HPD10/25/2017§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION ACOUSTIC CEILING ENTIRE STORY LOCATED AT DORMITORY 501, 5th STORY
HPD10/25/2017§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION ACOUSTIC CEILING , 1st STORY
HPD10/25/2017§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION ACOUSTIC CEILING , 2nd STORY
HPD10/25/2017§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION ACOUSTIC CEILING ENTIRE STORY , 5th STORY
DOB08/21/1991VP-VIOLATION UNSERVED ECB-ACTIVE
ECB12/24/2025OBSERVED ON THE THIRD FLOOR IN STAIRCASE A SPRINKLER HEAD IS DAMAGED AND ON THE FIRST FLOOR SPRINKLER HEAD CAP IS PAINTED TO CELLING. IN BASEMENT SPRINKLER MAIN VALVE AND WATER MAIN VALVE NOT ACCESSIBLE. ALSO TNothing owed — awaiting certificate of correction
ECB12/24/2025ON 5TH FLOOR INSTALLED NEW PIPING FOR SHOWER AND SINKS IN BATHROOM 95 PERCENT WORK COMPLETED NO PLUMBING PERMIT ON FILE, OBTAIN ALL PERMITSNothing owed — awaiting certificate of correction
ECB03/25/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED AC INSTALLED INTO WALL AT 1ST FLOOR AND BASEMENT AND HOLE PENETRATIONS TNothing owed — awaiting certificate of correction
ECB03/25/2025UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED FLAMMABLE CONTAINERS IN FIRE PUMP ROOM. (CAR ANTI FREEZE, DIESEL FUEL, POWER STEERING FUEL), MAINTAIN STORAGE IN COMPLIANCE WITH FIRE CODENothing owed — awaiting certificate of correction
ECB03/25/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED BENT SPRINKLER HEAD AT 3RD FLOOR STAIRWELL LANDING. POTENTIAL FIRE HAZARD., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB03/25/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSERVNothing owed — awaiting certificate of correction
ECB03/13/2025FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED PUMP ROOM OBSTRUCTED WITH CONSTRUCTION MATERIAL AND PIPES AT DOORWAY. POTENTIAL FIRE HAZARD., REMOVE OBSTRUCTIONNothing owed — awaiting certificate of correction
ECB05/29/2024OBSERVED IN THE BASEMENT/CELLAR JIM CAPS INSTALLED ON CAST IRON FITTINGS., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB05/15/2024FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39074958N ISSUED ON 11/30/2022 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURE TO FILE PERMINothing owed — awaiting certificate of correction
ECB05/15/2024FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39074958P ISSUED ON 11/30/2022 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLY WITH COMMISSINothing owed — awaiting certificate of correction
ECB05/15/2024FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #39074955H ISSUED ON 11/30/2022 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLY WITH COMMISSINothing owed — awaiting certificate of correction
ECB03/27/2024OBSERVED IN THE BOILER ROOM LOCATED IN THE BASEMENT/CELLAR ACTIVE LEAK ON PIPING FROM TEMP BOILER. AS PER 102.3 OF THE PLUMBING CODE MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BENothing owed — awaiting certificate of correction
ECB01/02/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#39074955H ISSUED ON 11/30/2022 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURENothing owed — awaiting certificate of correction
ECB01/02/2024UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #39074959P ISSUED ON 11/30/2022 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURNothing owed — awaiting certificate of correction
ECB12/15/2023UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#39074958N ISSUED ON 11/30/2022 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FAILURENothing owed — awaiting certificate of correction
