ECB11/28/2025FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR VIOLATION #39097281M, FILE A CERTIFICATE OF CORRECTION$1K due
ECB11/28/2025FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR VIOLATION #39069276J, FILE A CERTIFICATE OF CORRECTION$1K due
ECB11/03/2025OBSERVED ON THE ROOF FUTURE GAS LINE AND OPEN ENDED GAS. ALSO ON THE ROOF PVC DRAIN LINES INSTALLED WHICH IS CONTRARY TO CODE SECTIONS PC 1101.10 AND FGC 404.15, REPAIR AND/OR REPLACE$625 due
DOB02/21/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB01/10/2024FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB10/04/2023FAILURE TO CERTIFY CORRECTION ON IMMEDIATELY HAZARDOUS (CLASS 1) ECB VIOLATION
DOB06/04/2001VW-VIOLATION WORK WITHOUT PERMIT - ACTIVE
ECB10/18/2023I OBSERVED IN THE GAME/REC ROOM THE FLEXIBLE CORD OF THE PUMP ENTERING THE CEILING. AS NOTED IN THE PREVIOUS ECB 39069277L ISSUED ON 09/01/2022.; EC400.8, COMPLY WITH EC CODE; COMPLY WITH COMMISSIONER'S ORDERS.Nothing owed — awaiting certificate of correction
ECB10/18/2023I OBSERVED IN DOB RECORDS NO CERTIFICATE OF CORRECTION FOR ECB# 39069276J ISSUED ON 09/01/2022 FOR IMPROPER SUPPORT OF TEMP WIRING AND LIGHTS. THIS IS A FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDERS., FILE ANothing owed — awaiting certificate of correction
ECB10/18/2023I OBSERVED IN DOB RECORDS NO CERTIFICATE OF CORRECTION FOR ECB # 39069274X AS PER COMMISSIONER'S ORDERS., FILE A CERTIFICATE OF CORRECTION; FILE C OF CNothing owed — awaiting certificate of correction
ECB10/18/2023I OBSERVED ON THE ROOF THE FAILURE TO INSTALL AN EQUIPMENT GROUNDING CONDUCTOR IN THE RACEWAY OF THE WATER CHILLER AS REQUIRED WITH THE USE OF FLEXIBLE RACEWAYS AS PER EC 350.60; EC 350.60, COMPLY WITH EC CODE;Nothing owed — awaiting certificate of correction
ECB10/17/2023I OBSERVED IN DOB RECORDS THE FAILURE TO CORRECT ECB # 39069277L AND SUBMIT A CERTIFICATE OF CORRECTION AS REQUIRED., FILE A CERTIFICATE OF CORRECTION; MAKE CORRECTIONS AND FILE C OF CNothing owed — awaiting certificate of correction
ECB10/17/2023OBSERVED IN THE BASEMENT/CELLAR IN THE ROOM ADJACENT TO THE BOILER ROOM WASTE LEAK ON HOUSE TRAP AND CAST IRON PIPING IS CRACKED AND FLAKING. AS PER 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, ANDNothing owed — awaiting certificate of correction
ECB09/01/2022I OBSERVED IN THE BASEMENT PAST THE PUMP ROOM THE IMPROPER INSTALLATION AND SUPPORT OF TEMPORARY WIRING AND LIGHTING. PHOTOS TAKEN, PROTECT TEMPORARY WIRINGNothing owed — awaiting certificate of correction
ECB09/01/2022I OBSERVED AN FLEXIBLE CORD FROM THE ROOM DOWN THROUGH THE BOILER ROOM AND INTO THE PUMP ROOM AND CONNECTED TO AN INSTALLED PUMP CONTROL. THIS IS AN IMMEDIATE HAZARD AS THE CORD IS PASSING THRU DOORWAYS AND SECNothing owed — awaiting certificate of correction
ECB09/01/2022I OBSERVED IN THE FOURTH FLOOR MEN'S ROOM MULTIPLE DEFECTIVE/INOPERABLE GFCI OUTLETS. ALL ELECTRICAL EQUIPMENT SHALL BE MAINTAINED., COMPLY WITH EC; REPAIR, REPLACE OR REMOVE.Nothing owed — awaiting certificate of correction
ECB09/01/2022OBSERVED 2 ACTIVE LEAKS ON STEPS GOING TOWARDS BOILER, (1) ACTIVE LEAK ON SPRINKLER MAIN CAUSING CORROSION TO HAND RAIL, (2) ACTIVE LEAK ON POTABLE WATER PIPING CAUSING CORROSION TO METAL STEPS., REPAIR AND/ORNothing owed — awaiting certificate of correction
ECB08/08/2017FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 4TH STORY CORRIDOR, NORTH SECTION CONCRETE CEILING CRACKED AND PLASTER CRACKED AT VARIOUS LOCATIONS THROUGHOUT CORRIDOR. REMEDY: REPAIR AND/OR RENothing owed — awaiting certificate of correction
ECB08/08/2017FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 8/8/2017 AT ABOVE ADDRESS SPRINKLER PIPE IS BEING SUPPORTED BY WATER PIPE. ALSO NOT BEING SUPPORTED WITH HANGERS BUT WITH WIRE. REMEDY: REPAIRNothing owed — awaiting certificate of correction