HPD08/09/2026§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1P, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD08/09/2026§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 1P, 2nd STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD06/22/2026HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1P, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , 1st SECTION FROM WEST AT NORTH
HPD04/25/2026§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT STAIRCASE DOOR AT PUBLIC HALL STAIRS, 1st STORY
ECB04/22/2026FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS. AT TIME OF INSPECTION, OBSERVED NO PERMITS ON FILE, NO CERTIFICATE OF CORRECTION FILED WITH$1K due
HPD02/01/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AROUND THE WINDOW FRAME AT SOUTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 2M, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' ORIGINAL VIOLATION 18612093 ISSUED 01-FEB-26 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
HPD02/01/2026§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT AROUND THE WINDOW AT SOUTH WALL IN THE KITCHEN LOCATED AT APT 2M, 2nd STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''NORTH'' ORIGINAL VIOLATION 18612091 ISSUED 01-FEB-26 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE 27-2017.3a(3)(a) or (b).
HPD01/06/2026HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 3C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT SOUTH
HPD12/13/2025§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQUARE FEET AT CEILING AND WEST WALL IN THE 3rd ROOM FROM EAST LOCATED AT APT 2M , 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST
ECB06/05/2025FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION I OBSERVED EXP #1 EAST-CRACKED/SPALLING BRICK BY 6FLWINDOW.-EXP #3 WEST(1) 2 BROKEN WINDOW GLASS 1ST FL AND 5 FL(2) PEALIN$5K due
ECB06/05/2025FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 EAST, #3 WEST OBJECTS ON FIRE ESCAPES MULTI LOC. IMPEDING EMERGENCY EXOT PASSAGEWAY. REMEDY: REMOVE ALL OBJECTS FR$1K due
HPD09/23/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQUARE FEET AT CEILING IN THE BATHROOM LOCATED AT APT 1M, 2nd STORY, 3rd APARTMENT FROM SOUTH AT WEST
DOB08/02/2024FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2024FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD04/11/2024HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1D, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST
HPD01/02/2024§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 4M, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH ORIGINAL VIOLATION 16567176 ISSUED 02-JAN-24 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE §27-2017.3a(5)(a) or (b).
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
HPD07/05/2023§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... CEILING & WALLS AT NORTH CLOSET (APPROX.10 SQ.FT) IN THE 1st ROOM FROM EAST LOCATED AT APT 4M, 4th STORY, 3rd APARTMENT FROM SOUTH AT WEST , 1st SECTION FROM WEST AT NORTH ORIGINAL VIOLATION 16076827 ISSUED 05-JUL-23 HAS BEEN UPGRADED TO CLASS C PER ADMINISTRATIVE CODE §27-2017.3a(5)(a) or (b).
HPD05/22/2023§ 300 M/D LAW FILE PLANS AND APPLICATION AND LEGALIZE THE FOLLOWING ALTERATION OR RESTORE TO THE LEGAL CONDITION EXISTING PRIOR TO THE MAKING OF SAID ALTERATION PARTITION WALLS ERECTED FROM FLOOR TO CEILING SUBDIVIDING THE ROOM AND REDUCING NATURAL LIGHT VENTILATION. IN THE KITCHEN LOCATED AT APT 6N, 6th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD10/28/2022§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING APPROXIMATELY 6 SQ.FT IN THE BATHROOM LOCATED AT APT 5N, 5th STORY, 1st APARTMENT FROM NORTH AT EAST ORIGINAL VIOLATION 15451768 ISSUED 28-OCT-22 HAS BEEN UPGRADED TO CLASS B PER ADMINISTRATIVE CODE §27-2017.3a(3)(a) or (b).
