DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
DOB11/14/2025VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
ECB04/17/2026REISSUE ON ECB#35719765R FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT EXPOSURES#4 & #3 AND #1 SPALLING MISSING CHUNKS OF CONCRETE AND VERTICAL CRACKS ON PERIMETER RETAINING WALL OBSERVED UPON INothing owed — awaiting certificate of correction
ECB04/17/2026REISSUE ON ECB#35684961R FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:SPALLING PLASTER AND CRACKS ON BULKHEADS C AND E DUE TOWATER PENETRATION AND/OR LEAKS FROM ON TOP OF ROOF BULKHEAD AND FAULTYNothing owed — awaiting certificate of correction
ECB04/17/2026REISSUE ON ECB#35719763N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY ILLUMINATION DISCHARGE AND EXIT BONothing owed — awaiting certificate of correction
ECB04/17/2026REISSUE ON ECB#35719766Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FIRE RATED CLASSROOMS AND SMOKE DOORS NOT SELF-CLOSING DUE TO BINDING MISSING AND ON FAULTY HARDWARE IN CLASSROOMS 430,431,42Nothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35684959H DATE OF ISSUE: 09-26-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 4TH FLOOR ROOM-419 WATER PENETRATION AT CEILING. REMED: REPAINothing owed — awaiting certificate of correction
ECB07/11/2025EXIT DOOR NOT SELF-CLOSING PROPERLY AT THE TIME OF INSPECTION. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 1ST FL EXITB 3 AND 4, 3 EXIT DOOR, AT 1ST FLOOR EXIT-2 ONE EXIT DOOR(INSIDE) AT 1ST FLOOR AUDITORIUNothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35684957Y DATE OF ISSUE #09-26-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER AT THE TIME OF INSPECTION OBSERVED AT 4TH FLOOR ROOM 457, 459, 460, 422 AT 3RD FL. 303, 352, 359, 2ND FL. 262Nothing owed — awaiting certificate of correction
ECB07/11/2025REISSUE #35684960P DATE OF ISSUE: 09-26-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGESAND PUBLIC CORRIDPRS PER BC 1006.1; 27-381. AT 1ST FLOOR PLAY ROOM(OLDNothing owed — awaiting certificate of correction
ECB06/12/2025REISSUE #35684958X DATE OF ISSUE: 09-26-2024. FAILURE TO MAINTAIN BUILDING WALL(S) OR A APPURTENANCES. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT EXPOSURE 4(LEFT) AND EXIT-1 RETAINING WALL CRACKED AND BULGNothing owed — awaiting certificate of correction
ECB09/26/2024REISSUE#35663422P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED AT 4 FLOOR ROOM 419 WATER PENETRATION AT CEILING.REM:REPAIRAND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB09/26/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED AT BULKHEADS STAIR C AND E CRACKS AND SPALLING.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB09/26/2024REISSUE#35676306K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES,AND PUBLIC CORRIDORS PER BC 1006.1;27-381.OBSERVED 3 FLOOR GYM ENTRANCE,BOX#2,4,19,24,27,AUDITORIUMNothing owed — awaiting certificate of correction
ECB09/26/2024REISSUE#35663424Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED AT 4 FLOOR ROOM 457,459,460,422,3 FL 303,352,359,2 FL 262,1FL AUDITORIUM.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB09/26/2024REISSUE#35663423R FAILURE TO MAINTAIN BUILDING(S)OR APPURTENANCES.OBSERVED AT EXPOSURE 4(LEFT)AND EXIT 1 RETAINING WALL CRACKED AND BULGING LOOSE CONCRETE.REM:REPAIR AND/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB07/03/2023REISSUE #35655464N DATE OF ISSUE: 06.27.22 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED THAT AT 4TH FLOOR 402, 403, 411, 459, 460, 420, 421, 422, 423, 424,Nothing owed — awaiting certificate of correction
