DOB06/23/2024FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2023)
DOB01/13/1997V-DOB VIOLATION - ACTIVE
ECB04/14/2026FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). NOTED: CLASSROOMS DOOR HAVE PROHIBITED HARDWARE(KICKSTOPS) ON THEM AT RM #S-217, 213, 20Nothing owed — awaiting certificate of correction
ECB04/14/2026RE-ISSUE #35719989X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIOR FIRE-PROOF DOORS DO NOT SELF-CLOSE PROPERLY AT 3RD FLR STAIRCASE "E", "K". 2ND FLR-STAIRCASE "C". CLASSROOM DOORS DO NNothing owed — awaiting certificate of correction
ECB04/14/2026RE-ISSUE #35719987M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT RM #573 FAN ROOM, INTERIOR RUNNING CRACK, EXTERIOR STAIRCASE BULKHEAD CRACKS STAIRCASE WALLS. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB12/09/2025PARTIAL STOP WORK ORDER ISSUED FOR WORKING AFTER HOURS WITHOUT A PERMIT NOTED AT TIME OF INSPECTION WORKERS WERE JACKHAMMERING INSIDE OF COURTYARD WITHOUT A AFTER HOURS PERMT STOP ALL AFTER HOURS WORK, OBTAIN ANothing owed — awaiting certificate of correction
ECB07/09/2025REISSUE #35682677K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED AT ENTIRE BUILDING ALL LEVELS EMERGENCY LIGHTNothing owed — awaiting certificate of correction
ECB07/09/2025REISSUE #35682676Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 573 FAN ROOM INTERIOR RUNNING CRACK, EXTERIOR STAIRWELL BULKHEAD CRACKS STAIRWELL WALLS. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/09/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT ELECTRICAL ROOM FOUNDATION WALLS AT BOTTOMS WATER PENETRATION, WATER PUDDLING. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/09/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 3 FLOOR CORRIDOR BY 348, 357, 204(2), HALLWAY BY STAIR E BROKEN GLASS PANELS. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/09/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 4 FLOOR 437, 450, 434, 3 FL. 331, 2FL. 245, BASEMENT B3 DOORS ARE NOT SELF-CLOSING. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/09/2025REISSUE #35434176J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT TUNNEL IN 1930 WING, WATER PENETRATION CEILING TUNNEL FLOODED TOWARDS 91 STREET. REMEDY: REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB06/04/2024OPERATION OF A PLACE OF ASSEMBLY WITHOUT A CURRENT CERTIFICATE OF OPERATION.NOTED 2ND FL LIBRARY ARRANGED WITH APPROX.115 SEATS NO PA PERMITPOSTED OR PROVIDED UPON REQUEST.REM:OBTAIN PLACE AT ASSEMBLY CERTIFICANothing owed — awaiting certificate of correction
ECB06/04/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:SEVERAL EMERGENCY LIGHTS WITH BATTERY BACK UP POWER NOT WORKING WHEN TNothing owed — awaiting certificate of correction
ECB06/04/2024REISSUE#35674936X FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT TOP ROOF LEVEL.FAN ROOM#572,VERTICAL CRACK ON WALL APPROX.5FT LONG WITH 1/2 SEPARATION.ALSO HORIZONTAL CRACK APPROX.15FT LONG RUNothing owed — awaiting certificate of correction
ECB05/16/2023REISSUED#35657735P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED AT ROOF LEVEL FAN ROOM HAS A VERTICAL CRACK APPROX 5 FEET LONG 1/2 UNDER.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/14/2023REISSUED#35657739M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED IN CELLAR LEVEL INSIDE OIL TANK ROOM.FOUNDATION WALL HAS BECOME PORCUS ALLOWING WATER IN.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/13/2022REISSUE#35560930J.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED AT CELLAR FOUNDATION WALL HAS BEEN POROUS ALLOWING WATER TO PENETRATE.REMEDY:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/13/2022REISSUED#35560939X FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT REAR LEVEL FROM ROOM HAS VERT CRACK APPROX 5'LONG1/2 WIDE ON BACK WALL.