ECB03/14/2023Reissue#35591605H failure to maintain building in code-compliant manner.note:observed at cellar level,gas meter room has multiple metal shelves installed and is currently being used for storage with numerous ca$6K due
ECB02/28/2020Work after hours without variance permit note:at the time of inspection it was observed that workers were installing a chain link fence on top of concrete barriers from previous issued permit job#201202938.that$-2,533 due
ECB03/31/202628-301.1. Reissue on ECB #35717265L. Failure to provide ventilation togas meter room per P115.6(1968 code), fgc appendix e(E4)(2014 code). Noted: no ventilation exists in gas meter room observed upon inspectionNothing owed — awaiting certificate of correction
ECB03/31/2026Exit door not self-closing. Noted: emergency exterior exit door not self-closing due to binding and/or faulty hardware on emergency exit exterior door at cellar level not self-closing when tested upon inspectioNothing owed — awaiting certificate of correction
ECB03/31/2026Failure to maintain building in code-compliant manner. Illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. Noted: emergency illuminated discharge boxes and exit signs not illuminNothing owed — awaiting certificate of correction
ECB03/31/2026Failure to maintain building in code-compliant manner. No fire stopping per bc 712.3; 27-345. Noted: missing fire stopping in various locations throughout electrical switch gear room observed upon inspection atNothing owed — awaiting certificate of correction
ECB03/31/2026Reissue on ECB #35682967Z. Failure to maintain building in code-compliant manner. Noted: fire rated smoke doors and classroom doors not self-closing due to binding, missing or faulty hardware on smoke door staiNothing owed — awaiting certificate of correction
ECB03/31/2026Reissue on ECB #35717266N. Failure to maintain building in code-compliant manner. Noted: metal shelves and storage in gas meter room at cellar level observed at time of inspection. Remedy: repair and/or replaceNothing owed — awaiting certificate of correction
ECB10/20/2025Found federal model#PLW231 oil fired boiler with low water cut of missing on water column, both safety relief valves evidence of leaking, replace valves.Nothing owed — awaiting certificate of correction
ECB10/20/2025Found federal plw-231 oil fired boiler with smoke alarm on breeching not operable, both safety relief valves defective, evidence valves are leaking, needs to be replaced.Nothing owed — awaiting certificate of correction
ECB07/05/202528-301.1. Reissue: 35682969M-failure to provide ventilation at gas room. Remedy: comply with code.Nothing owed — awaiting certificate of correction
ECB07/05/2025Reissue: 35663335R-failure to maintain building in code-compliant manner: gas meter room has metal shelves with storage. Remedy: comply withcode.Nothing owed — awaiting certificate of correction
ECB08/01/202428-301.1 failure to provide ventilation to gas meter room per P115.6.note:gas meter room in the cellar has multiple metal shevles throughoutstacked with gar board boxes.rem:comply with notice of violation.Nothing owed — awaiting certificate of correction
ECB08/01/2024Reissued ECB#35663337K exit door not self closing.noted:exit doors notworking properly 3 fl staircase b-2FL staircase b.rem:repair/replace door.Nothing owed — awaiting certificate of correction
ECB03/16/2022Re-issued #35546386Y failure to maintain building in code compliant manner.noted:observed at cellar level(gas meter room)multiple shelves installed & now being used for storage with multiple boxes,plastic binsNothing owed — awaiting certificate of correction
ECB02/03/2021Reissue#35495905J failure to maintain bldg in code compliant manner noted:bsmt gas meterrm's used for storage w/shelves.multiple boxes,papers&school supplies.comply w/code.Nothing owed — awaiting certificate of correction
ECB08/07/2020Smoke watchman boilers no.1 & no.2 defective-corrosion on blow off valve at front of boiler no.2-oil leak in area of burner no.2; correct all violating conditions, submit a certificate of correction.Nothing owed — awaiting certificate of correction
ECB05/29/2020Failure to maintain bldg in code compliant manner. Noted: at basement gas meter room created shelving units w/storage of multiple boxes,crates & other various items throughout. Remedy: comly w/code.Nothing owed — awaiting certificate of correction
Likely answered · the city's own records show a filing, but DOB's feed still lists these as active
DOB11/14/2025Violation issued-failure to file 2024 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered2 identical filings
DOB06/20/2023Violation issued-failure to file 2019 external low pressure inspectionThe owner has filed since: boiler inspection reports are on file for later years (latest 2026). This one is not shown as answered2 identical filings