ECB12/24/2025CLASS 1 RTS AGG 1 CONT: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REMEDY: RESTORE TO SERVICE AND CONTACT THE DOB ELEVATOR DIVISION AT ELEV$12K due
DOB02/22/2023FAILED TO FILE FISP CYCLE 9B TECHNICAL REPORT BY 2/21/2023
DOB07/20/2021V-DOB VIOLATION - ACTIVE
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB09/06/2019VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2017 CAT 1 INSP/TST TST
DOB05/20/2019FAILURE TO PERFORM CATEGORY 5 INSPECTION
DOB06/26/2018V-DOB VIOLATION - ACTIVE
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/26/2018VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2016 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB01/03/2017VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2015 CAT 1 INSP/TST
DOB08/30/2013FAILED TO FILE FISP CYCLE 7B TECHNICAL REPORT BY 08/21/2012
DOB10/26/2010V-DOB VIOLATION - ACTIVE
DOB01/13/1997V-DOB VIOLATION - ACTIVE
DOB03/17/1992VP-VIOLATION UNSERVED ECB-ACTIVE
DOB05/29/1990V-DOB VIOLATION - ACTIVE
DOB05/23/1989V-DOB VIOLATION - ACTIVE
ECB08/19/2026CLASS 2 RTS: DEVICE FOUND IN A NON COMPLIANT CONDITION REQUIRING RETURN TO SERVICE. AS PER 1 RCNY 11 02 AND BC 3001.2. REMEDY: RESTORE DEVICE TO FULL CODE COMPLIANT OPERATION AND VERIFY ALL SAFETY FUNCTIONS.Nothing owed — awaiting certificate of correction
ECB04/20/2026ATOI: OBSERVED DEMO WORK IN BASEMENT AREA WITCH INCLUDED INTERIOR WALLS,DOOR FRAME EXTENSION. NO PERMIT ON FILE FOR THIS WORK ., OBTAIN ALL PERMITSNothing owed — awaiting certificate of correction
ECB12/24/2025CLASS 2: MISSING CITY ID NUMBER ON CONTROLLER, PROVIDE. MISSING DOOR OPERATOR COVER EXPOSING INTERNAL COMPONENTS, INSTALL. FLOORS B AND 6 HOISTWAY DOORS NOT SELF CLOSING, VERIFY OPERATION ON ALL FLOORS AND ADJUNothing owed — awaiting certificate of correction
ECB12/24/2025CLASS 1 AGG 1 RTS CONT: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REMEDY: RESTORE TO SERVICE AND CONTACT THE DOB ELEVATOR DIVISION AT ELEVNothing owed — awaiting certificate of correction
ECB06/16/2025CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.UPON INSPECTION DEVICE IS FOUND TO BE OUT OF SERVICE,CREATING A HAZARDOUS CONDITION PER 1RCNY 11-02. REMEDY: RESTORE TO SERVICE IMMEDIATELY AND CONTNothing owed — awaiting certificate of correction
ECB06/16/2025CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.UPON INSPECTION DEVICE FOUND TO BE OUT OF SERVICE,CREATING A HAZARDOUS CONDITION PER 1RCNY 11-02. REMEDY: RESTORE TO SERVICE IMMEDIATELY AND CONTACTNothing owed — awaiting certificate of correction
ECB03/25/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11Nothing owed — awaiting certificate of correction
ECB03/18/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE.OBSERVED UNPERMITTED FOAM ULITILIZE FOR HOLE PENETRATION. HOLE PENETRATIONS THROUGNothing owed — awaiting certificate of correction
ECB03/18/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11Nothing owed — awaiting certificate of correction
ECB03/18/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LEAKING PIPES ABOVE CLIENTS BEDDING ON 3RD FLOOR. POTENTIAL SLIP HAZARD., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB03/18/2025CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. NO DATE ON CATEGORY 5 DATA TAG. NO CITY ID# ON CONTROLLER. PROVIDE AN UPDATED MAINTENANCE LOG. PROVIDE A MAINTENANCE PROGRAM. PROVIDE PROPER TENSION ON HOISTWAYNothing owed — awaiting certificate of correction