ECB12/08/2022OBSERVED: AT EXPOSURE # 3, BACK YARD, DISCHARD FIRE SCAPE IS BEING OBSTRUCTED BY MATERIALS STORED. ALSO, AT FIRST FL, EXIT TO BACKYARD, A DEFECTIVE WOODEN STAIRCASE WAS BUILT, BEING AN EMINENT RISK OF ACCIDENTNothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT FIRST FLOOR, MECHANICAL ROOM, WOODEN STRUCTURE THAT SUPPORTS THE ROOF OF THE MECHANICAL ROOM, IS BEING PROVISIONALLY SUPPORTED BY DEFECTIVE WOODEN COLUMNS, WITHOUT PROPER ANCHORING AND INSTALLATIONNothing owed — awaiting certificate of correction
ECB12/06/2022AS PER ONE AO SMITH DOMESTIC HOT WATER BOILER, YEAR BUILT 2014, SERIAL NO. 1433M001233. BOILER NOT REGISTERED. APPLY FOR PROPER PERMITS, CORRECT VIOLATING CONDITIONS, CALL FOR AN INSPECTION.Nothing owed — awaiting certificate of correction
ECB12/06/2022AS PER ONE NATURAL GAS BURNHAM BOILER, YEAR BUILT 2006. SERIAL NO. 64938167; BOILER NOT REGISTERED. APPLY FOR PROPER PERMITS, CORRECT VIOLATING CONDITIONS, CALL FOR AN INSPECTION.Nothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT FIRST FL, MECHANICAL ROOM, FLAMMABLE MATERIAL IS BEING STORED. ALSO, WOODEN STRUCTURE THAT SUPPORTS THE CEILING (COLUMNS) AND CEILING BEAMS HAVE NO FIRE PROTECTION, ROOM CONDITION WITH EASY PROPAGANothing owed — awaiting certificate of correction
ECB12/06/2022AS PER ONE NATURAL GAS, BURNHAM CAST IRON BOILER, YEAR BUILT 2015, SERIAL NO. 65539938; BOILER NOT REGISTERED. APPLY FOR PROPER PERMITS, CORRECT VIOLATING CONDITIONS, CALL FOR AN INSPECTION.Nothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT FIRST FLOOR, MECHANICAL ROOM, WOODEN STRUCTURE THAT SUPPORTS THE ROOF OF THE MECHANICAL ROOM, IS BEING PROVISIONALLY SUPPORTED BY DEFECTIVE WOODEN COLUMNS, WITHOUT PROPER ANCHORING AND INSTALLATIONNothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT CELLAR LEVEL, FIRE PROOF WALLS & CEILING SHOWS SEVERAL HOLES, OPENINGS DUE TO CEILING DAMAGE OR PIPE PENETRATION WITHOUT FIRE STOPPING PROVIDED. PREVIOUS VIOLATION # 39048680Z., PROVIDE/MAINTAIN FINothing owed — awaiting certificate of correction
ECB12/06/2022AT FIRST FLOOR, MECHANICAL ROOM, ACTIVE WATER FILTRATION FROM THE ROOF TO THE INTERIOR OF THE MECHANICAL ROOM., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB04/20/2022FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:OBSERVED:AT 1ST FL,MECHANICAL ROOM,EXPOSED WOOD CEILING W/O FIRE BARRIER,CEILING SUPPORTED BY DEFECTIVE WOODEN COLUMNS(CRACKS). ALSO,THE STRUCTURE(SHORING)Nothing owed — awaiting certificate of correction
ECB04/07/2022OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS.OBSERVED CERTIFICATE OF OCCUPANCY #113386/1997 INDICATES AT CELLAR LEVEL BOILER ROOM FIRE PUMPRM GENERATOR PUMP ROOM & STONothing owed — awaiting certificate of correction
ECB10/15/2021NOTED: OBSERVED AT CELLAR'S, GENERATOR/FIRE PUMP ROOM, FIREPROOF CEILING TILES ARE MISSING AT VARIOUS LOCATIONS EXPOSING WOODEN JOISTS FROM FLOOR ABOVE., PROVIDE/MAINTAIN FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB10/15/2021NOTED: OBSERVED AT FIRST FLOOR LEVEL (REAR) MECHANICAL ROOM, 6"X6" WOODEN VERTICAL POST THAT SUPPORTS THE CEILING IS SHIFTING OFF OF THE CEILING JOISTS, JOIST IS RESTING ON BEAM BY APPROXIMATELY 1 INCH., REPAIRNothing owed — awaiting certificate of correction
