Illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. Noted: emergency illumination discharges not operating upon testing onNothing owed — awaiting certificate of correction
ECB03/17/202628-301.1. Unlawful placement of furnishings, decorations or other objects at exit that obstruct access to egress from or visibilty the roof per FDNY 2008 code; fc 1027.4. Noted: stair b 3RD floor behind emergenNothing owed — awaiting certificate of correction
ECB10/22/2025Failure to maintain building in code-compliant manenr. Noted: observedin original school side, classroom fireproof self-closing doors, are not self-closing due to missing door check/hardware. Remedy: repair andNothing owed — awaiting certificate of correction
ECB10/22/202528-301.1. Reissue #35679007Y 3/29/24. Failure to provide ventilation to gas meter room per P115.6. Noted: observed at time of inspection in original school basement gas meter room/crawl space no ventilation supNothing owed — awaiting certificate of correction