ECB03/18/2025UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. UNSAFE STORAGE IN MECHANICAL ROOMS THROUGHOUT BUILDING.(BOXES, CHAIRS, CLEANING MATERIALS) POTENTIAL FIRE HAZARD., MAINTAIN STORAGE IN COMPLIANCE WITH FIRENothing owed — awaiting certificate of correction
ECB03/17/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). ILLENothing owed — awaiting certificate of correction
ECB06/03/2024NO EMERGENCY LIGHTING TO ILLUMINATE AND OR INDICATE EMERGENCY EXIT LOCATED THROUGHOUT BUILDING STAIRCASE CORRIDORS., REPAIR AND/OR REPLACE LIGHTINGNothing owed — awaiting certificate of correction
ECB06/03/2024OBSERVED IN THE STORAGE ROOM LOCATED IN THE BASEMENT/CELLAR JIM CAPS INSTALLED ON CAST IRON FITTINGS. AS PER 102.3 OF THE PLUMBING CODE MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALLNothing owed — awaiting certificate of correction
ECB06/03/2024COMBUSTIBLE MATERIAL, (BOXES, AND OFFICE MATERIAL) STORED ON MEZZIDENE LEVEL BLOCKING EGRESS/EMERGENCY EXITS.; 28-301.1, COMPLY WITH CODENothing owed — awaiting certificate of correction
ECB05/29/2024CRACKS AND DETACHED CEMENT FOUND UNDERNEATH STAIRCASE LANDING LOCATED AT STAIRCASE C, ROOF LEVEL., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB05/17/2024CLASS 1 RTS DEVICE UNDER CEASE USE ORDERSNothing owed — awaiting certificate of correction
ECB05/17/2024BOTTOM CWT RUNBY LESS THAN 6 INCHES. NEED TO SHORTEND ROPES.Nothing owed — awaiting certificate of correction
ECB05/17/2024CLASS 1 RTS. DEVICE UNDER CEASE USE ORDERSNothing owed — awaiting certificate of correction
ECB04/11/2024FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#900821.REM:SUBMIT ACCEPTABLE REQUIRED TNothing owed — awaiting certificate of correction
ECB04/28/2023RESTORE TO SERVICENothing owed — awaiting certificate of correction
ECB12/08/2022I OBSERVED IN BASEMENT GAS METER WAS MADE INACCESSIBLE BY WOOD FRAME COLUMN. AS PER APPENDIX E OF THE 2014 FGC METERS SHALL BE ADEQUATELY PROTECTED AGAINST EXTREME COLD OR HEAT AND SHALL BE READILY ACCESSIBLE FNothing owed — awaiting certificate of correction
ECB12/08/2022GAS LEAK FOUND ON COMMERCIAL COOKING EQUIPMENT. CON-ED CALLED AND FOUND THE LEAK ON THE GAS REGULATOR. THEY THEN PROCEEDED TO SHUT AND RED TAG THE COMMERCIAL COOKING EQUIPMENT., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB12/08/2022CURRENTLY OUT OF SERVICE AND NOT WORKING; REPAIR AND RE INSPECT ELEVATORNothing owed — awaiting certificate of correction
ECB12/08/2022OBSERVED: AT ROOF LEVEL, STANDPIPE RM, AT CELLAR & SUB CELLAR (PARTIAL UNDER REPAIR) LEVELS, ELECTRICAL RM, KITCHEN RM, STORAGE RM SEVERAL OPENING THROUGH FIREPROOF WALLS/CEILING WITHOUT FIRE STOPPING PROVIDED.Nothing owed — awaiting certificate of correction
ECB12/08/2022ELEVATOR CURRENTLY STUCK IN LOBBY AND OUT OF SERVICE; RESTORE TO SERVICE AND RE INSPECT WITH NYC DOBNothing owed — awaiting certificate of correction
ECB12/06/2022OBSERVED: AT SUB CELLAR LEVEL, BOILER ROOM, FOUNDATION WALL HAS VERTICAL CRACKS & CONSTRUCTIVE JOINTS OPEN WITHOUT JOINT SEALING AND CRACK REPAIR, FROM FLOOR TO CEILING. PREVIOUS VIOLATION # 35651071Y, MAINTAINNothing owed — awaiting certificate of correction