ECB09/12/2022CEASE USE VIOLATION ISSUED, CAR DOOR RESTRICTOR ALTERED AND NOT WORKING, REMEDY REPAIR THEN NOTIFY NYCDOB, FOR RESTORE TO SERVICE REINSPECTION,........ CLASS 2 VIOLATION ISSUED, 1) NO CODE TAG ON DEVICE, REMEDY$1K due
HPD06/14/2022HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 5N, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
HPD06/14/2022HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5N, 5th STORY, 1st APARTMENT FROM NORTH AT EAST
DOB12/01/2021FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB04/29/2021FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
DOB03/03/2021V-DOB VIOLATION - ACTIVE
DOB03/03/2021V-DOB VIOLATION - ACTIVE
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB05/02/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/16/2019FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
HPD08/28/2018§ 27-2005 HMC:TRACE AND REPAIR THE SOURCE AND ABATE THE NUISANCE CONSISTING OF MOLD ... AT CEILING AND WALLS APPROX 5 SQ.FT IN THE BATHROOM LOCATED AT APT 3C, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH ''
DOB02/02/2018FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB05/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB02/02/2017FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB11/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB08/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/02/2016FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB06/01/2016FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB10/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2013 INSPECTION/TEST
DOB10/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2013 INSPECTION/TEST
DOB06/06/2014FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
DOB03/31/2014VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2012 INSPECTION/TEST
DOB10/01/2012VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2011 INSPECTION/TEST
DOB12/13/2011VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2010 INSPECTION/TEST
DOB07/01/2005V-DOB VIOLATION - ACTIVE
DOB03/10/2000V-DOB VIOLATION - ACTIVE
ECB05/04/2024WORK WITHOUT PERMIT. AT TIME OF INSPECTION I OBSERVED WORKERS AT REAR OF PREMISES PERFORMING FACADE WORK. THERE ARE NO PERMITS ON FILE FOR THIS WORK., OBTAIN PERMITNothing owed — awaiting certificate of correction
ECB03/10/2022PHONE NOT WORKINGNothing owed — awaiting certificate of correction
ECB09/19/2019(C/U)45M07;61T07,02X10,57M07,68M07 CEASE USE CONTINUE AGGRAVATED 1. THE VIOLATING CONDITION LISTED ABOVE CONTINUE TO EXIST ON THE DEVICE CREATING A HAZARDOUS CONDITION FOR TENANTS,VISITORS AND EMERGENCY RESCUE.Nothing owed — awaiting certificate of correction
ECB09/10/2019(CEASE USE-45M7)(56B10,57M7,64M7,15M7,2X10)ONE CEASE USE ITEM/45M7 PROVIDE LED SEAL WITH FULL LOAD OF WEIGHTS AND TAC DEVICE IN THE PRESENCEOF A DOB ELEVATOR INSPECTOR AT TIME OF REINSPECTION.56B# HOIST MOTOR MNothing owed — awaiting certificate of correction
ECB09/04/201556Y13,67M07,68B07,97X10. 67M07-PROVIDE COMMUNICATION IN CAR (TELEPHONE) 68B07-PROIVDE UPDATED MAINTENANCE LOG; 97X10-REPAIR ELEVATOR AND RETURN TO SERVICE SO A COMPLETE INSPECTION CAN BE MADE BY THE DEPARTMENT.Nothing owed — awaiting certificate of correction
ECB08/11/201567M10,68B07,60X10,24X10,15L10,19M10. 67-PROVIDE EMERGENCY COMMUNICATION (PHONE) IN ELEV CAB TO AN OUTSIDE SOURCE; 68-FOUND NO MONTHLY MAINTENANCE LOG ENTRIES SINCE 5/15 (8.6.1.4); 60-REBULB OR REPAIR LIGHT FIXNothing owed — awaiting certificate of correction
ECB05/22/201501D06;05M07;19M07;29Q03;36Q03;21Q03;42D06;56Y13;72M07;05-M-07 PROVIDE CAR DOOR RESTRICTOR (ZONE LOCK) 19-M-07 PROVIDE BOTTOM HOISTWAY DOOR SAFETY RETAINER (FIRE GIBBS) 36-Q-03 INSTALL COVER & FOR ELECTRICAL BOXNothing owed — awaiting certificate of correction
ECB01/20/201241D06,99BB05,98BB05,72M10,100I10,45H10,17H10;100/I/10-METAL STAIR STEPDAMAGED FOR ENTRY TO MOTOR ROOM.45-GOV BEARING.Nothing owed — awaiting certificate of correction
ECB10/28/201141D06/ 99BB05/ 98BB05/ 100I10/ 45H10/ 05J10/ 40M7/ 72M10/ 17H10/ 41 - REPAIR DOOR LOCK 100I10 - METAL STAIR STEP DAMAGED FOR ENTRY TO MOTOR ROOM 45 - REPAIR WORN GOV. BEARING 05 - CAR DOOR NOT OPENING FREELY TENothing owed — awaiting certificate of correction
ECB10/28/201199BB05/ 98BB05/ 42G11/ 17H10/ 72M10/ 42H10/ 42 - FUSE WIRE JUMPED ON CONTROLLER 42 - SELECTOR SHEAVE ( WORN BEARING ) IN MOTOR ROOMNothing owed — awaiting certificate of correction
ECB10/05/201115 34A 48A 50ABC 50A-WATER LEAK @ TUBE OR CHAMBER 50B-DEFECTIVE SMOKE ALARM 50C-NO CONNECTED ACCESS CONNECTED ACCESS CONTROL @ KING VALVENothing owed — awaiting certificate of correction