ECB10/04/2019NOTE: OBSERVED AT FIRST FLOOR MECHANICAL ROOM, 6"X6" WOODEN SUPPORT MEMBERS THAT SUPPORT THE CEILING HAVE SHIFTED AND ARE BARELY ON THE HORIZONTAL BEAM. , REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB10/04/2019NOTED: OBSERVED AT FIRE PUMP/GENERATOR ROOM AT CELLAR, FIREPROOF CEILING TILES ARE MISSING THROUGHOUT ROOM AND EXPOSING WOODEN JOISTS AND SUB-FLOORING, ALSO ABOVE GAS METER. , PROVIDE/MAINTAIN FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB09/25/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345. NOTED:AT CELLAR, IN FIRE PUMP ROOM, DROP CEILING TILES MISSING AT CEILING ELIMINATING FIRE STOPPING. REMEDY:PROVIDE/MAINothing owed — awaiting certificate of correction
ECB09/25/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 9/25/18 AT ABOVE ADDRESS GAS LEAK ON DRESSER COUPLIN ON THE SERVICE SIDE OF THE BUILDING. CON-ED CALLED AND LOCKED THE VALVE. REMEDY:REPLACE ANNothing owed — awaiting certificate of correction
ECB09/25/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 1ST STORY IN MECHANICAL ROOM, WATER PENETRATING CEILING WITH AN ACTIVE FLOW. REMEDY: REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB03/08/2018FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED.OBSERVED A PRESSURE GAUGE INSTALLED @THE UPPERMOST PART OF THE AUTOMATIC FIRE SPRINKLER SYSTEM HOWEVER DOB RECORDS DOES NOT SHOW ANY TEST BEING PERFORMED ONNothing owed — awaiting certificate of correction
ECB03/08/2018WORK W/OUT A PERMIT.OBSERVED ON THE UPPERMOST FL IN THE STIRWELL WHERETHE INSP TEST(VALVE)IS INSTALLED A PRESSURE GUAGE HAS BEEN INSTALLED W/OUT A PERMI DOB RECORDS DO NOT SHOW ANY PERMITS/APPROVALS ISSUED FORNothing owed — awaiting certificate of correction
ECB03/08/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRE STOPPINGPER BC 712.3;27-345.NOTED:OBSERVED AT CELLAR-WITHIN FIRE PUMP ROOM/GENERATOR ROOM PIPE/CONDUIT PENETRATIONS,SECTIONS OF ACOUSTICAL CEILING TNothing owed — awaiting certificate of correction
ECB03/08/2018FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:OBSERVED AT FIRST FLOOR MECHANICAL ROOM,6INCH X 6INCH POSTS THAT ARE BEING USED TO SUPPORT AND ARRY THE LOAD OF THE SMALL ROOF AT THE REAR HAVE SHIFTENothing owed — awaiting certificate of correction
ECB08/31/2017FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:NOTED.FIRE STOP MISSING IN THE FIRE PUMP ROOM THRU OUT ROOM HOLE IN WALL & CEILING,(GAS) & FUEL TANK ALSO IN ROOM.REM:PROVIDE/MAINTAIN FIRE STOPPING.Nothing owed — awaiting certificate of correction
ECB08/31/2017FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.OBSERVED @TOP OF STAIRWELL INSP TEST W/NO PRESSURE GAUGE INSTALLED AS IS REQUIRED.REM:REPAIR &/OR REPLACE. PHOTO TAKEN.Nothing owed — awaiting certificate of correction
ECB07/19/2016FAILURE TO MAINTAIN BLDG CODE COMPLIANT: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: @ CELLAR BOILER ROOM, APPROX 3' X 3' AREA OF METAL CEILING IS CORRODED/OPEN/MISING EXPOSING CONCEALED SPACE W/ WOOD JOISTSNothing owed — awaiting certificate of correction
ECB06/17/2016WORK W/O PERMIT ON SANDPIPE TIME OF INSPECTION 1:15PM. AT TIME OF INSPECTION I OBSERVED DISCONNECTED AND CAPPED FIRE HOSE CONNECTION FOR FIRE DEPT USE ON EACH FLOOR FROM 1ST THROUGHOUT 5TH ON EXISTING STANDPIPENothing owed — awaiting certificate of correction
ECB03/11/1999FAILURE TO MAINTAIN BUILDING EXTERIOR. NOTED AT ROOF LEVEL FRONT FACADE (WEST SIDE) METAL LOOSE WITH SEPARATION FROM BUILDING. PROVIDE OVER HEAD PROTECTION OF SIDE WALK AT ONCE REPAIRED ALL DEFECTS.Nothing owed — awaiting certificate of correction
ECB07/06/1988OPERATION OF A PA WITHOUT A CURRENT PERMIT. REMEDY: OBTAIN A PERMIT EMERGENCY LIGHTING IS INADEQUATE. REMEDY: INSTALL AMPLE HEADER EMERGENCY LIGHTING AT EXITS.Nothing owed — awaiting certificate of correction