ECB07/03/2023REISSUE #35655472N DATE OF ISSUE: 06.27.22 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. AT THE TIME OF INSPECTION OBSERVED THAT ON WEST ELEVATION CRUGER AVENUE, RETAINING WALL HAS VERTICAL CRACKS & SENothing owed — awaiting certificate of correction
ECB07/03/2023REISSUE #35655474R DATE OF ISSUE:06.27.22 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AT THE TIME OF INSPECTION OBSERVED THAT AT 4TH FLOOR ROOM 419 WATER PENETRATING THROUGH CEILING DAMAGING CEILING BNothing owed — awaiting certificate of correction
ECB07/03/2023REISSUE #35665101N DATE OF ISSUE: 06.27.22 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381. AT FIRST FLOOR AUDITORIUM 3 EMNothing owed — awaiting certificate of correction
ECB06/27/2022FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORRIDORS PER BC1006.1;27-381.NOTED:OBSERVED@1FL-AUDITORIUM&(BRADY)LUNCHRM BY EXIT2 EXISTING EMERGENCY LIGHTS ARENTNothing owed — awaiting certificate of correction
ECB06/27/2022REISSUE35586640R-FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES.NOTED:OBSERVED@EXP2/CRUGERAVE&EXP1/BRADYAVE-RETAINING WALLS HAS VERT CRACKS&SEVERAL STEP CRACKS THRUOUT ENTIRE RETAINING WALLS.MAINTAIN EXT BLDNothing owed — awaiting certificate of correction
ECB06/27/2022REISSUE35586639J-FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED:OBSERVED NUMEROUS CLASSRM DOORS@VARIOUS LOCATIONS OF ALL 4FL OF BLDGARE DEFECTIVE DUE TO MISSING &OR DAMAGED (SELFCLOSER) HARDWARE.REPAIRNothing owed — awaiting certificate of correction
ECB08/25/2021RE-ISSUE #35498597K FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGE & CORRIDORS PER BC1006.1,27-381.NOTED:UPON INSPECTION OBSERVED EMERGENCY LIGHTING AT BLDG #600 BY ROOMNothing owed — awaiting certificate of correction
ECB08/25/2021RE-ISSUE #35557803J BLDG OR OPEN LOT OCCUPIED W/OUT A VALID CERTIFICATE OF OCCUPANCY.NOTED:UPON INSPECTION OBSERVED,AT EXP.#3 REAR YARD HAS 2 TEMP BLDGS OCCUPIED & USED FOR CLASSROOMS.BLDGS WERE ERRECTED UNDERNothing owed — awaiting certificate of correction
ECB08/25/2021RE-ISSUE #35498591J FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.NOTED:UPON INSPECTION OBSERVED ON 4TH FL,ROOMS #403,407,411,459,460,420,421,422,423,424,425,402,431,430,452.ON 3RD FL,ROOMS #313A,357,309,35Nothing owed — awaiting certificate of correction
ECB09/18/2020REISSUE#35498587R BUILDING OR OPEN LOT OCCUPIED W/O A VALID C OF O. NOTE:OBSERVED AT EXP-3 YARD 2 TEMP CLASSROOMS BLDGS HAVE BEEN INSTALLED UNDER APP#200391307 APPROVED ON 8/20/97,BUT THE JOB HAS NOT BEEN SIGNENothing owed — awaiting certificate of correction
ECB06/10/2020FAILURE TO MAINTAIN BLDGS WALLS & APPURTENANCES. NOTED: OBSERVED RETAIING WALL AT WEST ELEVATION W/VERTICAL CRACKS & MULTIPLE SPIDER CRACKS THROUGHOUT. REMEDY: MAINTAIN EXTERIOR BLDG WALL.Nothing owed — awaiting certificate of correction
ECB06/10/2020FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: OBSERVED CLASSROOM DOORS AT 4TH FL ROOMS 403,407,411,459,460,420,421,422,423,424,425,3RD FL ROOMD 313A,357,309,356,2ND FL,256A,256B,207,260 BR,262,261,Nothing owed — awaiting certificate of correction
ECB02/16/2011TWO 1 STY TEMP CLASSROOM UNITS IN USE W/O A VALID C/O. NB 200391307 (1997). REMEDY: OBTAIN A VALID C/O.Hearing held — result not yet published
ECB06/17/2010REISSUE 34760719Y NEW BLDG OR OPEN LOT OCCUPIED W/O A VALID CERT OF OCCUPANCY NOTED JOB#200391307 FOR 2 TEMPORARY CLASS ROOM UNITS NOW OCCUPIED W/O A TEMPORARY CERT OF OCCUPANCY OR A SIGN OFF REM: OBTAIN A VALINothing owed — awaiting certificate of correction
ECB02/03/2009NEW BUILDING OCCUPIED W/O A VALID C OF O APPLICATION #200391307 FOR 2 TEMPORARY CLASSROOM UNITS NOW OCCUPIED WITH NO TCO OR FINAL SIGN OFF. REMEDY: OBTAIN TCO OR FINAL SIGN OFF FORTHWITH.Nothing owed — awaiting certificate of correction