ECB12/23/2025Observed obstructed sprinkler heads throughout the building, missing insulation on bathroom traps, lack of firestopping around sprinkler line on the 6TH floor stairwell a , and a leaking sink waste line on fistNothing owed — awaiting certificate of correction
ECB12/23/2025Found a o smith (model#hw 670) gas fired boiler not registered correct violating condition submit certificate of correctionNothing owed — awaiting certificate of correction
ECB12/23/2025Found weil mclain(model# 588) dual fuel boiler not registered, correct violating condition submit certificate of correctionNothing owed — awaiting certificate of correction
ECB12/23/2025Observed in basement damaged sprinkler head; the door opens into sprinkler line, and the drain line is in the dedicated electrical room which contrary to code section bc 101.4.5, repair and/or replaceNothing owed — awaiting certificate of correction
ECB12/23/2025Found weil mclain(model# 588 dual fuel boiler not registered correct violating condition submit certificate of correctionNothing owed — awaiting certificate of correction
ECB01/11/2023As per one natural gas burning, hot water boiler model 588 series 1, boiler no. 100473-01. Boiler not registered as per DOB records; register boiler and call for an inspection.Nothing owed — awaiting certificate of correction
ECB01/11/2023As per one natural gas burning, ao smith domestic hot water boiler. Model no. Hw-670 200, serial no. 1937M000013; boiler not registered as per DOB records.Nothing owed — awaiting certificate of correction
ECB01/11/2023As per one, natural gas burning, weil mclain, hot water boiler, model 588 series 1, boiler no. 100473-02; boiler not registered as per DOB records; register boiler and call for an inspection.Nothing owed — awaiting certificate of correction
ECB12/08/2022Observed: at second floor, terrace, concrete tiles are split /cracked and deteriorated., repair and/or replaceNothing owed — awaiting certificate of correction
ECB12/08/2022Observed: from first floor to 6TH floor, mechanical room, gas meter/generator rms, exposed steel structure (columns, girders, trusses, beams,) is requirements for structural members and assemblies to be fire prNothing owed — awaiting certificate of correction
ECB12/13/2021Noted: observed pipes and electrical conduits penetrating through each floor and ceiling within all ac rooms with no fire stopping provided., provide/maintain fire stoppingNothing owed — awaiting certificate of correction
ECB05/18/2018Failure to maintain building in code compliant manner. No fire stopping per bc 712.3 27-345. Noted: at cellar level section of wall missing above door and holes in ceiling and walls. That were not fire stoppedNothing owed — awaiting certificate of correction
ECB04/27/2018Failure to maintain building code compliant manner. I observed in cellar gas meter and gas piping installed in the same room as the firepump which is contrary to the requirements of the nfpa as adopted byNothing owed — awaiting certificate of correction
ECB08/31/2017404.1 gas piping prohibited location-fire pump room.observed on 8/31/17 at above address gas meter is located in teh fire pump room. Remedy:comply with summons.Nothing owed — awaiting certificate of correction
ECB03/21/2017Gas piping in a prohibited location-fire pump room observed on 3/21/17GAS piping installed in fire pump room. Rmdy: comply with summons. Photos taken.Nothing owed — awaiting certificate of correction