ECB12/06/2022AS PER ONE FEDERAL FST-150, HEATING BOILER; FLANGE GASKET ON STEAM MAIN LEAKING-FEEDWATER PIPING NEAR HARTFORD LOOP, CORRODED AND LEAKING-BODY DRAINS ON SAFETY VALVES PLUGGED-BODY DRAINS NOT INSTALLED ON SAFETYNothing owed — awaiting certificate of correction
ECB12/01/2022OBSERVED IN THE BASEMENT CRACKED CAST IRON WASTE FITTINGS IN CEILING. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION IN ACNothing owed — awaiting certificate of correction
ECB10/31/2022RECURRENT CONDITION CONTINUED CLASS 1Nothing owed — awaiting certificate of correction
ECB08/19/202297,X,10 RESTORE TO SERVICE CLASS 1. REPAIR AND CALL DOB FOR PROPER INSPECTIONNothing owed — awaiting certificate of correction
ECB07/08/2022I OBSERVED ON ALL FLOORS THE INSTALLATION OF CONDUITS, JUNCTION BOXES, DEVICES, AND BRANCH CIRCUIT WIRING TO SUPPLY POWER TO WALL MOUNTED HEPA FILTERS. NO PERMIT IN DOB RECORDS COVERS THIS WORK., OBTAIN PERMIT;Hearing held — result not yet published$800 proposed
ECB07/08/2022I OBSERVED IN THE MAIN ELECTRICAL ROOM AN ELECTRICAL DISTRIBUTION CABINET IN A STATE OF SEVERE CORROSION. ALL ELECTRICAL EQUIPMENT SHALL BE MAINTAINED AND PROTECTED AGAINST DETERIORATING AGENTS., COMPLY WITH ECHearing held — result not yet published$800 proposed
ECB04/19/2022I OBSERVED AN ACTIVE LEAK ON THE THE STEAM PIPING IN STAIR A ON THE 6 FLOOR ALSO IN THE CELLAR., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB04/19/2022FOUND ELEVATOR OUT OF SERVICE. RESTORE TO SERVICE FOR PROPER INSPECTION BY NYCDOB.Nothing owed — awaiting certificate of correction
ECB04/19/2022I OBSERVED FERNCO COUPLING AS WELL AS JIM CAPS INSTALLED ON SANITARY ( CAST IRON) PIPING IN THE CELLAR., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB04/19/2022FOUND ELEVATOR OUT OF SERVICE. RESTORE TO SERVICE FOR PROPER INSPECTION BY NYCDOB.Nothing owed — awaiting certificate of correction
ECB03/31/2022FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC 712.3; 27-345 OBSERVED AT BASEMENT LEVEL BOILER ROOM ELECTICAL ROOOM ELEVATOR ROOM GAS METER ROOM(UNDERCONSTRUCTION)SEVERAL OPENINGNothing owed — awaiting certificate of correction
ECB03/31/2022FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.OBSERVED:ALL BASEMENT LEVEL,BOILER ROOM,GROUNDWATER BEING PENETRATED THROUGH FOUNDATIONWALL INTO BOILER ROOM,ALSO THE FOUNDATION WALL HAS VERTICAL CRACK IN INothing owed — awaiting certificate of correction
ECB03/29/2022FOUND ELEVATOR OUT OF SERVICE. RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB.Nothing owed — awaiting certificate of correction
ECB03/29/2022BRAKE PICK SWITCH IS NOT WORKING. REPLACE/REPAIR. CAT1 TAG MISSING IN THE ELEVATOR MACHINE AND CONTROL ROOM. PROVIDE.Nothing owed — awaiting certificate of correction
ECB03/29/2022OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE. REMEDY: RESTORE TO SERVICE IMMEDIATELY AND, NOTIFY NYCDOB THE DEVICE HAS BEEN RETURNED TO SERVICE. E-MAIL EIR@BUILDINGS.NYC.GOV SO AN INothing owed — awaiting certificate of correction
ECB12/13/2021UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTIONNothing owed — awaiting certificate of correction
ECB10/15/2021FEDERAL FST-150 FTM=LEAKING GASKET ON STEAM FLANGE BOILER CONNECTION, LEAKING BACKFLOW, MISSING SPILL SWITCH, CAN NOT PLUG SAFETY VALVES BODY DRAIN, MISSING SAFETY VALVES PULL CHAINNothing owed — awaiting certificate of correction
