ECB01/02/2025OBSERVED IN THE BASEMENT/CELLAR NO VENTILATION IN THE GAS METER ROOM. AS PER E 4 OF THE FUEL GAS CODE GAS METER ROOM SHALL BE PROPERLY VENTED., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB12/05/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE).OBSERVENothing owed — awaiting certificate of correction
ECB12/05/2024EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS AT BASEMENT LEVEL. IN AN EMERGENCY NON CLOSING DOORS MAY AID A FIRE OR SMOKE HAZARD., REPAIR/REPLACE DOORNothing owed — awaiting certificate of correction
ECB12/05/2024FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED OBSTRUCTED EXITS DOORS PASSAGEWAY AT EXPOSURE 2. IN CASE OF EMERGENCY ALL PASSAGE WAYS MUST BE UNOBSTRUCTED., REMOVE OBSTRUCTIONNothing owed — awaiting certificate of correction
ECB12/05/2024FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ACTIVE LEAK IN GAS METER ROOM. POTENTIALLY A FALL HAZARD., REPAIR AND/REPLACENothing owed — awaiting certificate of correction
ECB11/20/2024OBSERVED RUSTED AND CORRODE GAS PIPE IN GAS METER ROOM LOCATED AT BASEMENT/CELLAR. AS PER 102.3 OF THE PLUMBING CODE MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PNothing owed — awaiting certificate of correction
ECB11/20/2024OBSERVED 1 PAINTED SPRINKLER HEAD ON THE 2ND FL AND MULTIPLE PAINTED SPRINKLER HEADS ON THE 1ST FL. ALSO OBSERVED SPRINKLER HEAD ON 4TH FLOOR TO CLOSE TO LIGHT FIXTURE. AS PER 102.3 OF THE PC, INSTALLATIONS BOTNothing owed — awaiting certificate of correction
ECB01/12/2022AT ROOF LEVEL LARGE SECTION OF COOPER FLASHING HAS RIPPED OFF AND IS HANGING ON ROOF, ALSO SMALLER PARTS OF FLASHING HAVE COME OFF ALONG WALL., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/12/2022I DID NOT OBSERVE ANY FRESH AIR VENTILATION IN THE GAS METER ROOM., REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB01/08/2022UNLAWFUL ACTS FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP MADE TO CORRECT OR CERTIFY ECB #35583848M #35290291P.REMEDY:COMPLY WITH COMMISSIONER'S ORDERS.Nothing owed — awaiting certificate of correction
ECB11/26/2021UNLAWFUL ACTS.FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP WAS MADE TO CORRECT OR CERTIFY ECB #35583953Y & #35290291P.REMEDY:COMPLY WITH COMMISSIONER'S ORDERS.Nothing owed — awaiting certificate of correction
ECB08/24/2021AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS#35290291P ISSUED ON 08/30/2017,FOR ELECTRICAL WORK WITHOUT A PERMIT.REM:COMPLY WITH EC CODE.Nothing owed — awaiting certificate of correction
ECB01/22/2021FEDERAL FST-125 HFT STEAM BOILER FTMNothing owed — awaiting certificate of correction
ECB09/26/2018OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION. NOTED:OBSERVED AT 1ST FL-CAFETERIA/DINING AREA ARRANGED W/ TABLES AND CHAIRS FOR THE ACCOMODATION OF 112 PERSONS, POSTED SIGNAGE INDICATENothing owed — awaiting certificate of correction
ECB03/09/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED THROUGHOUT CELLAR AT VARIOUS LOCATIONS-WATER PENETRATION WATER ENTERINGBUILDING THROUGH WALLS AT CELLAR AND POOLING ON THE GROUND WITHIN ELECNothing owed — awaiting certificate of correction
ECB03/09/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:OBSERVED EXISTING EMERGENCY LIGHT PACKAGES AT 4TH FLOOR STAIR G 2ND FLOOR STAIR GNothing owed — awaiting certificate of correction
ECB01/25/2018UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. INAUGUST 30,2017 AN ELECTRICAL VIOLATION WAS ISSUED TO THE RESPONDENT. THE RESPONDENT FAILED TO COMPLY WITH (NYC).ELECTRICAL CODE #27-3018(B)Nothing owed — awaiting certificate of correction
ECB01/24/2018FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35290314Z ISSUED ON 08/30/17 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01.IN CHILLAR APPROXIMATELYNothing owed — awaiting certificate of correction