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/05/2021FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED:OBSERVED@TIME OF INSP ROOF LEVEL FAN RM HAS VERT CRACK APPROX5' LONG 1/2" WIDE ON WALL.REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/05/2021REISSUED 3549580H FAILURE TO MAINTAIN BLDG WALLS &/OR APPURTENANCES. NOTED:OBSERVED DURING INSPECTION OF OLD OIL TANK ROOM IN SUB-BASEMENT WATER PENETRATED INTO THE ROOM,W/STANDING WATER COLLECTING TO OVER 1INNothing owed — awaiting certificate of correction
ECB05/05/2021REISSUED35495679K FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED:OBSERVED DURING INSP OF SUBBSMT (CELLAR) FOUNDATION WALLS HAVE BECOME POROUS ALLOWING WATER TO PENETRATE&COLLECT ON FL ALTHO OUT (1930 BLNothing owed — awaiting certificate of correction
ECB05/20/2020REISSUE#35028804H-FAILURE TO MAINTAIN BUILDING WALLS AND OR APPURTENANCES.NOTED:THE FOUNDATION HAS ALLOWED WATER TO PENETRATE INTO TANK ROOMSTANDING WATER!REMEDY:REPAIR AND/OR REPLACES.Nothing owed — awaiting certificate of correction
ECB05/20/2020REISSUE#35260591J-FAILURE TO MAINTAIN BUILDLING IN CODE-COMPLIANT MANNER.THERE'S A TUNNEL @ CELLAR LEVEL THAT LEAKS/FLOODS DURING RAIN.REMEDY:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB05/28/2019REISSUE #3533175J DATE OF ISSUE 05-03-2018 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER SPALLING PLASTER CEILING AT 19305 TUNNEL LEAKS VIAIBLE.REPARI ADN/OR REPLACENothing owed — awaiting certificate of correction
ECB05/28/2019REISSUE #35328824J DATE OF ISSUE 05-03-2018 FAILURE TO MAINTAIN BUILDING WALLS AND OR APPURTENACES FUNDATION WALL AT OIL TANK ROOM HAS POROUSE WALLS WATER PENETRATION VISIBLE.MAINTAIN EXTERIOR BUILDINGSNothing owed — awaiting certificate of correction
ECB05/03/2018REISSUE: 35260593N FAILURE TO MAINTAIN BLDG WALLS AND OR APPURTENANCES FOUNDATION WALL AT OIL TANK ROOM HAS POROUS WALLS WATER PENETRATION VISIBLE. RMDY: REPAIR REPLACE MAINTAIN EXTERIOR BLDG WALLS.Nothing owed — awaiting certificate of correction
ECB05/03/2018REISSUE: 35260591J FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER SPALLING PLASTER CEILING AT 1930S TUNNEL LEAKS VISIBLE. RMDY: REPAIR/ REPLACE.Nothing owed — awaiting certificate of correction
ECB05/09/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER 1930S TUNNEL AT CELALR FLOODS/LEAKS DURING RAIN STORMS WATER THROUGHOUT TUNNEL. RMDY: REPAIRNothing owed — awaiting certificate of correction
ECB05/09/2017REISSUE #35216159M FAILURE TO MAINTAIN BUILDING WALLS/APPURTENANCES FOUNDATION WALL AT OIL TANK ROOM HAS BECOME POROUS ALLOWING WATER TO PENETRATE CELLAR. RMDY: REPAIR/REPLACE.Nothing owed — awaiting certificate of correction
ECB10/17/2016REISSUE #35127841K FAILURE TO MAINTAIN BLDG WALL(S)APPURTENANCES.NOTED:THE FOUNDATION WALL @OIL TANK ROOM HAS BECOME POROUS ALLOWING WATER TO PENETRATE INTO CELLAR.Nothing owed — awaiting certificate of correction
ECB09/09/2015RESISSUE #35028804H.FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES.@ CELLAR WATER PENETRATIONS @ OIL TANK RM STANDING WATER PRESENT.REM:COMPLY W/ NOTICE OF VIOLATION.Nothing owed — awaiting certificate of correction
ECB09/05/2014REISSUE 35028804H.WATER PENETRATION @ OIL TANK ROOM CELLAR NOTED STANDING WATER PRESENT.REM:SEAL PENETRATIONS.Nothing owed — awaiting certificate of correction
ECB07/30/2013WATER PENETRATION. AT OIL (FUEL) TANK ROOM (CELLAR) THE FOUNDATION HASBECOME POROUS ALLOWING WATER TO PENETRATE INTO THE TANK ROOM WITH APPRX 1" OF STANDING WATER. PENETRATION APPEARS TO BE ABOVE THE DYKE LINENothing owed — awaiting certificate of correction