ECB10/15/2021UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. RESTORE TO SERVICE IMMEDIATELY. YOU CAN CONTACT NYCDOB AT EIR@BUILDINGS.NYC.GOV FO A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB10/15/2021CLASS 1 RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB.Nothing owed — awaiting certificate of correction
ECB10/15/2021FEDERAL FST-150 FTM= MISSING SPILL SWITCH, CAN NOT PLUG SAFETY VALVES BODY DRAIN, MISSING SAFETY VALVE PULL CHAINNothing owed — awaiting certificate of correction
ECB09/27/2021FEDERAL FST-150 FTM=MISSING SPILL SWITCH, CAN NOT PLUG SAFETY VALVES BODY DRAIN, MISSING SAFETY VALVE PULL CHAINNothing owed — awaiting certificate of correction
ECB07/01/2021CLASS 1 RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB.Nothing owed — awaiting certificate of correction
ECB07/01/2021NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K 3 OF THE 2014 NYCBC THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY REMEDY FILE APPLICATION, ,INSTALL DLM ANNothing owed — awaiting certificate of correction
ECB12/30/2020BACK FLOW LEAKING, STEAM HEADER LEAKING. CORR VIO COND & SUBMIT CERT OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/21/2020BODY DRAINS ON SAFETY VALVES MISSING DISCHARGE PIPES; CORRECT VIOLATIONS AND SUBMIT THE CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/08/2020BODY DRAINS ON SAFETY VALVES MISSING DISCHARGE PIPES; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB10/08/2020BURNER FLAME OUT NOT OPERATING AUTOMATICALLY-BODY DRAINS ON SAFETY VALVES MISSING DISCHARGE PIPES; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTIONNothing owed — awaiting certificate of correction
ECB09/01/2020ELEVATOR OUT OF SERVICE, RETURN BACK TO SERVICENothing owed — awaiting certificate of correction
ECB09/01/2020ELEVATOR OUT OF SERVICE, RETURN BCK TO SERVICENothing owed — awaiting certificate of correction
ECB08/31/2020NO DOOR LOCK MONITORING INSTALLEDIN CONTROLLER AS MANDATED IN3.10.12 OF APPENDIX K OR THE 2014 BUIDLING CODE. REMEDY: INSTALL DLM, FILE, AND PERFORM TEST WITH NYC DOBNothing owed — awaiting certificate of correction
ECB08/07/2020UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. RESTORED TO SERVICE IMMEDIATELY AND CONTACT DOBNYC FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB08/07/2020NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFORNothing owed — awaiting certificate of correction
ECB08/07/2020UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDOB FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB03/16/2020CAR GATE DAMAGED REPAIR HOLES( CU ) . PROVIDE MISSING INTERLOCKS COVERS IN THE HOISTWAY.Nothing owed — awaiting certificate of correction
ECB03/16/2020UPON INSPECTION THE DEVICE WAS FOUND TO BE OUT OF SERVICE . RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB03/16/2020DOOR ZONE RESTRICTOR NOT WORKING( CU ). NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY.Nothing owed — awaiting certificate of correction
ECB10/17/201997X10: 97X10 - ENTIRE DEVICE INOPERATIVE RESTORE TO SERVICE IMMEDIATELYNothing owed — awaiting certificate of correction
ECB04/11/2019UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT MATERIALS, APPARATUS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED ON ROOF TOP EXHAUST DISCONNECT INACCESSIBLE DUE TO RUSTED BOLT AND NUT, ON 4TH FLOOR BREAKENothing owed — awaiting certificate of correction