ECB01/24/2018FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35290312P ISSUED ON 08/30/17 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01.ON FLOORS PRESSURE GAUGENothing owed — awaiting certificate of correction
ECB11/24/2017FAILURE TO COMPLY WITH THE COMMISSIONR'S ORDER CONTAINED IN SUMMONS/VIOLATION #35290312P ISSUED ON 08/30/17 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 OBSERVED ON ALL FLOORS PRESSURE GAUGES INNothing owed — awaiting certificate of correction
ECB11/24/2017FAILURE TO COMPLY WITH THE COMMISSIONR'S ORDER CONTAINED IN SUMMONS/VIOLATION #35290314Z ISSUED ON 08/30/17 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1AND 1RCNY102-01.OBSERVED IN CELLAR APPROXINothing owed — awaiting certificate of correction
ECB08/30/2017FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED IN CELLADR APPROXIMATELY 100 FEET OF CONDENSATE RETURN LINE INSTALLED THAT DOB RECORDS DO NOT INDICATE THAT IT WAS TESTED. PHOTO TAKEN. REM: PERFONothing owed — awaiting certificate of correction
ECB08/30/2017WORK WITHOUT A PERMIT. OBSERVED ON ALL FLOORS PRESSURE GAUGES INSTALLED AT THE FLOOR CONTROL VALVES FOR THE FIRE SPRINKLER SYSTEM WITHOUT A PERMIT.REMEDY:OBTAIN ALL REQUIRED PERMITS.Nothing owed — awaiting certificate of correction
ECB08/30/2017ELECTRICAL WORK W/OUT A PERMIT OBSERVED IN BSMT:THE ELECTRICAL INSTALLATION OF POWER FEEDERS,BRANCH CIRCUIT WIRING,PANELS & TRANSFER SWITCHES TO PROVIDE POWER TO BLDG FROM A BACKUP POWER GENERATOR PRIOR TO OBTANothing owed — awaiting certificate of correction
ECB08/30/2017FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTS. OBSERVED ON ALL FLOORS PRESSSURE GAUGES INSTALLED ON THE FLOOR CONTROL VALVES FOR WHICH DOB RECORDS DO NOT SHOW THAT ANY TEST WAS DONE. PHOTO TAKEN. REM: PENothing owed — awaiting certificate of correction
ECB08/30/2017FAIL TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC 102.3; 27-902. OBSERVED ON ALL FLOORS AT THE FLOOR CONTROL VALVES FOR THE FIRE SPRINKLER SNothing owed — awaiting certificate of correction
ECB08/30/2017WORK WITHOUT A PERMIT. OBSERVED IN CELLAR APPROXIMATELY 100 FEET OF CONDENSATE RETUREN LINE WITHOUT A PERMIT WAS INSTALLED.REMEDY:OBTAIN ALL REQUIRED PERMITS.Nothing owed — awaiting certificate of correction
ECB03/23/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED ON 3/23/17 NO GAUGE ON SPRINKLER BRANCH MAIN. RMDY: REPAIR AND OR REPLACE.Nothing owed — awaiting certificate of correction
ECB03/23/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT CELLAR LEVEL OBSERVED WATER PENTRATING AT VARIOUS LOCATIONS THROUGHOUT CELLAR TO WATER PENETRATION COMING IN THROUGH WALLS AT BOILER ROOM & STORAGENothing owed — awaiting certificate of correction
ECB03/23/2017DRIPS - FUTURE GAS CONNECTION EXIST DOWN STREAM OF APPLIACNE. OBSERVED3/23/17 ON CELLAR LEVEL FUTURE GAS CONNECTION EXIST. RMDY: COMPLY WITH SUMMONS. PHOTOS TAKEN.Nothing owed — awaiting certificate of correction
ECB03/23/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC 102.3; 27-902. OBSERVED ON 03/23/2017 IN CELLAR FERNCO COUPLINGS AS WELL AS JIM CAPS INNothing owed — awaiting certificate of correction
ECB07/12/2016OPERATING A PLACE OF ASSEMBLY W/OUT A C OF OPERATION. REISSUE#35171406Y, 1ST FLR CAFETERIA ARRANGED W/ TABLES & CHAIRS TO BE OCCUPIED FOR 112 PERSONS W/ POSTED SIGN FOR 195 OCCUPANCY. NO APPLICATION OR CERTIFICNothing owed — awaiting certificate of correction
ECB02/04/2016OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION. NOTED: OPERATING 1ST FLR CAFETERIA W/MAXIMUM OCCUPANCY 135 PERSONS (POSTED) W/O A CURRENT CERTIFICATE OF OPERATION.RMDY:OBTAIN A PLACE OFNothing owed — awaiting certificate of correction