ECB04/11/2019FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 4/11/2019 AT ABOVE ADDRESS INADEQUATE FIRE PROTECTION ON THE MEZZANINE LEVEL. REM: REPAIR AND OR REPLACE.Nothing owed — awaiting certificate of correction
ECB01/17/20195B10,RL59BB7,67X10,4B10. 5B10-CLOSE LARGE GAP IN BETWEEN THE TWO CAR DOORS. 59BB7-BRAKE MAINTENANCE TAG EXPIRED; 67X10-IN CAR PHONE NOT WORKING; 41B10-MACHINE ROOM DOOR NOT SELF CLOSING. THIS DEVICE WAS NOTNothing owed — awaiting certificate of correction
ECB01/17/20195B10,52K2,59M7,67X10,41B10. 5B10-CLOSE LARGE GAP IN BETWEEN THE TWO CAR DOORS. 52K2-HOIST ROPES RUSTED CLEAN AND MONITOR CODITION; 59M7-BRAKE MAINTENANCE TAG MISSING; 67X10-IN CAR PHONE NOT WORKING. 4110-MACHINothing owed — awaiting certificate of correction
ECB03/08/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON THE 6TH FLOOR STAIR "A" BULKHEAD SPALLING PLASTER THROUGHOUT BULKHEAD WALLS AND CEILING HOLE IN CEILING APPROX 18"AT THE CORNER DUE TO WATER PENNothing owed — awaiting certificate of correction
ECB03/08/2018FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.OBSERVED ON ALL FLS IN STAIRWELL NO HANDLES ON THE SITE (DRAIN) VALUES, & IN THE KITCHEN IN THE CELLAR A FIRE SPRINKLER HEAD INSTALLED LESS THAN 4 INCHES NEXT TNothing owed — awaiting certificate of correction
ECB11/21/201740Q7,44Q7. (40Q)UNGUARDED SHAFT OPEN, PROVIDE CLOSURE. (44Q)TRACTION SHEAVE UNGUARDED, PROVIDE.Nothing owed — awaiting certificate of correction
ECB09/10/2017FAILURE TO MAINTAIN BUIDLING IN CODE COMPLIANT MANNER;NO FIRE STOPPING PER BC 712.3;27-345 NOTE: MAIN ELECTRICAL ROOM HOLES IN WALL.REMEDY: PROVID/MAINTAIN FIRE STOPPINGNothing owed — awaiting certificate of correction
ECB09/01/2017FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER; FAILURE TO COMPLY WITH LAW FOR DRAINAGE SYSTEM PER PC 702.1;27.911. OBSERVED TWO SINK IN THE KITCHEN IN THE CELLAR NOT INSTALLED WITH INDIRECT WAS AS ISNothing owed — awaiting certificate of correction
ECB03/23/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED ON 3/23/17 IN FIRE PUMP ROOM OS AND Y VALVE IS MISSING CHAIN (BUT IS IN THE OPEN POSITION). RMDY: REPAIR AND/OR REPLACE. PHOTOS TAKEN.Nothing owed — awaiting certificate of correction
ECB07/19/2016FAILURE TO MAINTAIN BLDG CODE COMPLIANT. NOTED: @ BULKHEAD 6A, 6C, SPALLING/BROKEN/OPEN CEILING W/ AREA CRUMBLING. REM: COMPLY W/ CODE, REPAIR CEILING.Nothing owed — awaiting certificate of correction
ECB02/01/2016OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS.NOTED:COFO #45506 ISSUED ON 4/10/1956 INDICATE CEL LAR TO BE ENGINE,FUMIGATION AND STORAGE ROOMS.CELLAR IS NOW OCCUPIEDNothing owed — awaiting certificate of correction
ECB02/01/2016FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDOR.NOTED: DEFECTIVE EMERGENCY LIGHTING AT 1ST FLR STAIR "B", 2ND FLR STAIR "C" AND BANothing owed — awaiting certificate of correction
ECB02/01/2016EXIT DOOR NOT SELF-CLOSING.NOTED: EXIT DOOR AT 4TH FLR STAIR"B",3RD FLSTAIR "B",BASEMENT (KITCHEN) AND SUB CELLAR (BOILER ROOM) DOORS NOT SELF CLOSING. RMDY: REPAIR/REPLACE DOOR.Nothing owed — awaiting certificate of correction
ECB07/12/2002FAILRU TO FILE AN AMENDED ROUND FIVE REPORT ACCEPTABLE TO THIS DEPARTMENT PURSUANT TO RULE R.C.N.Y 32-03B(5), INDICATING CORRECTION OF HAZARDOUS CONDITIONS DESCRIVED IN INITAL LL11/98. REMEDY: FILE AN AMENDED RNothing owed — awaiting certificate of correction